Fraktal/AB - starting a new station

Updated 2026-10-05 through press75 fit, Line verification, shared HMI detail-read repair and press78 configuration memory reduction; 2026-10-06 adds where retained data lives and the missing-features handover. This guide explains how to apply the binding; Part III is normative. Read AGENTS.md, the AB README and the relevant Core clauses before editing. One committed declaration is the source; the L5X is output, never hand-edited. This guide replaces superseded build-by-build advice; historical evidence remains unchanged.

The port is not complete apart from power. Main press operation and Phase 0-6 features are verified on the named press68 deployment. Signal tower remains absent; optional local Part traceability, host events and nameplates have compiler/model proof and local Echo lifecycle/recovery acceptance, while device host/carrier integration and other optional profiles or probes remain unclaimed. Line owner/weekly shifts are loaded in press75; press72 failed linking at LineValidate and press73 failed with a final global memory error. The owner confirms press75 completed download at 0/0 and Run; native/browser/retention acceptance is recorded separately. Press69 added model creation/current export and scoped air Start away from Changeover, but owner Studio Verify refused nested array subscripts. Corrective press70 has owner-confirmed completed-download fit and eleven restored native regression suites (159 rows). M-101 export/live repository read pass; Chrome acceptance and physical model/download retention remain separate. See section 7 and the TC3 handoff.

Reference State
Bench 1769-L24ER-QB1B, firmware 33.014, 192.168.100.89, serial 7036B510
Successful loaded / memory baseline C:/work/press75.L5X; SHA-256 82AB065C32BCD112D49DD00839B8047C1B5E957A5356FB9D61EF3C1C2F3172A5
Coherent native manifest 94E302F650BA1DB5 / revision 9757442, major 4 / binding 2, 65,552 bytes
Online data/logic memory 758,568 / 786,432 bytes; available 27,864, largest free block 27,376 (owner Studio screenshot)

These are reference measurements, not acceptance for another controller/cabinet. Never advance the loaded or memory baseline on generation or Verify alone. The 2026-10-05 guarded read now sees the Calendar V3 contract 026DC8F584CA2D70 / 159176, matching prepared press76. It does not identify private code or supply a new Studio Capacity/download record. Press75 remains the last owner-accepted memory measurement. Press77 subsequently failed global linking with a 799,860-byte offline data/logic estimate (13,428 over capacity). Press78 is the current prepared correction; the owner reports “its good now” and requests commit/push, without exact-artifact download or new Capacity data. See correction evidence.

1. Two questions, asked before anything else

Section titled “1. Two questions, asked before anything else”

For v38 continuation, first read the native-feature overlap audit. Every proposed runtime service names the native counterpart and records why to reuse it, adapt/project it, or retain the existing contract owner. Studio version alone does not establish the controller family’s or Echo’s capabilities.

The L81E/v38 native compiler evidence records exact attribute widths and spellings: MaxInterval/MinInterval are accepted; MaximumInterval is rejected; ForceStatus requires an empty instance. These are compiler results, not physical module or runtime clock acceptance.

The shared HMI Settings shows the active PLC/gateway endpoint, including the native runtime port, without URI credentials. Check it when two controllers publish the same station name. A gateway URL identifies the gateway service; confirm its configured controller, route and serial independently. Disconnect and Connect use the connection owner and do not issue an equipment command.

The gateway fieldbus view reads controller input/output process-image words. Good output quality establishes a valid sample, not electrical actuation or permission to move. Input and output validity are independent, and both require known fault data. An incomplete module sample keeps the node offline while valid channel samples remain available; failed samples withdraw quality and output forcing. This does not replace the still-provisional module-object connection-state work in Part III AB §10.

Ask the project owner and record both answers in the station binding record:

  1. Read-only or write-enabled? The gateway defaults to no write root and refuses mutations. Complete inert QUERY_CONFIG batches may use the mailbox for read pages without granting mutation authority. Enabling writes arms Core section 14: authenticated principals, least privilege, no anonymous write. Transport authentication and PLC operator authorization are separate layers.
  2. Which controller baseline? Prefer firmware v37+ on a CIP Security-capable family. Measured v33 L24ER uses the legacy zone-and-conduit posture. Repeat S2/S4/S11/S12 on another family/revision; do not assume types, security, connection sizes or scan/read budgets transfer.

Controller-changing actions require current explicit authorization and an exact serial/target check immediately before use. Import/Verify/download are the owner’s licensed-desktop steps. An agent does not start a write-enabled gateway or infer authorization from a previous deployment.

The generator derives lifecycle, PLCopen handshake/Execute-drop reset, pending step diagnosis, controller alarm active/history/reset classes, per-step history, active cursors/annotations, counts, cycle/command timing, OEE buckets, ConfigPersist reporting, self-description and the closed command mailbox from one valid declaration. The runtime base owns common behavior once. MachineState is derived by projection, not latched in a client.

Events, visited steps and completed-command timing belong on the PLC: polls can miss transitions shorter than their interval. The generic HMI renders the contract, without per-station screens. ConfigPersist reporting alone does not establish physical durability for every value or across an upgrade.

Copy fraktal_ab_station_template.py. It includes Phase 0-6 basics, station sets, value classes and an empty user provider. Its two-model catalog is static (model_capacity=0); creation is an additional choice, not already on in every copied template. Remove absent capabilities instead of publishing placeholders.

Feature Declaration / requirement
CONTINUOUS / SINGLE_STEP / HOLD_TO_RUN run_styles=decl.RUN_STYLES; non-safety step pacing
OEE Performance decl.ideal_cycle_ms(...), ideal_cycle_member; measure against actual cycles
Degradation watch decl.baseline_work_ms(...), baseline_work_member; registered reason; zero disables per model
Derived state flags state_flags=(decl.StateFlag(...),); at most 12; compute every scan
System health decl.SystemHealth.for_task(period_ms) and registered reasons
Start / direction permits start_permits, module permits; one report and action predicate
Manual / Changeover manual mode + actual command catalogue; models/default + CHANGEOVER chain
I/O / forcing io_modules; electrical identity once; safety/control-power coils never forceable
ST/SFC/LD one graph, generated renditions; selector is harness-only and exists only for several; carry one where memory is short (the press ships AUTO in LD only since press80)
Capture / named sets decl.capture(...), config_sets=True; typed capabilities and PARAMETER_SETS reasons
Retained-data medium / live documents config_medium=decl.ConfigMedium(live_documents=...); file medium; live documents need a write-enabled gateway, the access provider and a seeded first image; press79 prepared offline, fit/retention are owner gates
PLC users / data classes access_users, data_classes, decl.config_access(...); provision before tightening policy
Shelving eligible rationalized events; blocking semantics unchanged
Runtime model creation model_capacity=N, seeds and sets; seed count <= N <= 8; press70 owner-created M-101/native bank and duplicate refusal verified
Current-value export sets enabled; native read permission checks; no saved slot
Line owner / weekly shifts optional fraktal_ab_line.Line(...), access provider and sets; press75 fit and 17 native calendar/end rows pass; Chrome/physical retention remain separate
Freshness/read budget read_budget=decl.ReadBudget(...); actual target measurements

The press task is 10 ms. Require synchronization/fieldbus capabilities only where commissioned; an unavailable required probe must be explained, not faked.

Run commands from FraktalCore/PLC/Allen-Bradley/tools unless stated otherwise.

Terminal window
Copy-Item fraktal_ab_station_template.py fraktal_ab_MyStation.py
$env:FRAKTAL_AB_DECLARATION = 'fraktal_ab_MyStation'

Edit this copy, never a generic tool. Name modules as the schematics do; reserve the project reason band; declare records/capabilities, reusable module types, I/O identity and complete mode graphs. Defaults match ParCfg. SchemaVersion is first; persistent/published changes need versioning/migration. Pass the same selection to gateway and harnesses. Fixed press fixtures refuse other stations; write a bounded fixture for the actual declaration instead of substituting IPs.

Terminal window
python -B -m unittest discover -s . -p 'test_*.py'
python -B ../../../../tools/check_consistency.py

From the repository root also run python -B -m unittest tools.test_check_consistency. Adapt TemplateTests from test_fraktal_ab_station.py; catalogue every key (check_consistency.py --emit prints missing stubs). Execute generated ST and semantic mutants, not only source-presence checks. Use -B and fresh bytecode caches: an old same-size mutant .pyc once survived restoration. Run shared HMI/transport checks when those change. Native compile is a separate gate.

Terminal window
python -B fraktal_ab_generate.py <seed.L5X> <stationNN.L5X>

Seed controller/type revision must match. Generation refuses existing outputs; keep named builds and JSON. Record L5X SHA-256, ContentHash, manifest bytes, capacities and GeneratedSize; regenerate byte-identically. ContentHash covers contract and native mailbox/catalog profiles, not every logic/private-storage change. Equal hashes alone do not identify identical builds. Never patch L5X.

For an upgrade, validated --initial-config <image.json> carries configuration, recipe banks and active ordinal. An expanded runtime catalog also requires modelCodes: an ordered list matching every bank, bounded by declared capacity. The original seed codes must keep their ordinals; added codes are unique, printable ASCII of 1-80 characters. Complete typed/schema/range and active-bank validation happens before output. Omit modelCodes only for legacy seed-only images. The helper seeds the already-declared catalog; it adds no PLC storage. Capture twice under exact serial/build guards and require identical values; recapture immediately before generating a later upgrade. Credentials, sessions and command latches are excluded and need their own migration procedure. See the catalog-image proof. A live-document station needs a seed only for its first live-document image; the gateway restores later downloads from its documents (Part III AB §3.8b).

The owner imports, runs Verify Controller, completes the download, then restarts the existing gateway with the same declaration and approved security settings:

Terminal window
python -B fraktal_ab_gateway.py <ip> --expect-serial <serial> --port <port>

Preserve write-root/origin/authentication; never echo tokens. Do not bypass hash/capacity mismatch. A gateway needed before download must run from a worktree at the loaded build’s commit. A canceled download proves no new state.

On the reference Windows bench, gateway 127.0.0.1:8099 and Caddy HTTPS/WSS are separate processes. Starting only the gateway does not start press.localhost. The owner’s hidden sign-in launcher uses the existing config/certificate store:

Terminal window
powershell.exe -NoProfile -ExecutionPolicy Bypass -File C:\work\caddy\Start-WebProxy.ps1

HTTPS 401 proves reachability/authentication, not PLC readiness. The plaintext loopback-upstream warning is expected behind this same-host TLS proxy. Verify served asset hashes; Ctrl+Shift+R reloads Chrome. See reboot recovery.

If Configuration disappears, inspect manifest hydration before changing tab visibility or access rules. Press75 publishes 22 configuration entries (four model, five station, thirteen Line); the shared client previously rejected anything over TwinCAT’s 16-entry window. Page capacity belongs to the binding: validate the count against the freshly read discovered rows, require complete Scope/Item/ValueText and reject duplicate slot aliases. Do not raise a global constant or allocate a larger PLC buffer to repair this client assumption. Typed Boolean read text 0/1 is normalized to FALSE/TRUE by the shared manifest mapper; write validation remains unchanged. This correction is HMI-only; no PLC download or gateway source change is needed. See configuration-page evidence.

4.5 Verify on the controller, and record it

Section titled “4.5 Verify on the controller, and record it”

Read manifest with fraktal_ab_manifest_read.py <ip> --expect-serial <serial>, then healthz/livez/readyz and read-only S3. Compare coherent full readback, hash/capacities. Authorized write fixtures need exact guards, an explicit arm, bounded waits, finally restoration, independent final readback and disarm. Cancel/disconnect never authorizes replay. Prove actions with actual command counts/end positions: ACKs or step traces can pass while a stroke was skipped. Wait on stable levels/counters instead of short-lived flags. Preserve failures. Isolate direct native fixtures from HMI tabs: a separate process is outside the production gateway’s mailbox lock. Each direct command reads the settled request/ACK cursor afresh, stages arguments, then refuses a changed cursor before committing. An old ACK is not proof of a new command. Login must settle with its own LoginResultSequence. Program mode leaves the task stopped and can cause a login timeout. Start a watchdog stopwatch before its command/setup reads, and also verify the controller’s elapsed timer; those reads consume real time. Append .md/.json evidence; never edit an old result to match a new build.

Logix v33 contract members are DINT (including 0/1 flags). Do not use unmeasured BOOL layouts or TRUE/FALSE tag references. ST string literals are replaced by numeric keys at projection. AOIs cannot reach controller scope. Mode ordinals are AUTO 0, MANUAL 1, HOME 2, CHANGEOVER 3. Durations respect task period. Scalable checks use bounded loops/one term per statement within operator limits. Resolve an indirect array index into existing scalar scratch before indexing: Studio v33 rejected Levels[Staged.Ordinal[Index] - 1] in press69. Keep the ordinal bounds and data permissions; do not unroll the checks to avoid syntax. Read structures via dimension-aware read_layout, not member-by-name shortcuts that break when arrays move offsets. Chart steps <=32 and state flags <=12.

Start consumes the release report the HMI explains. Project entry permits may use decl.Permit(..., modes=(MODE_AUTO, MODE_HOME)). Press70 removes air only from Changeover’s Start set; cylinders retain pressure/directional permits.

Fields/Localization reserve follows rows plus eight rows of headroom in eight-row blocks, with 768 ceilings and a 102,400-byte whole budget. Generation refuses truncation. Empty reserve costs memory. Press57/65 exhausted Verify memory; press66 passed Verify but failed link/download. Share routines/scratch instead of unrolled copies. The press ceiling stays four users; TC3 need not inherit that limit.

On divided-memory controllers, record both areas using Controller Properties → Capacity → Estimate after importing and verifying the exact offline artifact. See Rockwell’s offline memory procedure. The owner reports press73 at 799,428 maximum estimated data/logic bytes against 786,432 total: 12,996 over. I/O uses only 2,640 / 1,048,576; spare I/O capacity does not resolve this data/logic limit. Press75’s completed download passes; online used/max is 758,568 / 786,432 with 27,864 available and largest free block 27,376. The estimate and online use have different measurement bases. Record a new Estimate before the next larger artifact, then require completed linking and native timing. A source reduction does not predict compiled saving.

From the repository root:

Terminal window
python -B FraktalCore/PLC/Allen-Bradley/tools/fraktal_ab_generated_size.py C:\work\press75.L5X --baseline C:\work\press70.L5X

Press70 adds 2,700 declared bytes, 5,135 ST source bytes, 59 terminators and 54 lines over press68; RLL remains 20. The subscript correction adds zero data bytes, 50 ST source bytes and five statements/lines over refused press69. These trends exclude compiled code, AOI storage, metadata/reserve/unsupported layouts. Fit requires Verify and completed link; Press75 reduces declared data by 1,812 bytes, ST source by 30,972 bytes, terminators by 447 and lines by 413 over press70, preserving all three renditions. Owner-confirmed completed download establishes press75 as the current baseline. See native acceptance.

Table Static template rows/capacity Historical press68/70 Press75 rows/capacity
Fields 379/392 565/640 616/624
Localization 481/496 570/640 652/664

The current template also sizes other discovery tables from their rows, keeping one spare rounded to small blocks within each frozen ceiling. Modules/Nameplates share their capacity. Its manifest is 46,080 bytes (offline-tested); earlier 16/32 and 64-row policies measured 53,112 and 58,232 bytes. Press is 68,472 (press68 and press70 read back); press75 reads 65,552. The template needs its own native fit/live gates.

Structured Text layout and routine ownership

Section titled “Structured Text layout and routine ownership”

fraktal_ab_st_format.py owns emitted ST layout. The generator applies it at the serialization boundary to runtime AOIs, program routines and SFC actions/ conditions: four spaces per block, spaced operators/arguments, one instruction per line, separated CASE arms and advisory 120-column wrapping. Literals, operands and executable token order are preserved and checked. Fix the source or this formatter; never edit generated L5X or duplicate formatting rules in each feature. Frozen Phase 0 fixtures remain historical inputs.

scan_sections() owns the ordered scan plan and emits complete services once: access startup; mailbox frame/handler; restore before the scan increment; passive/commanded modules; Start; Unit and sequence dispatch; health; diagnostics and alarms; Line/statistics; then forcing under this scan’s permission verdict. The main routine calls each section once. ConfigWrite and ConfigSets run inside the mailbox’s existing authorized CASE arms; acknowledgement and secret wipe stay in the caller. LineStage shares calendar copying across individual writes, complete sets and calendar application, using the existing scratch.

Keep the AOI lifecycle at its owning level. Program services may use controller scope; AOIs cannot call those services. Extract whole blocks rather than moving RETURN/RTN/EXIT across boundaries. Share repeated behavior; do not split every small conditional into a new routine or add scratch solely for organization. Keep released names/layouts/ordinals and every rendition a chain declares intact. The inline scan/mailbox views are derived from the same plan for test execution; they are not a second authored implementation.

Press77 preserves every pre-existing executable token after expanding only the new service calls, plus AOI/RLL/SFC structure and all declared data/initializers. It adds zero declared data bytes and removes 28 ST terminators relative to press76. Formatting adds source whitespace; neither source size nor terminator count measures compiled memory. Additional routine metadata/JSR costs still need exact-artifact Studio Verify, Capacity Estimate, completed linking and native scan timing. The SDK attempt reports No valid license; the owner’s licensed desktop is the remaining native gate. See the linked cleanup evidence.

The subsequent press77 native download reaches compilation/linking but exceeds the controller’s data/logic area. Press78 preserves the organization while grouping identical immutable bounds/type/flag facts into multi-label CASE arms. Configuration snapshot SAVE/EXPORT selects the kind once and copies its fields once, including the selected inactive model; count is published after the copy. Commit addresses, access checks, staging, audit, ACK and secret wipe remain at their existing owners. No tags, types or reserves are added or removed. The emitted delta is -156 ST terminators and -12,373 ST source bytes versus press77. Boundary, address-isolation and snapshot tests plus 205 old/new execution comparisons check behavior. The owner reports resolution, but no new measured compiled-memory margin. Require that margin before further growth.

Treat source documentation as part of the target budget: Rockwell documents that embedded ST comments are downloaded into controller memory (SFC programming manual, page 67). This does not attribute the press77 excess to whitespace or quantify its cost. Share repeated executable behavior and fact selection; retain useful ownership comments without repeating every capability label. Record source, statements, data and native Capacity separately. See failure and correction.

The template has zero accounts, open thresholds and zero timeout. Register up to four before tightening policy. Use one PowerShell command:

Terminal window
& C:\work\venv_gw\Scripts\python.exe -B .\fraktal_ab_access_provision.py station_admin --level 4

Hidden prompts create a salted hash registration for the declaration, not a live PIN write. Replacing a user’s PIN row requires controlled deployment; no online SET_PIN exists. Never put PINs in argv/commits or copy bench accounts. Plan credential upgrades separately from physical-cycle retention.

PLC session/roles own every permission. Login ACK means consumed, not success; the HMI waits for the matching outcome/session, not old LoginFailed. Logout cancels pending work; read/list/export/release polling does not extend timeout. AB accelerates login using 256 gateway prefix hashes plus final PLC verification, retaining 257 iterations, role authority and eight SHA rounds per scan. Full native PIN clients remain supported. Protect/wipe prefixes like PINs. Measure before considering this platform optimization on TC3. See 16/16 access proof.

Use data_classes=(decl.DataClass('calibration', 'project.dataClass.calibration', read_level=0, write_level=3),) and decl.config_access(member, 'calibration', min_write_level=3). Up to eight stable class IDs; PLC combines class level with immutable value minimum. Corrupt/unknown policy requires ADMIN; SET_CLASS_LEVEL needs ACCESS_POLICY. Blank ClassId follows DATA_READ/DATA_WRITE. QUERY_CONFIG gives metadata but blanks unreadable ValueText. Loads validate all before commit; exports check all read permissions. SAVE/DELETE require CONFIG_SET alone, not permission to read fields of an opaque snapshot. The gateway never grants privilege. See 18/18 proof.

Resolve SourcePath + Description to exactly one live eligible event, not a recycled slot. Require permission/rationalization; reject foreign, duplicate, safety/unshelvable requests. Positive whole seconds <=8 hours; task-time expiry survives logout/calendar changes. Shelved blocking events still block Start; slot reuse clears state. Press67 15/15 and later regressions pass. See proof.

Press68 V3 native writes pass 17/17, all eleven regressions/restoration and S3 6/6 before/after. Frame arguments fit one connected 500-byte write (89 DINTs, 312 aggregate ASCII bytes), then Sequence last. Use mailbox.command_writes, not decoded scalar/string writes. Large sets retain separate staging. See native proof.

The press budget is 500 ms polling, 250 ms cache, 1,000 ms slow heartbeat, 2,000 ms Good / 3,000 ms expiry and 4,000-byte reads. Monotonic expiry advances during stalled RPC; partial ACK/detail cannot renew complete station health. Commands recheck freshness. Owner restart/browser acceptance and the 60-second production reader yielded 121 complete updates, no STALE/DOWN, max gap 790 ms. This qualifies S9 on press68 only, not press70/new targets. See live proof.

If cycle charts repeatedly fill then disappear while the link and mailbox ACK remain healthy, inspect detail-batch ages separately. On press75, reading all closed-tab history/sequence data plus an extra poll gap let chart batches leave the Good window. The shared HMI now requests only the selected tab’s visible, access-permitted cards/control bindings and renews bounded sweeps on their slow cadence. Child command timing belongs to its root scope; parameter-set replies are explicit reads, never periodic chart work. Per-batch expiry remains enforced. Tab scoping alone passed a single-reader check but was insufficient with concurrent readers. The gateway now shares Good native records through an optional targeted DataValue envelope, preserving source age/quality/timestamps; the HMI ages them further across the RPC and local processing. Production still exposed expiry across leaf sweeps. Budgeted tiered transports now promote only the visible detail to the slow snapshot tier and exclude it again on close. Native records refresh once for shared viewers, with their original source quality/age; non-tiered transports retain bounded targeted fallback. Partial ACKs carry their own quality without renewing station health. Repeat multi-viewer checks on new targets. The optional snapshot processing bracket prevents counting native acquisition twice in the client transit allowance; source ages/limits remain unchanged, malformed brackets fail closed, and older gateways keep conservative full-RPC aging. Budgeted full polls now resume immediately after a period overrun, with one acquisition in flight; fast reads still respect the declared minimum period. Skipping to a later timer boundary had spent the remaining freshness margin. No PLC memory growth/download is needed. Restart the existing gateway and hard-refresh Chrome to load both source changes. See cycle-detail record.

Measure cold/steady reads, tier promotion and shared viewers per target. Keep guards, freshness and locks. The concurrent handler permits bounded RPC work without starving complete reads or parallelizing native writes. D6 writeAccess and Parameter sets browser acceptance are active. See activation.

decl.capture(member, 'Profiler.LastWork') targets an editable scalar. PLC samples the owning-root source and ignores the client candidate, applying normal setup, release/schema/range/value checks. ConfigAudit is shared. See capture proof.

Adding a model to the current AB application

Section titled “Adding a model to the current AB application”

After press70 deployment: Configuration -> Model data -> New model clones an existing model to a unique code. Edit it using Model selection, then activate via ordinary Changeover. A saved Model set offers Create model from set. Creation is inactive; all code/capacity/schema/typed values/read/write permissions are validated before publishing. Eight slots include three seeds; indices never move; no delete/automatic activation. Creation may run while BUSY; later editing keeps normal gates. Use an owner-selected code/source for native acceptance, never a disposable test model that cannot be removed.

Missing/zero capacity hides creation; the template grows statically by controlled declaration deployment. TC3 only reserves the kinds and exposes neither new capability. Physical created-model retention and native download/upgrade retention are unverified; expanded-catalog image generation/boot tests now pass. See press69 record.

The shared HMI model-page read correction is deployed on the bench. The owner created M-101; serial-guarded readback confirms its catalog entry and native schema-4 bank. The corrected HMI queries only discovered response paths and captures the selected page before cleanup. Hard-refresh Chrome; no PLC download is needed for that UI repair. Live production repository read returns all four M-101 fields; Chrome browser acceptance is pending. See the read/deployment record. A later generated image must include the expanded commissioned catalog and all banks via modelCodes; the tested helper now supports that. Native upgrade and credential retention still require separate acceptance.

Enable sets/reasons and typed capabilities. PLC owns values/validation; gateway owns documents/medium. Station load stages <=64 records and commits all-or-none. Import stores without applying. Direct Model-set load still refuses in AB/TC3 pending recipe/Changeover integration; inactive creation from a set is distinct. Exact pre-catalog and pre-Line revisions are recognized when value schemas are unchanged; unrelated/foreign/schema-invalid payloads refuse. Names are not ModelCodes.

Current values export without a saved-set slot; current/saved exports offer Download file (.jsonl, UTF-8) and Copy. All lines use one immutable connection-scoped snapshot; missing/refused lines abort. Receipt Pending/Failed correlates to store transactions but does not prove all physical durability. See station-set proof.

Where retained data lives. Logix has no PLC-side file system: controller tags are the native retained class, and a download resets every tag to its L5X initial value. Credentials travel as declaration registrations. The declaration picks the medium for everything else, as TC3’s MAIN does (Part III AB §3.8b): config_medium=decl.ConfigMedium(...), the file medium (FILE_JSON) today, with the folder %LOCALAPPDATA%\Fraktal\ConfigSets\<serial>-<root> (or FRAKTAL_AB_CONFIG_SET_DIR) on the gateway host. Saved sets are the four named FileStore documents there, the same JSON-lines text TC3 writes, behind the gateway’s SetStore interface. A database medium is refused until the owner names a server, schema and credentials owner.

Without live documents, commissioned values cross a download only when a fresh serial-guarded capture is seeded into the replacement image (fraktal_ab_initial_config.py). With ConfigMedium(live_documents=True) the gateway keeps the station, line and model data as documents in live\ beside the sets and re-applies them after a download: Start names std.release.configRestoring and configuration writes are refused until the restore answers. Enable it only where the binding record answers write-enabled and the access provider is declared: the restore runs under a logged-in session that the set gate permits, so after a download someone with that level logs in and the gateway restores immediately; a read-only gateway never restores. Seed the first live-document image from a fresh capture, because no document exists before it; later downloads need no seed. Watch liveDocuments in /healthz (kept, restoring, restored, unreadable, failed, with any losses by key). Do not delete the folder to “reset” a station: without its index a missing document reads as a first commissioning.

Select application(line=Line('LINE-1', 'PLC-1', utc_offset_min=-300)) when using the new-station template, importing Line from fraktal_ab_line. Leave it absent for a station without a line. The owner sits beside the root, never in its child tree. This binding currently accepts owners only; no mirror transport or multi-root sharing is proved by the single-root Press bench.

The current generator uses Calendar V3 with five unused rows and five zero production targets, so enabling Line does not immediately reset existing counts. Press75 remains the loaded V2 fit baseline; prepared press76 needs owner Capacity Estimate, Verify and completed download. Use Configuration → Line data: UTC offset applies to the whole line; each row has start minutes, duration minutes and weekday checkboxes. For a weekend-only 12-hour shift, set start 480 (08:00), duration 720 and select Saturday/Sunday (mask 96). Enable the days last when editing an unused row. A start of -1 or no selected days disables it. Sunday overnight intervals belong to Sunday even when they end on Monday.

Every proposed edit validates the complete weekly calendar. Overlaps refuse; adjacent endpoints are allowed. A V3 Line parameter set contains all 21 fields and loads atomically. Save/export/import use the existing generic set dialog, and current-value export consumes no saved slot. The minimum Line write level is ENGINEER, raised further by the controller’s effective policy. A weekday checkbox does not grant a write or bypass Save validation.

For three regular weekday shifts plus two special weekend shifts, configure rows 1–3 with Monday–Friday selected (mask 31), and rows 4–5 with Saturday–Sunday selected (mask 96). For example, weekday starts 0/480/960 with 480-minute duration, weekend starts 0/720 with 720-minute duration cover each day without overlap. Other start times/durations are valid when intervals do not intersect, including across the Sunday/Monday boundary. Enable days last, or atomically import a complete Line set. This example is not applied to the live controller automatically.

Each row also has Production target: a non-negative good-part count, with 0 unset. Targets are reporting goals, separate from recipe stop counts. The PLC latches the interval’s target at its start; an edit is pending until the calendar boundary. Statistics shows current good/target and percentage, then the target/attainment captured with each closed shift. No NOK/rework is added to the numerator; zero and unscheduled targets have no attainment calculation. Existing manual-reset/clock-quality flags still mark partial/unverified totals.

Prepared file C:/work/press76.L5X, SHA-256 806BB78A1D8B6A932AA826373C0F59F2C2D9848E6F6AA2004A11D2D5EF876C35, manifest 026DC8F584CA2D70 / 159176, 68,048 bytes. The explicit commissioning image bridge preserves the twice-read four-model catalog (including M-101) and every V2 schedule/current configuration value, adds an unused fifth row and zero targets. Credentials/session/history are excluded; existing access initializers remain byte-identical to press75. The source has 2,756 additional declared data bytes, 9,535 additional ST source bytes and 153 additional terminators; those are not compiled memory estimates. Record both Studio Capacity areas before downloading and completed-link/Run evidence afterwards, then restart the existing gateway and hard-refresh Chrome. See offline preparation.

Calendar edits wait for the current finite boundary. An empty-calendar edit applies next scan, preserving accrued unscheduled production unless an active shift starts. Unscheduled intervals are index 0 and close at the next enabled start. The controller owns eight newest records, counts, raw OEE inputs, quality and manual-reset flags; it snapshots before resetting. A manual OEE reset preserves full production counts but its OEE factors use the matching reset window. No client accumulates history. Clock quality is marked, never set by a gateway or inferred from the PC clock.

Loaded file: C:/work/press75.L5X, SHA-256 82AB065C32BCD112D49DD00839B8047C1B5E957A5356FB9D61EF3C1C2F3172A5. Manifest 94E302F650BA1DB5 / 9757442, 65,552 bytes, Fields 616/624, Localization 652/664. It preserves the fresh captured four-model catalog, all banks/current records and ordinals, including M-101. New Line defaults are explicitly added; credentials/sessions and runtime history are not captured. Trends over accepted press70: data -1,812 bytes, ST -30,972 source bytes, -447 terminators and -413 lines; RLL is unchanged. These do not prove compiled fit. Press72 verified/compiled but failed during download linking. Press73 frees 4,968 declared data bytes through proportional discovery reserves and removes 452 ST terminators through shared step-entry bookkeeping at the same execution point. AOIs, released UDTs, other tag initializers, tasks and LD remain identical to press72. PLC chart visits/history/timing, all renditions, four users and all permissions remain. The six-pair validator is unchanged: 2,020 calendars match an independent interval oracle. Press73 also fails with a final global memory error. Press75 shares native alarm allocation/close services using existing scratch, groups equal rationalized priorities and emits startup defaults once. It removes 19,863 source bytes, 240 terminators and 245 lines from press73; all layouts/tags/AOIs/tasks/other routines compare equal. Read the earlier allocation correction and current correction.

The owner confirms exact press75 completed download at 0/0 and Run. Online data/logic uses 758,568 / 786,432 bytes, leaving 27,864 available (3.54%) and a largest free block of 27,376. This differs from press73’s offline estimate; do not claim the subtraction as measured compiled saving. Fresh native reads confirm the complete manifest/capacities and all four captured model banks. See fit evidence. The shared Web HMI is deployed and HTTPS assets verified. Native Line behavior, Chrome controls and physical retention have separate acceptance records. Press75 now supplies 159 successful restored regression rows across eleven suites and 17 native Line rows. The Line vector verifies complete 13-field export/import, permission/range/overlap/partial-set refusal, a twelve-hour weekend-only interval and its natural end. The original calendar is declared pending during the active shift, then applies at that boundary; history is closed before the profile resets counters. Two actual closure rows remain, never erased for fixture cleanup. Final config/all four banks are restored, S3 passes 6/6 (max 8,384 us; no faults/overlap) and all health routes are ready. This is one weekend/end vector, not a hardware sweep of every weekday/history overflow. Chrome controls and physical Line retention remain owner gates. See native acceptance.

6. What a healthy station looks like on this baseline

Section titled “6. What a healthy station looks like on this baseline”

One LOW CONTROLLER_METRICS_UNAVAILABLE event is expected: no CPU/free-memory GSV source. It occupies a slot but does not block Start; find faults via FaultEvt, not Active[1]. Required unavailable probes make SystemHealth unhealthy by contract. Fieldbus/DC/fan/storage figures remain unavailable. Time-unsynchronized status authorizes neither a clock write nor weakened freshness. State is derived.

These are optional declarations; they do not grow an existing station image until enabled. Do not copy the disposable host demo’s fictitious asset identity into a project. Set Application.nameplate (and optionally Module.nameplate) to decl.Nameplate(manufacturer, product, serial, ...) using the asset’s actual identity. Product URI, year, hardware/firmware/software versions, order code and HTTP(S) documentation URL are supported. Text is printable ASCII, at most 240 bytes; documentation URLs cannot contain credentials. Missing optional fields remain empty. Nameplates are static, outside configuration/recipe writes. They select manifest major 5; the current Python gateway projects the existing generic HMI paths. An older major-4 reader, including the limited direct-CIP spike, must refuse that layout. Identity text uses the owning Logix ASCII encoder, including hex escaping of a CDATA terminator. Never repair L5X text by hand. Run fraktal_ab_readback.py <generated.L5X> <first_export.L5X> after clean SDK import/build: it checks executable bodies and initial values as well as the existing construct/SFC gates. A successful build can still contain discarded initializer data. The gateway compares actual manifest rows with the declared content before rendering; a matching header hash alone is insufficient.

Application.host_event_capacity=8 enables an eight-event PLC ring (supported bound 1..64); default zero omits it. The framework records mode changes and accepted/successfully completed Changeover. Every step incrementing ScrapCount also declares nok_reason: use 'Ctx.ReportedReason' to preserve the handled child’s captured first-out; use a registered literal only for a cause the step itself owns. Missing/zero reasons never become successful anonymous NOK events. ST, SFC and LD call the same generated append AOI. Required-InOut changes use a new Unit AOI name containing capacity/version; existing signatures stay intact.

The gateway reads the stream through its normal tiered projection. A host may also run a serial/build-guarded read-only acquisition into a local SQLite sink, selected with the station’s ordinary FRAKTAL_AB_DECLARATION:

Terminal window
python FraktalCore/PLC/Allen-Bradley/tools/fraktal_ab_host_events.py <controller> --expect-serial <serial> --cursor C:/StationData/mes.cursor.json --sqlite-output C:/StationData/mes.events.sqlite

The station must already publish the matching ring. A dedicated cursor belongs to one sink/controller/build; it advances only after durable sink acceptance. Delivery is at least once, so deduplicate idempotencyKey. SQLite commits before acknowledgement, stores each event/loss key once, and refuses the same key with different content. Its metadata binds the database to that station/controller/build. Use a dedicated local database and cursor together; do not point an acknowledged cursor at a new empty sink. Query Events ordered by Id; Record contains the complete JSON envelope. SQLite supplies transactions and duplicate exclusion; no additional Python package or second PLC history is introduced. The existing --output <file.jsonl> option appends JSONL with flush/fsync; it may append duplicates across a crash and downstream readers must deduplicate. Failed sinks are retried without acknowledging missing events. Ring overwrite and publisher epoch change are explicit loss notices. The bounded sequence fails rather than reusing a key at exhaustion. Event and loss envelopes both carry stable keys. Cursor files use an OS-held, nonblocking .guard lock and atomic replace from uniquely named .pending files. Process termination releases the lock; orphaned pending files are ignored and never treated as acknowledgements. Keep the persistent .guard file in place, including when idle. Stop older collectors before upgrading; an old .lock sentinel is refused and requires confirming the old writer has stopped before removal. A malformed or busy cursor is never silently reset. No outbound network sink is started by default.

Part events require the opt-in local carrier described below. For confirmed tool/material changes, annotate the owning chain’s existing MARK:

resource_kind='TOOL_CHANGED', resource_subject='UpperDie', resource_value='Cfg.ToolNumber'

Cfg.ToolNumber must actually exist as a scalar in that declaration; exact Unit or module scalars and signed DINT literals are also supported. MATERIAL_CHANGED uses the same seam for a numbered material lot. The subject is 1..63 printable ASCII characters; the captured value renders as signed decimal text. Choose the step that confirms the real process change, rather than a configuration edit. No per-scan call, second ring or new hardware driver is needed. A Part-helper failure on that step prevents the resource event. Device-carrier protocols and device-backed parent acquisition remain separate work. The opt-in physical host schema becomes V3, sharing the bounded identity cells between resource Subject and PartUid. Existing V1/V2 output stays unchanged. fraktal_ab_resource_demo is a disposable Echo fixture with fictitious tool/lot confirmations; it is not a commissioned asset declaration.

For a text value use the typed declaration, rather than quoting a scalar name:

resource_value=decl.ResourceText(literal='Lot ABC-123 / tool A')
# Or capture an existing, declared DINT ASCII array at that same boundary:
resource_value=decl.ResourceText(source='Cfg.MaterialLabelAscii')

The literal may contain 0..80 printable ASCII characters. The source must be an exact existing array of 1..81 DINT cells; this example does not declare it. Supply one form only. A shorter array is padded; captured text must terminate and have an all-zero tail, with no control/non-ASCII values or truncation. The framework captures before appending; changing the source later cannot rewrite history. Invalid capture latches the stream’s Failed flag without a partial event. This does not add a generic write or a device/carrier driver.

Only text-consuming declarations select physical host schema V4. Its native ring keeps the existing all-DINT reader contract, packing four ASCII bytes per word, with an 84-byte retained text slot. V1-V3 output remains unchanged; Unit and Part-service required-InOut types get new names. The logical HostEvents Value is still the existing HMI/sink string. The disposable fraktal_ab_text_resource_demo adds a fictitious text confirmation to the numeric resource fixture at an existing MARK, with no new chart row.

Clock replay, physical restart identity, retention, network sink delivery, installed-service and authenticated-write recovery and browser acceptance are separate target gates. Local Windows collector crash recovery is covered by the host recovery evidence. Ordinary same-manifest Echo download recovery and replay from its old cursor are covered by the publisher restart evidence. The compiler/read-back evidence records the disposable v38 fixture; it is not a physical v33/v38 deployment claim.

Set genealogy_capacity=2 on the local carrier only when the station consumes parent UIDs. At the existing MARK that confirms consumption, declare part_parents=(decl.AsciiSource(literal='COMPONENT-UID'), ...). Use AsciiSource(source='Module.Member') for an exact declared DINT ASCII array; a device adapter must supply the confirmed UID, not a mutable display label. The service validates the whole batch, appends unique IDs once and rejects invalid/self/overflow batches atomically. The bound is 1..8 parents, each 1..64 printable ASCII bytes. No project per-scan/reset wiring is needed.

The generic Part card shows current parent UIDs; canonical Part events and SQLite retain their captured parent list after a later receive clears the live context. This selects Part V2 and physical HostEvents V5, with distinct text/no-text type names and no genealogy allocation when disabled. The exact same declaration with only genealogy omitted is a recognized configuration predecessor. See genealogy evidence. RFID/DataMatrix/host carriers and native STRING adapters still need their own provider implementation and device acceptance.

The genealogy evidence also proves reconnect to a restarted disposable, read-only local gateway process, with unchanged Part/host history. This does not qualify the installed Windows service, authenticated write recovery or remote network/sink recovery.

The opt-in Application.part_carrier currently accepts only fraktal_ab_part.LocalCarrier(namespace, records, result_capacity=8, genealogy_capacity=0). The namespace is 1..30 ASCII letters/digits/underscores/hyphens and identifies the actual station. Register fraktal_ab_part.REASONS in the application reason catalogue, and enable host_event_capacity. Carrier storage and reads exist only when selected. The disposable fraktal_ab_part_demo.py shows the complete derived declaration with all three AUTO renditions; its identity is explicitly fictitious and it is not a deployment declaration.

At ordinary MARK boundaries declare part_action='receive', 'start', 'record', 'processed' or 'aborted'. A processed boundary supplies part_verdict (Core NONE=0/OK=1/NOK=2/REWORK=3) and part_reason (registered literal or captured Ctx.ReportedReason; NOK requires nonzero). The shared owner reads identity, checks the local provider’s captured identity, commits the full bounded result and only then counts/emits. Do not add GoodCount or ScrapCount marks: that duplicates the result owner’s count and is refused. Calling receive during handling re-entry preserves a present part; processing start may repeat for a new processing attempt. Final result/UID stay visible after Present drops, until the next successful receive clears the previous result. Fault/abort entry, reset and mode change close a present part automatically. Declare aborted at a project-owned manual-removal boundary the framework cannot infer. A carrier failure blocks advancement with the Core reason at the Unit.

Measurements are Measurement(name, unit, minimum, maximum, target, scale=1); stored numbers are signed DINT, and the physical value is stored / scale. This is an explicit physical encoding, not a narrowed LREAL. part_record is the one-based definition, and part_value names an existing scalar DINT member as Cfg.PressDwellMs, Ctx.SomeMember or PressRam.OutImm_Pos. The fixture records the applied dwell setting and the simulated ram position. Values are sampled by the PLC at that boundary. Each visit appends once; capacity 1..32 is enforced, and overflow faults RESULT_RECORD_REJECTED without a partial append. The generic HMI consumes the existing Part/result/record paths; no station screen is added. Part reads are metadata-bracketed, bounded and refused on invalid data. Every configured result slot keeps the same canonical paths while empty; an empty Name suppresses its row without changing discovery indices.

This selects a new host physical schema V2 with bounded ASCII UID bytes and new capacity/version-named UDTs/AOIs. Adding Part does not modify V1 non-part schemas; the logical host contract is unchanged. Provider state and service instances are private. Runtime data is read-only and outside recipe/configuration writes. The validated manifest hash covers carrier namespace and measurement definitions. Native AOIs/UDTs and the existing GSV clock are reused; no second SFC scheduler, alarm engine or device communication stack is added.

Local IDs contain namespace, startup clock epoch words and an exhaustion-checked serial. They are local BY_POSITION identities, not a physical RFID identity or a uniqueness guarantee under clock replay/download. Results remain in controller memory and the bounded host ring; download resets, durable sink recovery, physical retention and browser acceptance need target evidence. RFID/DataMatrix/host providers and expected external identity remain open. Confirmed local genealogy is available through the opt-in profile above. See source/compiler/model evidence. The owner-authorized Echo download adds idle Run/scan/manifest/Part/host projection acceptance on serial 601FC87B. The subsequent cycle/recovery evidence adds 21 passing ST/SFC/LD live checks, normal configuration restore and local sink refusal/reopen acceptance. Physical and power/download retention remain open. The gateway must select fraktal_ab_part_demo for that test image; direct CIP remains a major-4 spike and refuses its major-5 manifest. This authorization does not carry into another session or controller-changing operation.

tools/fraktal_ab_part_execute.py is a bounded acceptance harness for that exact local v38 Echo fixture. It requires current owner authorization, FRAKTAL_AB_DECLARATION=fraktal_ab_part_demo, --execute-fixture, --expect-serial, a local --credential-file and a new --output path. It refuses a different serial/product/revision/manifest before each write, uses the normal mailbox and declared simulation inputs, and restores stimuli, mode and logout in cleanup. If configuration is still restoring, it uses the ordinary Keeper/staged set transaction under the logged-in controller session; it never stamps SchemaVersion directly. The output contains no credentials. It also checks a dedicated local JSONL sink/cursor with refusal and reopen. This does not change gateway service configuration or qualify an external host.

For carrier-off looping chains with the existing scrap and shared good/finish marks, the generator derives one private FRK_T_CycleVerdictV1 record. The shared finish counts good only if that cycle was not scrapped, then clears the latch. The Unit owner also clears it on reset, abort and mode change. No project reset call is required. The new Unit InOut parameter selects the _CountV1 AOI suffix; regenerate/import its consumers together. Unit context and published counter paths stay unchanged. This deliberately changes the carrier-off generated logic; carrier-enabled counting stays with the carrier.

7. Remaining gaps and deployment boundaries

Section titled “7. Remaining gaps and deployment boundaries”

Set Application.signal_tower to fraktal_ab_signal_tower.SignalTower(lamp_test_duration_ms=3000, operator_uses_white=False, horn_on_high=True) to select Core §8.13. It is a startup convention, like TC3’s SetSignalTowerConfig; changing it requires regeneration. No runtime configuration writer or electrical output address is added. Without the declaration, no tower storage, timer, scan call or reads exist, and LAMP_TEST still refuses by name.

The shared generated service derives semantic Red/Amber/Green/Blue/White/Horn from the existing machine classifier, unshelved active alarm severity and pending decision. Blocking alarms still drive DOWN when shelved. Only the project hardware driver maps semantics to the real lamps/horn. The disposable fraktal_ab_tower_demo derives from the local Part fixture and has no physical I/O; it is not a commissioned asset declaration.

The normal acknowledged LAMP_TEST mailbox command uses the MANUAL access gate, not a mode requirement or the power-control gate. It refuses while the Unit is BUSY or the test is active. Client DurationMs cannot override the startup convention. A private native Structured Text TONR owns the timeout; nonpositive duration defaults to 3 seconds, and the maximum is 30 seconds. The timer runs every scan and does not depend on client polls, session or declared scan-period accumulation. Public semantic state is read-only; timer, request bookkeeping and convention storage have External Access None.

The existing generic HMI renders the tower with or without a health provider, uses its existing act-or-explain MANUAL gate, and disables test while active. No station screen is introduced. Adding this runtime profile recognizes the exact configuration-document revision of the otherwise identical declaration without the tower; all value/schema validation still applies. Unrelated revisions remain refused. The tower evidence distinguishes source/compiler/widget proof, local Echo and physical acceptance. The approved local Echo image is now fraktal_ab_tower_demo, manifest EA7BCE24FDA311EB: select that declaration for its Python gateway. The direct-CIP major-4 spike still refuses this major-5 image. The named native acceptance has 31 passing checks, including the existing ST/SFC/LD Part recovery matrix. fraktal_ab_tower_execute.py --core-regressions reuses those checks under the same exact-target/arm/credential-file boundary. Its policy checks use ordinary SET_ACCESS_LEVEL commands and restore the original policy; no private tag or electrical output write is used. The source fixture has no physical lamp wiring.

Capability Current state
Operating modes, holds, ST/SFC/LD, alarms/reports, timing/OEE/state feature gates and press68 regressions pass
Capture, station sets, users, classes, shelving, qualified S9 named press68 verified; new targets rerun gates
Model creation/current export/Changeover air scope press70 completed-download fit; owner-created M-101 native bank/export/duplicate refusal and mode-scoped air reports pass; Chrome/physical retention remain separate
Direct running-model set load refused in AB/TC3; needs provider/atomic Changeover integration
Part traceability (Core 3.16) optional local BY_POSITION carrier, bounded scaled records, verdict counts, identity/write guards and generic projection; ST/SFC/LD model/compiler and local Echo cycle/recovery proof; confirmed component genealogy is implemented; device providers and physical acceptance remain open
Line data/shifts (Core 3.8e, 8.5.2) press75 fit and 17 native calendar/weekend-end rows pass; Chrome/physical retention remain separate; mirror/shared-root composition remains unbound
SignalTower/LAMP_TEST optional shared mapper, native TONR, MANUAL mailbox gate and generic HMI implemented; exact target evidence linked above; electrical/HAL mapping and physical acceptance remain open
HostEvents optional PLC mode/changeover/NOK, local Part lifecycle and V3 DINT/V4 text tool/material producers and V5 Part genealogy snapshots; generic projection and acknowledged cursor; v38 compile/read-back, local Windows collector crash recovery and SQLite duplicate exclusion tested; device protocols, installed-service and authenticated-write recovery and network sink acceptance remain open
Control-power/safety profiles power deliberately excluded; process/two-hand logic is not certified-safety conformance
Nameplate/IDTA optional complete Core nameplate fields implemented through manifest v5/generic HMI; actual asset commissioning/browser and optional IDTA companion claims remain separate
I/O connection state in health native v38 compiler probes pass; external-module/runtime qualification remains open
MANUAL_HELD / Integrated Motion no manual-held route; L24ER has no motion/S14 proof
Retention owner confirms one admin and one air-threshold edit across cycles; full values/accounts/sets/models, durability and upgrade matrix remain unverified
Project-chosen retained-data medium (TC3 §3.8b, IMPLEMENTATION_NOTES §163) declared medium and SetStore interface (file medium; configuration database medium refused until named); staged station/line/model restore and reopened documents match on local Echo; physical fit, full power-cycle/download/upgrade retention and Chrome view remain separate gates. The optional SQLite HostEvents sink is independent of the configuration medium.
S1 clock probe, other targets and packaged AB installer separate acceptance; not implied by press68 S9

The owner requested completion beyond the earlier Phase 6 boundary. Follow the staged completion plan, continuing with Chrome/physical Line checks after press75 native acceptance, preserving press70 native acceptance.

The current gap census is in the completion plan’s remaining-work section. The October 6 handover retains its historical scope. The parity audit preserves history. No earlier PASS is broadened by this guide. The TC3 prompt separates needed binding work from improvements already shared by the HMI.

Symptom First check / lesson
Hash/capacity mismatch loaded build/declaration; never bypass discovery
Mode/Start refused after download gateway restart and declaration selection
HTTPS fails after reboot proxy startup/certificates separately; 401 is not readiness
Login fault then eventual success request/result/session correlation, pending state, served asset hashes
Parameter sets reloads home complete snapshots starved by RPC/detail work; retain locks and multiplex bounded requests
Model selector vanishes static replacement not hydrated; retain published metadata until complete
Reconnect loop/stale UI partial detail never renews whole health; independent monotonic expiry
Filters followed by a return to overview, possibly with a brief Connecting screen distinguish sample expiry from a browser refresh. Root-path retention alone covers recovery between frames; a painted connection gate remounts the detail. Retain tab ID and per-view time/severity choices in HMI-only state, never samples or permissions. Disable chip drawer-width animation and isolate card/control repainting; stress actual filters, not only an idle view. See filter recovery.
Steps visited but no stroke stale Done/missing Execute-low scan; count commands/end positions
Healthy fixture timeout fleeting flag or read cost; bracket acquisition, wait on counters
Out of memory code/data/reserve; Verify and successful linking, not source size alone
One value survives cycle evidence for that value only, not all persistence/upgrades
Gantt filter leaves blank time shared HMI concatenates visible durations linearly; retain full-cycle header/original tooltip starts
Raw key / inconsistent control size catalogue/shared tokens, not per-screen overrides

Current distribution is AGPL-3.0-only. Read LICENSING.md before distributing derived PLC/HMI/gateway work. Preserve notices and provide exact Corresponding Source as required; modified network programs need section 13’s source offer. Ordinary parameter exports are not automatically relicensed. Assess proprietary station code and vendor dependencies under actual combined-work/System-Libraries rules; no blanket linking exception is granted. License changes do not replace engineering gates.


Built from Specification/Guides/AB_NEW_PROJECT_GUIDE.md at revision a1163c7 of the Fraktal repository.