Annex H — Worked Example: Module Test Suite (TcUnit)

Companion to Fraktal Core (Part I) exercised through the Fraktal/TC3 binding (Part II); slots under Core §12. Core concepts demonstrated: conformance test checklist T1–T9 (§5.7), handshake/first-out/interlock/rollup under test (§6.1, §6.9, §7, §8.2), sim-only force hooks (§5.7). / TC3 mechanics used: TcUnit suites & TcUnit-Runner CI gate (TC3 §5.7). Reference implementation — illustrative, not compile-tested; validate against the pinned TwinCAT version and the TcUnit release in use.

This annex builds the automated test suite for a reusable module type (§5.7) and shows what no other annex does: the standard’s promises — the handshake (§6.1), the first-out diagnostic (§6.9), and the interlock reaction (§7) — proven automatically against the simulated HAL (§2.6), and a small sub-tree’s rollup (§8.2) checked end-to-end. The unit under test is the Annex B cylinder Control Module; the suite runs with no hardware and gates the merge in CI.

FB_CylinderCM (Annex B) ◀── unit under test (driven through its sim HAL)
FB_CylinderCM_Tests : TcUnit.FB_TestSuite ← H.2–H.4 (unit)
FB_ClampRollup_Tests : TcUnit.FB_TestSuite ← H.5 (integration, reuses Annex B EM)
PRG_TcUnitRunner ─▶ TcUnit.RUN() ─▶ JUnit XML ─▶ CI gate (§6.8)

The key enabler is §1.1 O6: because every module runs unchanged against the simulated HAL (§10), the same code is testable on any build agent. The test, acting as the plant, drives the HAL feedback the device would normally produce.


A suite extends TcUnit.FB_TestSuite; each TEST(...)/TEST_FINISHED() pair is one case. The cylinder is wired once to a simulated HAL and a stub recipe (MoveTimeout), exactly as the Unit wires it in production (§3.11) — only the HAL is simulated.

FUNCTION_BLOCK FB_CylinderCM_Tests EXTENDS TcUnit.FB_TestSuite
VAR
_cm : FB_CylinderCM; // unit under test (Annex B)
_hal : ST_CylinderHal; // sim HAL: ExtendOut/RetractOut, ExtendedFb/RetractedFb
_recipe : FB_StubRecipe; // MoveTimeout := T#2S
_wired : BOOL;
_t : TON; // for multi-cycle waits
END_VAR
IF NOT _wired THEN
_cm.Setup(Name := 'Test.Cyl', HalRef := _hal, Recipe := _recipe); _wired := TRUE;
END_IF

_hal is a plain struct here: with no real I/O mapped, writing _hal.ExtendedFb is the simulated sensor (the SIM toggle of §10.1, exercised by the test instead of a sim model).


H.2 The handshake completes on feedback (§6.1)

Section titled “H.2 The handshake completes on feedback (§6.1)”

A multi-cycle test (the documented TcUnit pattern): command EXTEND, let the CM raise ExtendOut, then — acting as the cylinder — make the sensor, and assert the handshake reaches Done.

TEST('Extend_completes_when_feedback_made');
_cm.Command := E_CylinderCommand.EXTEND; _cm.Execute := TRUE;
_cm(); // CM scans: drives _hal.ExtendOut, goes Busy
IF _hal.ExtendOut THEN _hal.ExtendedFb := TRUE; END_IF // plant: sensor reached
_cm(); // CM scans again: sees feedback → Done
AssertTrue(Condition := _cm.Busy OR _cm.Done, Message := 'should be Busy then Done');
IF _cm.Done THEN
AssertEquals_BOOL(Expected := TRUE, Actual := _cm.Done, Message := 'Done expected');
AssertEquals_BOOL(Expected := FALSE, Actual := _cm.Error, Message := 'no Error expected');
_cm.Execute := FALSE; _cm(); // drop Execute → returns to idle (§6.1)
AssertEquals_BOOL(Expected := FALSE, Actual := _cm.Busy, Message := 'idle after Execute drops');
TEST_FINISHED();
END_IF

H.3 The first-out diagnostic is itself under test (§6.9, §8.8)

Section titled “H.3 The first-out diagnostic is itself under test (§6.9, §8.8)”

Withhold the sensor and let MoveTimeout elapse; assert the exact reason and source path the operator would see. This is the test that guards the standard’s signature capability.

TEST('Extend_faults_first_out_when_feedback_withheld');
_cm.Command := E_CylinderCommand.EXTEND; _cm.Execute := TRUE;
_hal.ExtendedFb := FALSE; // plant: cylinder never arrives
_t(IN := TRUE, PT := T#2200MS); // > MoveTimeout (2 s)
_cm(); // tick the UUT every cycle
IF _t.Q THEN
AssertTrue(Condition := _cm.Error, Message := 'Error expected after MoveTimeout');
AssertEquals_DINT(
Expected := E_Reason.CYL_NOT_EXTENDED,
Actual := _cm.Status.Diagnostic.ReasonCode,
Message := 'first-out reason must be CYL_NOT_EXTENDED');
AssertEquals_STRING(
Expected := 'Test.Cyl',
Actual := _cm.Status.Diagnostic.SourcePath,
Message := 'reason must name the source path');
_t(IN := FALSE); TEST_FINISHED();
END_IF

H.4 A dropped interlock produces the defined reaction (§7)

Section titled “H.4 A dropped interlock produces the defined reaction (§7)”

With a permissive forced low, the command shall not drive the output and shall report INTERLOCK_DROPPED (the §7 contract), not silently stall.

TEST('Extend_blocked_when_permissive_dropped');
_cm.SimForceInterlock(id := 1, ok := FALSE); // test hook: drop 'Area safe'
_cm.Command := E_CylinderCommand.EXTEND; _cm.Execute := TRUE;
_cm();
AssertEquals_BOOL(Expected := FALSE, Actual := _hal.ExtendOut,
Message := 'output must not energize while interlocked');
AssertEquals_DINT(Expected := E_Reason.INTERLOCK_DROPPED,
Actual := _cm.Status.Diagnostic.ReasonCode,
Message := 'interlock reason expected');
TEST_FINISHED();

H.5 Integration: the cross-tier rollup (§8.2, §6.9)

Section titled “H.5 Integration: the cross-tier rollup (§8.2, §6.9)”

Assemble the Annex B clamp EM with one cylinder’s sensor withheld and assert the EM adopts the child’s first-out — proving the recursive GetFaultSummary walk, not just a leaf reason.

FUNCTION_BLOCK FB_ClampRollup_Tests EXTENDS TcUnit.FB_TestSuite
VAR _em : FB_ClampEM; _halA, _halB : ST_CylinderHal; _recipe : FB_StubRecipe; _wired : BOOL; _t : TON; END_VAR
IF NOT _wired THEN
_em.Setup(Name := 'ClampStation', HalA := _halA, HalB := _halB, Recipe := _recipe); _wired := TRUE;
END_IF
TEST('Clamp_rolls_up_CylB_first_out');
_em.Command := E_ClampCommand.CLAMP; _em.Execute := TRUE;
IF _halA.ExtendOut THEN _halA.ExtendedFb := TRUE; END_IF // CylA completes
_halB.ExtendedFb := FALSE; // CylB never arrives
_t(IN := TRUE, PT := T#2200MS); _em();
IF _t.Q THEN
AssertTrue(Condition := _em.Error, Message := 'EM should fault');
AssertEquals_DINT(Expected := E_Reason.CYL_NOT_EXTENDED,
Actual := _em.Status.Diagnostic.ReasonCode,
Message := 'EM adopts child first-out');
AssertEquals_STRING(Expected := 'ClampStation.CylB',
Actual := _em.Status.Diagnostic.SourcePath,
Message := 'rollup must name CylB');
_t(IN := FALSE); TEST_FINISHED();
END_IF

This is the §6.9/§8.2 promise — “ClampStation.CylB: cylinder did not reach extended” — asserted automatically, so a future refactor of the EM or CM that breaks the rollup fails CI immediately.


A small runner program executes every suite; TcUnit-Runner drives it headless on the build agent and converts results to JUnit XML, which the CI server reports natively and uses to gate the merge — alongside the lint checks of §5.5/§6.8.

PROGRAM PRG_TcUnitRunner
VAR CylTests : FB_CylinderCM_Tests; ClampTests : FB_ClampRollup_Tests; END_VAR
TcUnit.RUN(); // discovers & runs all suites; results harvested by TcUnit-Runner

Gate sequence on every commit: lint (naming, step/condition records, contract usage — §5.5/§6.8) → test (these suites, against sim) → build. A module type is releasable only when its suite is green against the §5.7 conformance checklist (T1–T9, applicable rows per tier) — the checklist, not the suite’s mere existence, is the bar (§1.5, §5.7). Coverage status (verified 2026-07-26 against the repo, 67 tests / 24 suites): the CM tier is complete — FB_CylinderCM_Tests covers T1–T5 explicitly, so the earlier note that T4/T5 were “left as the reader’s exercise” is superseded. The EM and Unit tiers are not: FB_ClampEM_Tests proves T6 (rollup) and FB_ClampStationUnit_Tests proves only that the root is a Unit, leaving the other applicable Unit rows (T1–T5, T8, T9, T10) unproven. (2026-09-28: the library clamp-station Unit was removed; its Unit-tier rows T6, T8, T9 and T10 now run as FB_UnitTier_Tests on a test-only probe root, FB_ProbeClampRoot.) Those rows are required for a release claim on those types (§1.5, §5.7) — see OBJECTIVES_AUDIT.md gap G9.

The gate is open-ended by design: every later module-type suite joins it unchanged. The Annex I robot suites — FB_RobotCM, the route planner, and the help resolver (§I.14) — run against their simulated connector on the same build agent and gate the same merge, exactly as the cylinder and clamp suites here. Adding a module type adds suites, never gate plumbing.


  • A reusable module type verified by a TcUnit suite against the simulated HAL — no rig (§5.7, §2.6, §10).
  • The handshake (§6.1), the first-out reason and source path (§6.9, §8.8), and the interlock reaction (§7) all asserted automatically — the standard’s promises are themselves under test.
  • An integration test asserting the cross-tier rollup (§8.2), so a refactor that breaks diagnosability fails CI.
  • Scope discipline (NG2): tests live in the type’s suite, never in application step bodies — verification is paid once per type, reinforcing the low-effort objective (§1.1 O1).
  • CI wiring (lint → test → build) extending the existing gate (§6.8, §1.5).

End of Annex H (draft). Part of the worked-example set A–I referenced in §12.