Annex B — Worked Example: Clamp Equipment Module

Companion to Fraktal Core (Part I) exercised through the Fraktal/TC3 binding (Part II); slots under Core §12. Core concepts demonstrated: EM orchestration through the handshake (§3.5/§6.3), parent-child rollup (§8.2), reusable sub-trees via Setup (§3.11). / TC3 mechanics used: OPC.UA.DA pragmas (TC3 §3.10), member FB_init ordering that motivates Setup (TC3 §3.11). Reference implementation — illustrative, not compile-tested; validate against the pinned TwinCAT version and your HAL.

This annex builds the Equipment Module tier (§3.5, §6.3) and shows the three things a CM example can’t: an EM orchestrating child Control Modules through the handshake, a short non-looping step chain, and the parent-child diagnostic rollup (§8.2) that carries a child’s first-out reason up to the operator.

The example is a synchronized dual clamp: a FB_ClampEM holding two clamp cylinders. Each cylinder is itself a Control Module — a cylinder plus its two position sensors (extended/retracted), the “clamp = cylinder + 2 sensors” leaf — built on the Annex A pattern. The EM exposes two commands, CLAMP and UNCLAMP, that string the cylinder commands together and add no device logic of their own (§3.5).

ClampStation (FB_ClampEM, Equipment Module)
├─ CylA (FB_CylinderCM, Control Module) ── HAL: ExtendOut/RetractOut, ExtendedFb/RetractedFb
└─ CylB (FB_CylinderCM, Control Module) ── HAL: …

The cylinder CM follows Annex A exactly (PLCopen handshake, four-structure contract, first-out diagnostic, interlocks in Ladder), so only its surface and reasons are shown here. Note it provides Setup(...) for nested use (§3.11).

{attribute 'qualified_only'}
TYPE E_CylinderCommand : (NONE := 0, EXTEND := 1, RETRACT := 2) DINT;
END_TYPE
// E_Reason additions — cylinder CM band 10100–10199
// CYL_NOT_EXTENDED := 10101 // ExtendedFb not made within MoveTimeout
// CYL_NOT_RETRACTED := 10102 // RetractedFb not made within MoveTimeout
// CYL_BOTH_SENSORS := 10103 // both feedbacks active → wiring/jam fault
TYPE ST_CylinderHal : STRUCT
ExtendOut, RetractOut : BOOL; // outputs
ExtendedFb, RetractedFb : BOOL; // the two position sensors
END_STRUCT END_TYPE
// Annex A/B pattern on the base class: the type is ONLY its device logic.
// Execute/Abort arrive through ExecuteCommand/AbortCommand, and Busy/Done/Error/
// Aborted/ErrorID, first-out stamping, rollup and publication are base-owned (§2.2).
FUNCTION_BLOCK FB_CylinderCM EXTENDS FB_ControlModuleBase
VAR_INPUT
Command : E_CylinderCommand;
ParCfg : ST_CylinderParCfg; // SchemaVersion, MoveTimeout …
ParCmd : ST_CylinderParCmd; // latched by the base on the Execute rising edge
END_VAR
VAR_OUTPUT
OutCmd : ST_CylinderOutCmd; // valid on Done
OutImm : ST_CylinderOutImm; // Extended, Retracted, Diagnostic (ST_Diagnostic)
Intlk : FB_PermIntlk; // conditions are DECLARED BY THE APPLICATION, not by this type
END_VAR
VAR
{attribute 'OPC.UA.DA' := '0'}
_hal : REFERENCE TO ST_CylinderHal;
_tMove : TON;
END_VAR
METHOD Setup : BOOL // late binding for nested use (§3.11)
VAR_INPUT Name : STRING(80); HalRef : REFERENCE TO ST_CylinderHal; Recipe : I_RecipeProvider; END_VAR
THIS^._hal REF= HalRef;
// No interlock is named here. "Area safe" / "Air pressure OK" are station facts, and a
// reusable library cannot name them for a station it has never seen: the application
// supplies them through DeclareCondition/SetCondition and the type only reads Intlk.AllOk (§7.2, §9.2).
// recipe wiring as Annex A …

Behaviour (body as Annex A): EXTEND drives ExtendOut, waits ExtendedFb within ParCfg.MoveTimeout → _M_Complete(), else _M_FaultStopped(Code := PL_ModuleReasons.CYL_NOT_EXTENDED, Text := 'std.error.cylinderNotExtended'); RETRACT is the mirror. Status.Diagnostic.SourcePath is the cylinder’s own browse path (e.g. ClampStation.CylA).


{attribute 'qualified_only'}
TYPE E_ClampCommand : (NONE := 0, CLAMP := 1, UNCLAMP := 2) DINT;
END_TYPE
// E_Reason additions — clamp EM band 11000–11999
// CLAMP_NOT_CONFIRMED := 11001 // both cylinders Done but a clamped sensor not held after settle
TYPE ClampParCfg : STRUCT
SettleTime : TIME := T#150MS; // dwell before confirming
ConfirmTimeout : TIME := T#1S;
END_STRUCT END_TYPE
TYPE ClampOutCmd : STRUCT Clamped, Unclamped : BOOL; END_STRUCT END_TYPE
TYPE ClampOutImm : STRUCT
Clamped, Unclamped : BOOL;
Diagnostic : ST_Diagnostic; // own stall reason, or a rolled-up child reason (B.4)
END_STRUCT END_TYPE

The EM holds its children as outputs, so they publish on the module tree and the generic rollup walk (§3.2) reaches them without a parallel I_ControlModule array. Its command is a short step chain that completes — it does not loop (§6.3).

// Annex B on the EM base: orchestration only, no device logic (§3.5); rollup §8.2.
// Publication is inherited from the explicitly marked deployed root instance.
FUNCTION_BLOCK FB_ClampEM EXTENDS FB_EquipmentModuleBase
VAR_INPUT
Command : E_ClampCommand;
ParCfg : ST_ClampParCfg;
ParCmd : ST_ClampParCmd;
END_VAR
VAR_OUTPUT
CylA, CylB : FB_CylinderCM; // children are outputs: published, and reached by the rollup walk
OutCmd : ST_ClampOutCmd;
OutImm : ST_ClampOutImm;
END_VAR
VAR
{attribute 'OPC.UA.DA' := '0'}
_recipe : I_RecipeProvider;
_step : INT;
_tSettle : TON;
END_VAR
// ---- one-shot wiring (called from the Unit's init, §3.11) ----
METHOD Setup : BOOL
VAR_INPUT Name : STRING(80); HalA, HalB : REFERENCE TO ST_CylinderHal; Recipe : I_RecipeProvider; END_VAR
CylA.Setup(Name := CONCAT(Name, '.CylA'), HalRef := HalA, Recipe := Recipe);
CylB.Setup(Name := CONCAT(Name, '.CylB'), HalRef := HalB, Recipe := Recipe);
// ---- cyclic body: orchestration only; the base owns the handshake ----
METHOD PROTECTED OnCyclic
OnCyclic := SUPER^.OnCyclic();
_M_TickChildren(); // children stay live, so their status is always current

The command body (one method serves both directions; confirmExtended decides which feedback to verify):

METHOD PROTECTED _M_Dispatch
VAR_INPUT Dir : E_CylinderCommand; END_VAR
VAR extend : BOOL; END_VAR
extend := (Dir = E_CylinderCommand.EXTEND);
CASE _step OF
10: // command both cylinders together (parallel)
CylA.Command := Dir; CylA.ExecuteCommand(Dir);
CylB.Command := Dir; CylB.ExecuteCommand(Dir);
_M_Wait('Clamping'); // pending reason while children run
_step := 20;
20: // wait both Done — or roll up the first child Error (B.4)
IF CylA.Error OR CylB.Error THEN
_M_RollupFault();
ELSIF CylA.Done AND CylB.Done THEN
_tSettle(IN := TRUE, PT := ParCfg.SettleTime);
_step := 30;
END_IF
30: // settle, then confirm both feedbacks held
IF _tSettle.Q THEN
_tSettle(IN := FALSE);
IF (extend AND CylA.OutImm.Extended AND CylB.OutImm.Extended)
OR (NOT extend AND CylA.OutImm.Retracted AND CylB.OutImm.Retracted) THEN
OutCmd.Clamped := extend;
OutCmd.Unclamped := NOT extend;
_M_Complete();
ELSE
_M_FaultN(Code := PL_ModuleReasons.CLAMP_NOT_CONFIRMED, Text := 'std.error.clampNotConfirmed');
END_IF
END_IF
END_CASE

The EM adds no device logic — it only sequences the cylinder CMs’ existing EXTEND/RETRACT commands through the handshake (§3.5), plus an EM-level settle/confirm.


B.4 Parent-child diagnostic rollup (the point of this annex)

Section titled “B.4 Parent-child diagnostic rollup (the point of this annex)”

When a child cylinder can’t finish, the EM does not invent a reason — it adopts the child’s first-out diagnostic (§8.2), so the message names the exact device and cause:

METHOD PRIVATE _M_RollupFault : BOOL
// Adopt the first faulted child's diagnostic VERBATIM — reason, SourcePath and Since (§8.2).
// No parallel I_ControlModule array is kept: the children are published members, and the
// base's rollup walk already reaches them.
IF CylA.FaultActive THEN
_M_AdoptFault(CylA.GetFaultSummary());
ELSIF CylB.FaultActive THEN
_M_AdoptFault(CylB.GetFaultSummary());
END_IF
CylA.AbortCommand(); CylB.AbortCommand(); // stop the partner safely

So if CylB’s cylinder never reaches its extended sensor, the chain is:

Unit step "Clamp" ──awaits──▶ ClampStation.CLAMP (EM, Busy on step 20)
ClampStation step 20 ──awaits──▶ CylB.Done
CylB ──Error──▶ ReasonCode = CYL_NOT_EXTENDED, SourcePath = "ClampStation.CylB"

The EM’s Status.Diagnostic becomes exactly { CYL_NOT_EXTENDED, "ClampStation.CylB", "Cylinder did not reach extended" }, the Unit’s stall walk (§6.9) reads it through the EM’s GetFaultSummary, and the operator sees “ClampStation.CylB: cylinder did not reach extended” — a precise, device-naming root cause produced with no hand-coded conditions at the EM or Unit level, just the standard rollup.


B.5 Instantiation & the Unit step that commands it

Section titled “B.5 Instantiation & the Unit step that commands it”

ClampStation is wired once via Setup (§3.11), injecting its name and the two cylinder HAL maps:

VAR ClampStation : FB_ClampEM; END_VAR
// in the Unit's init (one shot):
ClampStation.Setup(Name := 'ClampStation', HalA := Hal.CylA, HalB := Hal.CylB, Recipe := LineRecipe);

A step in the Unit’s AUTO mode chain (§6.2) commands the whole EM through the same PLCopen handshake it would use for any module — the Unit neither knows nor cares that two cylinders are involved:

// Unit AUTO chain, step N200 "Clamp part"
IF NOT ClampStation.Busy AND NOT ClampStation.Done THEN
ClampStation.Command := E_ClampCommand.CLAMP;
ClampStation.Execute := TRUE;
END_IF
IF ClampStation.Done THEN
ClampStation.Execute := FALSE; // Done advances the chain (§6.5)
END_IF
IF ClampStation.Error THEN
// divert; reason already rolled up in ClampStation.ErrorID / .Status.Diagnostic
END_IF

ClampStation.Cyclic (its body above) drives CylA/CylB every scan, so the children stay live whether or not a command is running.


The EM is rendered by laying out its children’s tiles — the automatic child view of §3.13:

Station ▸ ClampStation (EM tile: name, state LED ← ExecState)
├─ CylA (child tile: Extended/Retracted LEDs, manual EXTEND/RETRACT)
└─ CylB (child tile: …)
View Binding
Tile name; state LED ← ExecState; Clamped/Unclamped LEDs ← OutCmd; quick Clamp / Unclamp buttons; the two cylinder tiles beneath it.
Detail manual Clamp / Unclamp (release-gated, §7.6); the live Diagnostic.Description line — which, on a child fault, already reads “ClampStation.CylB: cylinder did not reach extended” via the rollup; tap-through to each cylinder’s own detail view.

The operator can therefore diagnose from the EM screen and drill straight to the offending cylinder — the same parent→child path the PLC tree and the OPC UA model already define, with no station-specific screen building.


  • An Equipment Module orchestrating Control Modules purely through the PLCopen handshake, adding no device logic (§3.5).
  • A short, completing step chain for an EM command, vs. the Unit’s looping mode chain (§6.2 vs §6.3).
  • Parent-child rollup: the EM and Unit report a child’s exact first-out reason and source path with zero per-level diagnostic code (§8.2, §6.9).
  • A reusable sub-tree wired by Setup(...) because member FB_init runs before the parent’s (§3.11).
  • Generic HMI: the EM renders its child tiles and surfaces the rolled-up reason, drill-through following the same tree (§3.13).

End of Annex B (draft).