Annex C — Worked Example: Station Unit
Companion to Fraktal Core (Part I) exercised through the Fraktal/TC3 binding (Part II); slots under Core §12.
Core concepts demonstrated: Unit mode chain (§6.2), mode cascade with graceful rejection (§3.7), top-down recipe (§3.8), stall walk & condition records (§6.9), verdict hook & routing by ID (§10.6/§10.7). / TC3 mechanics used: __QUERYINTERFACE cascade (TC3 §3.2), OPC.UA.DA pragmas (TC3 §3.10).
Reference implementation — illustrative, not compile-tested; validate against the pinned TwinCAT version.
This annex builds the top tier — a FB_Unit (the ModeHandler) — and ties Annexes A and B together. It shows the four things only the Unit tier can: a continuous mode step chain that runs until Stop, mode cascade to a child Unit with graceful rejection (§3.7), top-down recipe load on changeover (§3.8), and the stall-diagnostic walk that lands a child’s rolled-up reason on the operator screen (§6.9).
The station is an infeed Unit composed of one of each tier from the earlier annexes, plus a nested child Unit to exercise recursion:
InfeedUnit (FB_InfeedUnit : FB_Unit, ModeHandler) ← top instance = station ├─ Separator1 (FB_SeparatorCM, Control Module) ← Annex A ├─ ClampStation (FB_ClampEM, Equipment Module) ← Annex B (→ CylA, CylB) ├─ RobotHandling (FB_RobotHandlingEM, Equipment Module) ← Annex I §I.6 (→ Robot130 : FB_RobotCM → I_RobotConnector) └─ FixtureUnit (FB_FixtureUnit : FB_Unit, child Unit) ← recursion + mode cascadeC.1 Modes, step record, reasons
Section titled “C.1 Modes, step record, reasons”{attribute 'qualified_only'}TYPE E_Mode : (AUTO := 0, MANUAL := 1, HOME := 2, CHANGEOVER := 3, CALIBRATION := 4) DINT;END_TYPE
TYPE ST_StepRecord : STRUCT // §6.5 — what the stall walk reads StepNo : INT; StepName : STRING(80); AwaitingLabel : STRING(120); // e.g. "ClampStation.CLAMP" ("" if none) ExpectedTime : TIME; // defaults from the awaited command's timeout Conds : ARRAY[1..4] OF ST_CondRecord; // named plain-condition waits (§6.9(b))END_STRUCT END_TYPE
TYPE ST_CondRecord : STRUCT Label : STRING(60); Ok : BOOL; END_STRUCT END_TYPE // §6.9(b)
// E_Reason additions — framework band// STEP_STALLED := 2005 // step exceeded ExpectedTime with no child fault
INTERFACE I_VerdictProvider // optional per-cycle part-verdict hook — Annex E implements it (§E.2–E.3) METHOD Evaluate : BOOL // TRUE = part OK; called once at the verdict step PROPERTY Reason : E_Reason // first NOK reason when Evaluate() = FALSE — same vocabulary as a fault (§8.8)END_INTERFACE
// Robot point-list / point IDs are stable controller-side handles (Annex I §I.1) —// the application references them by ID, never by coordinate:// ID_PROCESS_G1_1 : DWORD // taught list "ProcessG1-1" (10 pts) on the robot controller// NEST_DRAWER_NIO : DWORD // NIO-drawer disposition position (Annex I §I.10.1)C.2 The Unit (composition & wiring)
Section titled “C.2 The Unit (composition & wiring)”The Unit holds its children both directly (to command them) and as ARRAY OF I_Module for the generic walks — discovery, fault rollup, and mode forwarding (§3.2). Wiring is one-shot via Setup because member FB_init runs first (§3.11).
// The application marks the deployed FB_InfeedUnit instance, not this type.FUNCTION_BLOCK FB_InfeedUnit EXTENDS FB_Unit IMPLEMENTS I_UnitVAR_OUTPUT ErrorID : DWORD; END_VARVAR Separator1 : FB_SeparatorCM; // Annex A ClampStation : FB_ClampEM; // Annex B RobotHandling : FB_RobotHandlingEM; // Annex I §I.6 — semantic ops; owns Robot130 (FB_RobotCM) + its connector FixtureUnit : FB_FixtureUnit; // child Unit (C.5) _children : ARRAY[1..4] OF I_Module;
_hal : REFERENCE TO ST_StationHal; ParCfg : InfeedParCfg; // station recipe (cycle params, …) OutImm : InfeedOutImm; // State, StallReason, Diagnostic …
_name : STRING(80); _mode : E_Mode := E_Mode.AUTO; _exec : E_ExecState := E_ExecState.READY; // READY=idle · BUSY=running · ERROR=held _step : INT; _stopReq : BOOL; _nokPending : BOOL; // verdict from step 35 → routes 40 to finish or disposition _verdict : I_VerdictProvider; // optional hook (0 = none → always OK); Annex E injects its implementation _curStep : ST_StepRecord; _awaiting : I_Module; // module the current step waits on (0 = none) _rTrig : R_TRIG; tStep : TON; // stall timerEND_VAR
METHOD Setup : BOOLVAR_INPUT Name : STRING(80); Hal : REFERENCE TO ST_StationHal; Recipe : I_RecipeProvider; Verdict : I_VerdictProvider := 0; END_VAR // optional — default keeps C standalone THIS^._name := Name; THIS^._verdict := Verdict; THIS^._hal REF= Hal; Separator1.FB_initLikeSetup(...); // per Annex A ClampStation.Setup(Name := CONCAT(Name,'.ClampStation'), HalA := Hal.CylA, HalB := Hal.CylB, Recipe := Recipe); RobotHandling.Setup(Name := CONCAT(Name,'.RobotHandling'), Endpoint := ParCfg.RobotEndpoint /* §3.8: endpoints are configuration, not I/O (audit R3) */, Recipe := Recipe); // wires Robot130 + portable connector internally (Annex I §I.5–I.6) FixtureUnit.Setup(Name := CONCAT(Name,'.FixtureUnit'), Hal := Hal.Fixture, Recipe := Recipe); _children[1] := Separator1; _children[2] := ClampStation; _children[3] := RobotHandling; _children[4] := FixtureUnit;C.3 Lifecycle — SetMode, Start, Stop (I_Unit)
Section titled “C.3 Lifecycle — SetMode, Start, Stop (I_Unit)”METHOD SetMode : BOOLVAR_INPUT Mode : E_Mode; END_VARVAR i : INT; childUnit : I_Unit; END_VAR IF NOT _M_Supports(Mode) THEN SetMode := FALSE; RETURN; END_IF _mode := Mode; IF Mode = E_Mode.CHANGEOVER THEN _M_LoadRecipes(); END_IF // top-down recipe (C.6)
// cascade to child Units only (§3.7) — found via __QUERYINTERFACE (Robot130 is a CM, so skipped) FOR i := 1 TO 4 DO IF __QUERYINTERFACE(_children[i], childUnit) THEN IF NOT childUnit.SetMode(Mode) THEN childUnit.Stop(); // child lacks this mode → safe state SetEvent(EVENT_CHILD_MODE_UNSUPPORTED, childUnit.Name); // §8.7 END_IF END_IF END_FOR SetMode := TRUE;
METHOD Start : BOOL IF _exec = E_ExecState.READY THEN _stopReq := FALSE; _exec := E_ExecState.BUSY; _step := 10; Start := TRUE; END_IF
METHOD Stop : BOOL _stopReq := TRUE; Stop := TRUE; // chain finishes the cycle, then idles (C.4)_M_Supports lists the station’s modes (AUTO/MANUAL/HOME/CHANGEOVER/CALIBRATION). ModeActive (property) returns _mode; State returns _exec.
C.4 Cyclic body & the continuous AUTO chain (§6.2)
Section titled “C.4 Cyclic body & the continuous AUTO chain (§6.2)”// children always tick so their status is liveSeparator1(); ClampStation(); RobotHandling(); FixtureUnit(); // RobotHandling ticks Robot130 + connector
IF _exec = E_ExecState.BUSY THEN CASE _mode OF E_Mode.AUTO: _M_AutoChain(); E_Mode.HOME: _M_HomeChain(); // own chain (elided) E_Mode.CHANGEOVER: _M_ChangeoverChain(); // elided E_Mode.CALIBRATION: _M_CalibrationChain(); // elided E_Mode.MANUAL: ; // no chain — operator triggers EM/CM commands, release-gated (§7.6) END_CASE _M_StallWalk(); // §6.9END_IF
ErrorID := TO_DWORD(Status.Diagnostic.ReasonCode);The AUTO mode sequence is a continuous step chain — it loops until Stop (§6.2). Each step commands a child through the same PLCopen handshake used everywhere (Annexes A/B), advances on Done, and adopts a child Error via rollup:
METHOD PRIVATE _M_AutoChainCASE _step OF 10: _M_SetStep(100, 'Separate', 'Separator1.SEPARATE', T#8S, Separator1); IF Separator1.Error THEN _M_AdoptChild(Separator1); RETURN; END_IF IF NOT Separator1.Busy AND NOT Separator1.Done THEN Separator1.Command := E_SepCommand.SEPARATE; Separator1.Execute := TRUE; END_IF IF Separator1.Done THEN Separator1.Execute := FALSE; _step := 20; END_IF
20: _M_SetStep(200, 'Clamp', 'ClampStation.CLAMP', T#5S, ClampStation); IF ClampStation.Error THEN _M_AdoptChild(ClampStation); RETURN; END_IF IF NOT ClampStation.Busy AND NOT ClampStation.Done THEN ClampStation.Command := E_ClampCommand.CLAMP; ClampStation.Execute := TRUE; END_IF IF ClampStation.Done THEN ClampStation.Execute := FALSE; _step := 30; END_IF
30: _M_SetStep(300, 'Plasma-clean', 'RobotHandling.PROCESS_PART', T#30S, RobotHandling); _M_Await(1, 'Plasma gas OK', _hal.PlasmaGasOk); // §6.9(b): plain-condition wait, named IF RobotHandling.Error THEN _M_AdoptChild(RobotHandling); RETURN; END_IF IF NOT RobotHandling.Busy AND NOT RobotHandling.Done THEN RobotHandling.Command := E_HandlingCommand.PROCESS_PART; // → Robot130.RUN_PATH internally (Annex I §I.6) RobotHandling.TargetId := ID_PROCESS_G1_1; // ID, not coordinates (Annex I §I.1) RobotHandling.Execute := TRUE; END_IF IF RobotHandling.Done THEN RobotHandling.Execute := FALSE; _step := 35; END_IF
35: // ── evaluate result via the injected verdict hook (C.1) — 0 = no provider → always OK ── IF _verdict = 0 THEN _nokPending := FALSE; // no provider wired → C runs standalone ELSE _nokPending := NOT _verdict.Evaluate(); // NOK: _verdict.Reason is the machine's OWN // first-out (§8.8) — no reject taxonomy. With // Annex E wired, the provider records verdict + // reason to carrier/MES (§E.2–E.3). END_IF _step := 40; // ALWAYS unclamp first — the part must be released // before it can be picked for disposition
40: _M_SetStep(400, 'Unclamp', 'ClampStation.UNCLAMP', T#5S, ClampStation); IF ClampStation.Error THEN _M_AdoptChild(ClampStation); RETURN; END_IF IF NOT ClampStation.Busy AND NOT ClampStation.Done THEN ClampStation.Command := E_ClampCommand.UNCLAMP; ClampStation.Execute := TRUE; END_IF IF ClampStation.Done THEN ClampStation.Execute := FALSE; _step := SEL(_nokPending, 50, 60); // OK → finish · NOK → disposition END_IF
60: // ── NOK disposition: segregate the bad part to the NIO drawer. NOT a special robot mode // (Annex I §I.10.1) — an ordinary operation with a DIFFERENT destination. Transferring a part // is pick + move + place, i.e. the handling EM's PLACE_PART_NOK (Annex I §I.6), which composes // gripper close → MOVE_TEMPLATE(NEST_PROCESS → NEST_DRAWER_NIO) → gripper open. Shown here as // one EM command; the robot exits the process nest via its default-EITHER entry corridor. _M_SetStep(600, 'Dispose NOK', 'RobotHandling.PLACE_PART_NOK', T#30S, RobotHandling); IF RobotHandling.Error THEN _M_AdoptChild(RobotHandling); RETURN; END_IF IF NOT RobotHandling.Busy AND NOT RobotHandling.Done THEN RobotHandling.Command := E_HandlingCommand.PLACE_PART_NOK; RobotHandling.TargetId := NEST_DRAWER_NIO; // disposition destination — ID only RobotHandling.Execute := TRUE; END_IF IF RobotHandling.Done THEN RobotHandling.Execute := FALSE; _nokPending := FALSE; _step := 50; END_IF
50: // finish — Stop idles the Unit; otherwise loop. Part leaves known-OK or known-NOK, never silently (Annex E) IF _stopReq THEN _exec := E_ExecState.READY; _step := 0; ELSE _step := 10; END_IFEND_CASEThis is the SFC step chain written in ST (§6.8 — SFC remains the default; ST shown here for the annex). The same chain in SFC would have steps N100/N200/N300/N400/N999 with the Done transitions, plus an SFC divergence at the verdict (N350) to an N600 NOK-disposition branch that re-joins before unclamp — behaving identically:
┌N100 Separate┐→┌N200 Clamp┐→┌N300 Plasma-clean┐→ N350 verdict ─┬─OK──→┌N400 Unclamp┐→ N999 ─loop→ N100 └─NOK─→└N400 Unclamp┘→┌N600 Dispose NOK┐→ N999 transitions = awaited command's Done (§6.5); N350 = SFC divergence on _verdict (§6.9(b) conditions named on stall)C.5 Mode cascade to the child Unit (§3.7)
Section titled “C.5 Mode cascade to the child Unit (§3.7)”FixtureUnit supports AUTO/MANUAL/HOME but not CALIBRATION:
FUNCTION_BLOCK FB_FixtureUnit EXTENDS FB_Unit IMPLEMENTS I_Unit// …METHOD _M_Supports : BOOLVAR_INPUT Mode : E_Mode; END_VAR _M_Supports := (Mode = E_Mode.AUTO) OR (Mode = E_Mode.MANUAL) OR (Mode = E_Mode.HOME);So when the operator puts the station into CALIBRATION, the cascade in SetMode (C.3) calls FixtureUnit.SetMode(CALIBRATION), which returns FALSE. The station does not force the child: it calls FixtureUnit.Stop() to bring it to a defined safe state and raises EVENT_CHILD_MODE_UNSUPPORTED (“InfeedUnit.FixtureUnit: mode not supported”). A parent in Calibration therefore never drags a child into an undefined state — exactly the rule of §3.7.
C.6 The stall-diagnostic walk landing on the HMI (§6.9)
Section titled “C.6 The stall-diagnostic walk landing on the HMI (§6.9)”_M_SetStep records the current step and the module it awaits, and restarts the stall timer on each step change — and it is also the feed for the §8.11.4 cycle profiler (StepChanged on every step change, CycleComplete at the finish step), so the same one-line record produces both the stall diagnostic below and the Unit’s cycle-time waterfall with no additional step code:
METHOD PRIVATE _M_SetStepVAR_INPUT no:INT; name:STRING(80); awaitingLabel:STRING(120); expected:TIME; awaiting:I_Module; END_VARVAR _i : INT; END_VAR IF _curStep.StepNo <> no THEN FOR _i := 1 TO 4 DO _curStep.Conds[_i].Label := ''; END_FOR // clear condition records (§6.9(b)) _curStep.StepNo := no; _curStep.StepName := name; _curStep.AwaitingLabel := awaitingLabel; _curStep.ExpectedTime := expected; _awaiting := awaiting; // 0 allowed (no single awaited child) tStep(IN := FALSE); // restart stall timer END_IF
METHOD PRIVATE _M_Await // §6.9(b) — register/refresh a named plain-condition waitVAR_INPUT n : INT; label : STRING(60); ok : BOOL; END_VAR _curStep.Conds[n].Label := label; _curStep.Conds[n].Ok := ok;_M_AdoptChild is the immediate rollup when a child raises Error (it copies the child’s first-out summary up — §8.2):
METHOD PRIVATE _M_AdoptChildVAR_INPUT child : I_Module; END_VAR Status.Diagnostic := child.GetFaultSummary(); // child reason + child SourcePath _M_HoldAll(); // stop the other children safely _exec := E_ExecState.ERROR;_M_StallWalk handles the slow case — a step that simply isn’t advancing — and composes the §6.9 message:
METHOD PRIVATE _M_StallWalkVAR diag : ST_Diagnostic; i : INT; END_VAR tStep(IN := TRUE, PT := _curStep.ExpectedTime); IF tStep.Q AND _exec = E_ExecState.BUSY THEN OutImm.StallReason := CONCAT5('Step ', INT_TO_STRING(_curStep.StepNo), ' ', _curStep.StepName, CONCAT(' stalled → awaiting ', _curStep.AwaitingLabel)); IF (_awaiting <> 0) AND _awaiting.FaultActive THEN diag := _awaiting.GetFaultSummary(); // walk into the child OutImm.StallReason := CONCAT4(OutImm.StallReason, ' → ', diag.SourcePath, CONCAT(': ', diag.Description)); Status.Diagnostic := diag; // adopt the child's first-out ELSE Status.Diagnostic.ReasonCode := E_Reason.STEP_STALLED; Status.Diagnostic.SourcePath := _name; FOR i := 1 TO 4 DO // §6.9(b): name the first FALSE registered condition IF _curStep.Conds[i].Label <> '' AND NOT _curStep.Conds[i].Ok THEN OutImm.StallReason := CONCAT3(OutImm.StallReason, ' → awaiting ''', CONCAT(_curStep.Conds[i].Label, ''' = FALSE')); EXIT; END_IF END_FOR Status.Diagnostic.Description := OutImm.StallReason; END_IF END_IFConcrete trace — a clamp cylinder never reaches its sensor:
InfeedUnit step N200 "Clamp" ──awaits──▶ ClampStation.CLAMPClampStation step 20 ──awaits──▶ CylB.DoneCylB (FB_CylinderCM) ──Error────▶ CYL_NOT_EXTENDED @ "InfeedUnit.ClampStation.CylB"The operator sees, on the Unit’s view:
Step 200 Clamp stalled → awaiting ClampStation.CLAMP → InfeedUnit.ClampStation.CylB: cylinder did not reach extended
The same walk serves the robot step with no extra code — an unreachable taught point or a dropped controller link surfaces identically through the handling EM’s rollup (RobotHandling adopts Robot130’s first-out exactly as the clamp EM adopts a cylinder’s, §8.2; Annex I §I.6–I.7):
Step 300 Plasma-clean stalled → awaiting RobotHandling.PROCESS_PART → InfeedUnit.RobotHandling.Robot130: point ‘ProcessG1-1.HelpCircle2’ unreachable
And a step held up by a plain condition — no module at fault — now names it instead of a blind stall (§6.9(b)):
Step 300 Plasma-clean stalled → awaiting RobotHandling.PROCESS_PART → awaiting ‘Plasma gas OK’ = FALSE
…produced with no per-step diagnostic code at any tier — only the standard handshake, the step record, and the recursive GetFaultSummary. That is the whole lean-vs-diagnosable resolution (§6.9) demonstrated across all three tiers.
C.7 Top-down recipe on changeover (§3.8)
Section titled “C.7 Top-down recipe on changeover (§3.8)”Entering CHANGEOVER performs the §3.8 subtree transaction—source-agnostic (local, OPC UA, socket, REST):
IF PrepareRecipe(Model := RequestedModel) THEN CommitRecipe(); // infallible bounded publication Model := RequestedModel; // publish only after the whole subtree swapsELSE AbortRecipe(); // active ParCfg remains unchanged everywhereEND_IFA child whose fetch, migration, or validation fails rejects prepare and reports RECIPE_INVALID; no participant commits and the prior model remains active. Commit contains no validation or I/O and cannot reject after successful preparation.
C.8 HMI (§3.13)
Section titled “C.8 HMI (§3.13)”The Flutter app renders the station by drilling the same tree, with the Unit’s mode/Start-Stop and the live stall line at the top:
InfeedUnit mode: AUTO ▾ [Start] [Stop] State ● BUSY ▸ current: Step 200 Clamp · "…CylB: cylinder did not reach extended" ← StallReason ├─ Separator1 (CM tile) ├─ ClampStation (EM tile) ├─ CylA ├─ CylB ├─ RobotHandling (EM tile) └─ Robot130 (CM tile: link LED ← Linked; Referenced ●) └─ FixtureUnit (Unit tile) …| View | Binding |
|---|---|
| Tile | name; state LED ← State; mode badge ← ModeActive; child tiles beneath. |
| Detail | mode selector (calls SetMode, release-gated), Start/Stop; the live StallReason / Diagnostic.Description line; drill-through to Separator1, ClampStation (→ CylA/CylB), RobotHandling (→ Robot130: link/Referenced status; teaching stays in the robot controller’s tool, Annex I §I.15), and FixtureUnit. |
Because the tree is self-describing over OPC UA (§3.10) and every node carries the same contract, none of this is hand-wired per station — the same screen logic renders any Unit.
C.9 What the three annexes together demonstrate
Section titled “C.9 What the three annexes together demonstrate”- One recursive model, three tiers: a leaf CM (Annex A), a composite EM with rollup (Annex B), and a Unit orchestrating both plus a child Unit (here) — all sharing one handshake, one data contract, one diagnostic.
- A robot is just another module: the AUTO chain commands
RobotHandling.PROCESS_PART/PLACE_PART_NOKexactly likeClampStation.CLAMP— one ID in,Doneadvances,Errorrolls up three tiers (Unit → handling EM → robot CM) — so a six-axis arm and a cylinder are indistinguishable to the Unit, with the robot brand hidden behind the injectedI_RobotConnector(§6.1, §10.6, Annex I §I.6). - Continuous vs. completing chains: the Unit’s AUTO chain loops until Stop; EM/CM commands complete (§6.2 vs §6.3).
- NOK disposition is ordinary branching: a bad-part verdict — delivered through the optional injected
I_VerdictProvider(default always-OK; Annex E implements it) — diverts the chain to route the part to the NIO drawer via a normal robot move (Annex I §I.10.1); the part leaves known-NOK carrying the machine’s own first-out reason, with no reject taxonomy and no special robot mode. - Mode cascade with graceful rejection of an unsupported mode (§3.7).
- Cross-tier diagnostics: a single cylinder’s first-out reason walks Unit → EM → CM to the operator with no per-step code (§6.9, §8.2).
- Source-agnostic recipe loaded top-down on changeover (§3.8).
- Generic HMI: every tier renders from the same self-describing tree (§3.13).
End of Annex C (draft). Part of the worked-example set A–I referenced in §12.