Annex A — Worked Example: Separator/Stopper Control Module
Companion to Fraktal Core (Part I) exercised through the Fraktal/TC3 binding (Part II); slots under Core §12.
Core concepts demonstrated: four-structure contract (§3.12), condition ownership (§7.2.1), recipe provider (§3.8), PLCopen handshake (§6.1), first-out diagnostic (§6.9/§8.8), HMI contract (§3.13), simulation (§2.6). / TC3 mechanics used: OPC.UA.DA pragmas (TC3 §3.10), REF= injection (TC3 §3.11), driver SIM toggles.
Realized, not illustrative. This annex describes shipping code:
FraktalCore/PLC/TwinCAT/Framework/Fraktal_Modules/FB_SeparatorCM.TcPOU and its
suite Tests/Fraktal_Tests/FB_Separator_Tests.TcPOU. Both compile under the
pinned TwinCAT and executed green on 2026-08-17 —
Specification/Evidence/2026-08-17_Separator_TcUnit.md, 112/112 across 32
suites. Where this text and the source disagree, the source is correct and this
document is a defect.
The device releases workpiece carriers one at a time — a common conveyor separator/stopper. Three inputs and one output, presented through the HAL:
| HAL signal | Meaning (short signal name) |
|---|---|
CarrierAt |
carrier present at the separator (SAt) |
CarrierAfter |
carrier present just past the separator (SOn) |
OpenedFb |
separator-opened feedback (SOpen, optional) |
ValveOpen |
drives the open solenoid (Valve) |
A.1 Supporting types
Section titled “A.1 Supporting types”Commands and behaviour variants. NONE exists so an unset command is a value the
dispatch can reject rather than a state it must guess at (§5.6):
{attribute 'qualified_only'}TYPE E_SeparatorCommand : ( NONE := 0, SEPARATE := 1, // release exactly one carrier OPEN_CLOSE := 2 // hold the stopper open or closed per ParCmd.OpenStopper) DINT;END_TYPE
{attribute 'qualified_only'}TYPE E_SeparatorMode : ( SEPARATOR := 0, // check carrier at AND after STOPPER := 1, // check carrier at only ASISTOPPER := 2, LEADFRAME := 3) DINT;END_TYPEReason codes are not redefined here. Core already owns the framework band
(TIMEOUT := 2001, PERMISSIVE_NOT_MET := 2002, INTERLOCK_DROPPED := 2003,
RECIPE_INVALID := 2004, UNSUPPORTED_COMMAND := 2008, STEP_STALLED := 2005)
in E_Reason. This type contributes only its own §8.8 band, in
PL_ModuleReasons beside every other module type’s:
// separator/stopper CM 10001-10005 (Annex A) SEP_NO_CARRIER_AT : DINT := 10001; // SAt never made SEP_CARRIER_NOT_CLEARED : DINT := 10002; // SAt did not clear after opening SEP_CARRIER_NOT_ARRIVED : DINT := 10003; // SOn did not arrive in time SEP_NOT_OPENED_FB : DINT := 10004; // open feedback missing SEP_SON_NOT_CLEARED : DINT := 10005; // SOn did not clear after closeThe HAL channel — the leading-underscore raw %I/%Q symbols live in the
Hardware Driver (§10.2); the HAL presents clean, typed signals:
TYPE ST_SeparatorHal :STRUCT CarrierAt : BOOL; // input (driver applies invert/debounce config) CarrierAfter : BOOL; // input OpenedFb : BOOL; // input (optional) ValveOpen : BOOL; // outputEND_STRUCTEND_TYPEThe four-structure data contract (§3.12). SchemaVersion comes first in
ParCfg (§3.8) so a migrate-or-fault decision can be made before reading
anything else:
TYPE ST_SeparatorParCfg : // recipe/config — filled by I_RecipeProvider (§3.8)STRUCT SchemaVersion : UINT := 1; Mode : E_SeparatorMode := E_SeparatorMode.SEPARATOR; CheckAfter : BOOL := TRUE; // require the carrier-after arrival/clear checks UsesOpenFb : BOOL := FALSE; // require the open feedback on OPEN_CLOSE MaxOpenTime : TIME := T#3S; // SAt must clear within this after opening SOnMaxTime : TIME := T#3S; // SOn must arrive/clear within this CloseDelay : TIME := T#0S; Timeout : TIME := T#10S; // overall command timeoutEND_STRUCTEND_TYPE
TYPE ST_SeparatorParCmd : // latched by the base on the Execute rising edgeSTRUCT OpenStopper : BOOL; // OPEN_CLOSE: TRUE = open, FALSE = closeEND_STRUCTEND_TYPE
TYPE ST_SeparatorOutCmd : // valid on DoneSTRUCT SeparateOk : BOOL; SeparatorOpen : BOOL;END_STRUCTEND_TYPE
TYPE ST_SeparatorOutImm : // cyclic live status + first-out diagnosticSTRUCT CarrierAt : BOOL; CarrierAfter : BOOL; OpenedFb : BOOL; ValveOpen : BOOL; Diagnostic : ST_Diagnostic; // §8.8END_STRUCTEND_TYPEA.2 Interlocks: the library declares none
Section titled “A.2 Interlocks: the library declares none”This is the part of the annex worth reading twice, because the obvious design is the wrong one.
A separator plainly has interlocks — area safe, air pressure, no jam downstream, downstream ready. The tempting move is to define them in the reusable type, since every separator needs them. Core §7.2.1 forbids it:
A reusable type derives its conditions from its HAL, parameters, child contracts, and explicitly injected semantic status—not by reaching into application globals or raw schematic I/O. […] Cross-module collision rules, active-mode entry permissives, and other project policy belong to the owning Unit’s application branch (§4.2), preferably in a visible
Release/Permissivesobject […] Reusable libraries retain only device-intrinsic conditions or explicitly injected generic policy; they shall not hide station-specific release logic.
Check the four candidates against the device’s own HAL:
| Condition | Where it comes from | Library-ownable? |
|---|---|---|
| Area safe | AllSafetyOk, the §9.2 safety alias |
No — injected system status |
| Air pressure OK | a utility flag | No — injected utility status |
| No jam at separator | a flag; not on ST_SeparatorHal |
No — injected, not derived |
| Downstream ready | conveyor/line state | No — line policy |
Not one of them is device-intrinsic. So FB_SeparatorCM defines no interlock
conditions at all, and the application declares and drives its own:
METHOD DeclareCondition : BOOL // returns FALSE on an out-of-range indexVAR_INPUT Index : INT; DescriptionKey : STRING(255); Reason : E_Reason; Bypassable : BOOL;END_VAR
METHOD SetCondition : BOOLVAR_INPUT Index : INT; Ok : BOOL; END_VARThe records still live in this module’s own FB_PermIntlk, which is what §7.2.1
requires — “its constituent ST_IntlkCond records remain available so the gate,
first-out diagnostic, and full release report all preserve provenance”. First-out,
the release report and the HMI drill-down are unchanged; only the naming moved
to the layer that has the semantic context.
In the owning Unit’s Release/ object (§4.2), authored in ST beside the rest of
the station’s policy:
// once, at compositionSeparator1.DeclareCondition(Index := 1, DescriptionKey := 'project.interlock.areaSafe', Reason := E_Reason.INTERLOCK_DROPPED, Bypassable := FALSE);Separator1.DeclareCondition(Index := 2, DescriptionKey := 'project.interlock.airPressureOk', Reason := E_Reason.INTERLOCK_DROPPED, Bypassable := FALSE);Separator1.DeclareCondition(Index := 3, DescriptionKey := 'project.interlock.noJamAtSeparator', Reason := E_Reason.INTERLOCK_DROPPED, Bypassable := FALSE);Separator1.DeclareCondition(Index := 4, DescriptionKey := 'project.interlock.downstreamReady', Reason := E_Reason.PERMISSIVE_NOT_MET, Bypassable := FALSE);
// every scanSeparator1.SetCondition(Index := 1, Ok := AllSafetyOk);Separator1.SetCondition(Index := 2, Ok := _AirPressureOk);Separator1.SetCondition(Index := 3, Ok := NOT _JamSensor);Separator1.SetCondition(Index := 4, Ok := DownstreamReady);A declared condition starts FALSE. Declaring one states an intent to gate, so the fail-closed default holds the module until the application drives it; a station that wants no gate simply declares nothing.
Why not one setter per condition. An earlier revision of this annex, and of the cylinder CM, exposed a named setter (
SetAreaSafe(Ok, DescriptionKey)) per condition. It does not scale, and in practice it went unused:SetAreaSafeshipped, and no application ever called it, soCond[1]sat at itsTRUEdefault and operators saw an “area safe” interlock that was permanently satisfied and meant nothing. A library-declared condition that no application supplies is worse than no condition, because it looks like a gate.
A.3 The Control Module
Section titled “A.3 The Control Module”FB_SeparatorCM EXTENDS FB_ControlModuleBase. The PLCopen handshake, the
Execute-drop reset, ExecState mapping, ErrorID publication and abort routing are
inherited and written once in FB_ModuleBase (§6.1); rows T1 and T4 are
proven once for every inheriting type in FB_Base_Tests (§5.7) and are not
retested here. The type is only its device logic.
FUNCTION_BLOCK FB_SeparatorCM EXTENDS FB_ControlModuleBaseVAR_INPUT Command : E_SeparatorCommand; ParCfg : ST_SeparatorParCfg; ParCmd : ST_SeparatorParCmd;END_VARVAR_OUTPUT OutCmd : ST_SeparatorOutCmd; OutImm : ST_SeparatorOutImm; Intlk : FB_PermIntlk;END_VAROnCyclic re-applies every application condition each scan — so a manual command
obeys the same rule as a sequenced one — evaluates the container, mirrors the HAL
into OutImm, and republishes the diagnostic.
_M_Dispatch rejects an unsupported command, tags the command for §8.11.4(a)
timing, and then:
Interlock loss is HELD, not a fault (§6.1). An interlock is by definition a condition that must hold during the action, and losing one is often expected operator behaviour. The valve is withdrawn by the same permit that gates it, the phase timer is reset so a hold cannot silently consume the window it was not moving for, and the chain rewinds to its first step and resumes when the condition returns. Under §8.4 this is a wait, not a downtime event.
SEPARATE is a five-step chain:
| Step | Waits for | Fails with |
|---|---|---|
| 10 | open the valve; CarrierAt present |
SEP_NO_CARRIER_AT |
| 20 | CarrierAt clears within MaxOpenTime |
SEP_CARRIER_NOT_CLEARED |
| 30 | CarrierAfter arrives within SOnMaxTime — skipped unless CheckAfter |
SEP_CARRIER_NOT_ARRIVED |
| 40 | close after CloseDelay |
— |
| 50 | CarrierAfter clears — skipped unless CheckAfter |
SEP_SON_NOT_CLEARED |
OPEN_CLOSE drives the valve from ParCmd.OpenStopper. Closing completes
immediately; opening confirms OpenedFb only when ParCfg.UsesOpenFb says the
station wired one, and otherwise completes at once.
Every fault withdraws the output first. Faults go through a private
_M_FaultClosed(Code, Text) that calls WithdrawOutputs() and then raises:
METHOD PRIVATE _M_FaultClosedVAR_INPUT Code : DINT; Text : STRING(255); END_VAR
WithdrawOutputs();_M_FaultN(Code := Code, Text := Text);This is not decoration. _M_FaultN raises the reason and does not touch outputs,
so an earlier revision faulted from an open phase while leaving the stopper
energised — reporting ERROR while the device kept releasing carriers it could no
longer account for. The suite caught it on first execution; source review had not,
because every individual line was correct and the defect was in what two correct
lines together failed to do.
Diagnostic text is a localization key, never prose: _M_FaultN(Code := PL_ModuleReasons.SEP_NO_CARRIER_AT, Text := 'std.error.separatorNoCarrierAt').
The HMI resolves it per operator language (§3.13); a literal English string in a
library is a defect the cross-artifact gate rejects.
A.4 Instantiation & reuse (§3.11)
Section titled “A.4 Instantiation & reuse (§3.11)”Two separators, same type, different name + HAL mapping + recipe source:
VAR Separator1 : FB_SeparatorCM; Separator2 : FB_SeparatorCM;END_VAR
// composition root, onceSeparator1.Setup(Name := 'Separator1', HalRef := Hal.Sep1, Recipe := LineRecipe);Separator2.Setup(Name := 'Separator2', HalRef := Hal.Sep2, Recipe := LineRecipe);Setup sets the name (= OPC UA browse name = schematic name, §4.8), sets the
presentation keys, binds the HAL by reference, publishes the two commands for the
HMI, and runs the recipe prepare/commit transaction (§3.8). It defines no
interlocks — see A.2.
Recipe := 0 is supported and means “no provider”: ParCfg is used as-is. That
is what the test suite does, and what a station without a recipe source does.
A step in an Equipment Module (Annex B) commands this CM through the standard handshake:
IF NOT Separator1.Busy AND NOT Separator1.Done THEN Separator1.Command := E_SeparatorCommand.SEPARATE; Separator1.Execute := TRUE;END_IFIF Separator1.Done THEN Separator1.Execute := FALSE; // advances the step (§6.5)END_IFA.5 HMI views (§3.13)
Section titled “A.5 HMI views (§3.13)”The Flutter app discovers the instance and renders it generically from the node sub-structure — no per-station screen building:
Station ▸ Infeed ▸ Separator1 Identity : { Name, ModuleType=CONTROL_MODULE } State : ExecState (READY/BUSY/DONE/ERROR/ABORTED) + Held Commands : SEPARATE, OPEN_CLOSE (Features-gated, §3.9; release-gated, §7.6) ParCfg : Mode, CheckAfter, UsesOpenFb, MaxOpenTime, SOnMaxTime … (recipe view) OutImm : CarrierAt, CarrierAfter, OpenedFb, ValveOpen, Diagnostic| View | Binding |
|---|---|
| Tile | name; state LED ← ExecState; carrier LED ← OutImm.CarrierAt; open LED ← OutImm.ValveOpen; quick buttons Separate / Open·Close. |
| Detail | manual Separate / Open / Close (each inhibited unless its §7.6 release is TRUE); status LEDs for CarrierAt/CarrierAfter/OpenedFb/ValveOpen with their interlock descriptions; the live Diagnostic.Description line (the first-out reason); the recipe (ParCfg) panel. |
When a SEPARATE stalls — say a carrier never clears SAt — the Detail view
shows “Separator1: Carrier did not clear separator” directly from
Status.Diagnostic, and on timeout the same text becomes the Error with
ErrorID = 10002. That is the §6.9 walk landing on the operator’s screen with no
per-step diagnostic code.
Because the interlock descriptions come from the application’s
DeclareCondition calls, the drill-down names the station’s own condition —
“Downstream conveyor not ready” — rather than a generic library phrase. Provenance
travels with the record (§7.2.1).
A.6 Simulation vs. hardware (§2.6)
Section titled “A.6 Simulation vs. hardware (§2.6)”FB_SeparatorCM only ever touches _hal. Whether _hal is fed by the real
Hardware Driver or by the DI/DO SIM is a driver-level choice; the CM is unchanged:
IF GVL.SimEnabled THEN // SIM: a test model writes the HAL inputs (e.g. clear CarrierAt shortly after ValveOpen) Hal.Sep1.CarrierAt := SimModel.Sep1CarrierAt; Hal.Sep1.CarrierAfter := SimModel.Sep1CarrierAfter;ELSE // HARDWARE: the driver maps terminals to the HAL Hal.Sep1.CarrierAt := _Sep1_SAt; // %I* via driver (invert/debounce per config) Hal.Sep1.CarrierAfter := _Sep1_SOn; _Sep1_Valve := Hal.Sep1.ValveOpen; // %Q* via driverEND_IFThere are no SIM-only force hooks in the module (§5.7, lint rule C8). The suite drives the shipped surface: it declares conditions the way an application does and writes the HAL the way a driver does, so what the tests exercise is what ships.
A.7 Conformance rows (§5.7)
Section titled “A.7 Conformance rows (§5.7)”| Row | Where |
|---|---|
| T1 handshake, Execute-drop reset | FB_Base_Tests — once for all inheriting types |
| T4 abort, no self-resume | FB_Base_Tests — once for all inheriting types |
T2 first-out reason + SourcePath |
No_carrier_at_the_separator_faults_10001 |
| T3 interlock withholds output | Interlock_withholds_the_valve_and_holds_rather_than_faults |
| T5 recipe migrate-or-fault | PrepareRecipe faults RECIPE_INVALID; provider-less path covered by Setup |
| Ownership (§7.2.1) | Library_declares_no_interlocks_and_application_conditions_are_fail_closed |
Executed 2026-08-17: 6/6 in SeparatorTests, within 112/112 across 32 suites.
End of Annex A — realized against Fraktal_Modules 0.5.0.0.
Built from Specification/Annexes/Annex_A_Separator_ControlModule.md at revision a1163c7 of the Fraktal repository.