Annex A — Worked Example: Separator/Stopper Control Module

Companion to Fraktal Core (Part I) exercised through the Fraktal/TC3 binding (Part II); slots under Core §12. Core concepts demonstrated: four-structure contract (§3.12), condition ownership (§7.2.1), recipe provider (§3.8), PLCopen handshake (§6.1), first-out diagnostic (§6.9/§8.8), HMI contract (§3.13), simulation (§2.6). / TC3 mechanics used: OPC.UA.DA pragmas (TC3 §3.10), REF= injection (TC3 §3.11), driver SIM toggles.

Realized, not illustrative. This annex describes shipping code: FraktalCore/PLC/TwinCAT/Framework/Fraktal_Modules/FB_SeparatorCM.TcPOU and its suite Tests/Fraktal_Tests/FB_Separator_Tests.TcPOU. Both compile under the pinned TwinCAT and executed green on 2026-08-17 — Specification/Evidence/2026-08-17_Separator_TcUnit.md, 112/112 across 32 suites. Where this text and the source disagree, the source is correct and this document is a defect.

The device releases workpiece carriers one at a time — a common conveyor separator/stopper. Three inputs and one output, presented through the HAL:

HAL signal Meaning (short signal name)
CarrierAt carrier present at the separator (SAt)
CarrierAfter carrier present just past the separator (SOn)
OpenedFb separator-opened feedback (SOpen, optional)
ValveOpen drives the open solenoid (Valve)

Commands and behaviour variants. NONE exists so an unset command is a value the dispatch can reject rather than a state it must guess at (§5.6):

{attribute 'qualified_only'}
TYPE E_SeparatorCommand : (
NONE := 0,
SEPARATE := 1, // release exactly one carrier
OPEN_CLOSE := 2 // hold the stopper open or closed per ParCmd.OpenStopper
) DINT;
END_TYPE
{attribute 'qualified_only'}
TYPE E_SeparatorMode : (
SEPARATOR := 0, // check carrier at AND after
STOPPER := 1, // check carrier at only
ASISTOPPER := 2,
LEADFRAME := 3
) DINT;
END_TYPE

Reason codes are not redefined here. Core already owns the framework band (TIMEOUT := 2001, PERMISSIVE_NOT_MET := 2002, INTERLOCK_DROPPED := 2003, RECIPE_INVALID := 2004, UNSUPPORTED_COMMAND := 2008, STEP_STALLED := 2005) in E_Reason. This type contributes only its own §8.8 band, in PL_ModuleReasons beside every other module type’s:

// separator/stopper CM 10001-10005 (Annex A)
SEP_NO_CARRIER_AT : DINT := 10001; // SAt never made
SEP_CARRIER_NOT_CLEARED : DINT := 10002; // SAt did not clear after opening
SEP_CARRIER_NOT_ARRIVED : DINT := 10003; // SOn did not arrive in time
SEP_NOT_OPENED_FB : DINT := 10004; // open feedback missing
SEP_SON_NOT_CLEARED : DINT := 10005; // SOn did not clear after close

The HAL channel — the leading-underscore raw %I/%Q symbols live in the Hardware Driver (§10.2); the HAL presents clean, typed signals:

TYPE ST_SeparatorHal :
STRUCT
CarrierAt : BOOL; // input (driver applies invert/debounce config)
CarrierAfter : BOOL; // input
OpenedFb : BOOL; // input (optional)
ValveOpen : BOOL; // output
END_STRUCT
END_TYPE

The four-structure data contract (§3.12). SchemaVersion comes first in ParCfg (§3.8) so a migrate-or-fault decision can be made before reading anything else:

TYPE ST_SeparatorParCfg : // recipe/config — filled by I_RecipeProvider (§3.8)
STRUCT
SchemaVersion : UINT := 1;
Mode : E_SeparatorMode := E_SeparatorMode.SEPARATOR;
CheckAfter : BOOL := TRUE; // require the carrier-after arrival/clear checks
UsesOpenFb : BOOL := FALSE; // require the open feedback on OPEN_CLOSE
MaxOpenTime : TIME := T#3S; // SAt must clear within this after opening
SOnMaxTime : TIME := T#3S; // SOn must arrive/clear within this
CloseDelay : TIME := T#0S;
Timeout : TIME := T#10S; // overall command timeout
END_STRUCT
END_TYPE
TYPE ST_SeparatorParCmd : // latched by the base on the Execute rising edge
STRUCT
OpenStopper : BOOL; // OPEN_CLOSE: TRUE = open, FALSE = close
END_STRUCT
END_TYPE
TYPE ST_SeparatorOutCmd : // valid on Done
STRUCT
SeparateOk : BOOL;
SeparatorOpen : BOOL;
END_STRUCT
END_TYPE
TYPE ST_SeparatorOutImm : // cyclic live status + first-out diagnostic
STRUCT
CarrierAt : BOOL;
CarrierAfter : BOOL;
OpenedFb : BOOL;
ValveOpen : BOOL;
Diagnostic : ST_Diagnostic; // §8.8
END_STRUCT
END_TYPE

This is the part of the annex worth reading twice, because the obvious design is the wrong one.

A separator plainly has interlocks — area safe, air pressure, no jam downstream, downstream ready. The tempting move is to define them in the reusable type, since every separator needs them. Core §7.2.1 forbids it:

A reusable type derives its conditions from its HAL, parameters, child contracts, and explicitly injected semantic status—not by reaching into application globals or raw schematic I/O. […] Cross-module collision rules, active-mode entry permissives, and other project policy belong to the owning Unit’s application branch (§4.2), preferably in a visible Release/Permissives object […] Reusable libraries retain only device-intrinsic conditions or explicitly injected generic policy; they shall not hide station-specific release logic.

Check the four candidates against the device’s own HAL:

Condition Where it comes from Library-ownable?
Area safe AllSafetyOk, the §9.2 safety alias No — injected system status
Air pressure OK a utility flag No — injected utility status
No jam at separator a flag; not on ST_SeparatorHal No — injected, not derived
Downstream ready conveyor/line state No — line policy

Not one of them is device-intrinsic. So FB_SeparatorCM defines no interlock conditions at all, and the application declares and drives its own:

METHOD DeclareCondition : BOOL // returns FALSE on an out-of-range index
VAR_INPUT
Index : INT; DescriptionKey : STRING(255);
Reason : E_Reason; Bypassable : BOOL;
END_VAR
METHOD SetCondition : BOOL
VAR_INPUT Index : INT; Ok : BOOL; END_VAR

The records still live in this module’s own FB_PermIntlk, which is what §7.2.1 requires — “its constituent ST_IntlkCond records remain available so the gate, first-out diagnostic, and full release report all preserve provenance”. First-out, the release report and the HMI drill-down are unchanged; only the naming moved to the layer that has the semantic context.

In the owning Unit’s Release/ object (§4.2), authored in ST beside the rest of the station’s policy:

// once, at composition
Separator1.DeclareCondition(Index := 1, DescriptionKey := 'project.interlock.areaSafe',
Reason := E_Reason.INTERLOCK_DROPPED, Bypassable := FALSE);
Separator1.DeclareCondition(Index := 2, DescriptionKey := 'project.interlock.airPressureOk',
Reason := E_Reason.INTERLOCK_DROPPED, Bypassable := FALSE);
Separator1.DeclareCondition(Index := 3, DescriptionKey := 'project.interlock.noJamAtSeparator',
Reason := E_Reason.INTERLOCK_DROPPED, Bypassable := FALSE);
Separator1.DeclareCondition(Index := 4, DescriptionKey := 'project.interlock.downstreamReady',
Reason := E_Reason.PERMISSIVE_NOT_MET, Bypassable := FALSE);
// every scan
Separator1.SetCondition(Index := 1, Ok := AllSafetyOk);
Separator1.SetCondition(Index := 2, Ok := _AirPressureOk);
Separator1.SetCondition(Index := 3, Ok := NOT _JamSensor);
Separator1.SetCondition(Index := 4, Ok := DownstreamReady);

A declared condition starts FALSE. Declaring one states an intent to gate, so the fail-closed default holds the module until the application drives it; a station that wants no gate simply declares nothing.

Why not one setter per condition. An earlier revision of this annex, and of the cylinder CM, exposed a named setter (SetAreaSafe(Ok, DescriptionKey)) per condition. It does not scale, and in practice it went unused: SetAreaSafe shipped, and no application ever called it, so Cond[1] sat at its TRUE default and operators saw an “area safe” interlock that was permanently satisfied and meant nothing. A library-declared condition that no application supplies is worse than no condition, because it looks like a gate.


FB_SeparatorCM EXTENDS FB_ControlModuleBase. The PLCopen handshake, the Execute-drop reset, ExecState mapping, ErrorID publication and abort routing are inherited and written once in FB_ModuleBase (§6.1); rows T1 and T4 are proven once for every inheriting type in FB_Base_Tests (§5.7) and are not retested here. The type is only its device logic.

FUNCTION_BLOCK FB_SeparatorCM EXTENDS FB_ControlModuleBase
VAR_INPUT
Command : E_SeparatorCommand;
ParCfg : ST_SeparatorParCfg;
ParCmd : ST_SeparatorParCmd;
END_VAR
VAR_OUTPUT
OutCmd : ST_SeparatorOutCmd;
OutImm : ST_SeparatorOutImm;
Intlk : FB_PermIntlk;
END_VAR

OnCyclic re-applies every application condition each scan — so a manual command obeys the same rule as a sequenced one — evaluates the container, mirrors the HAL into OutImm, and republishes the diagnostic.

_M_Dispatch rejects an unsupported command, tags the command for §8.11.4(a) timing, and then:

Interlock loss is HELD, not a fault (§6.1). An interlock is by definition a condition that must hold during the action, and losing one is often expected operator behaviour. The valve is withdrawn by the same permit that gates it, the phase timer is reset so a hold cannot silently consume the window it was not moving for, and the chain rewinds to its first step and resumes when the condition returns. Under §8.4 this is a wait, not a downtime event.

SEPARATE is a five-step chain:

Step Waits for Fails with
10 open the valve; CarrierAt present SEP_NO_CARRIER_AT
20 CarrierAt clears within MaxOpenTime SEP_CARRIER_NOT_CLEARED
30 CarrierAfter arrives within SOnMaxTime — skipped unless CheckAfter SEP_CARRIER_NOT_ARRIVED
40 close after CloseDelay —
50 CarrierAfter clears — skipped unless CheckAfter SEP_SON_NOT_CLEARED

OPEN_CLOSE drives the valve from ParCmd.OpenStopper. Closing completes immediately; opening confirms OpenedFb only when ParCfg.UsesOpenFb says the station wired one, and otherwise completes at once.

Every fault withdraws the output first. Faults go through a private _M_FaultClosed(Code, Text) that calls WithdrawOutputs() and then raises:

METHOD PRIVATE _M_FaultClosed
VAR_INPUT Code : DINT; Text : STRING(255); END_VAR
WithdrawOutputs();
_M_FaultN(Code := Code, Text := Text);

This is not decoration. _M_FaultN raises the reason and does not touch outputs, so an earlier revision faulted from an open phase while leaving the stopper energised — reporting ERROR while the device kept releasing carriers it could no longer account for. The suite caught it on first execution; source review had not, because every individual line was correct and the defect was in what two correct lines together failed to do.

Diagnostic text is a localization key, never prose: _M_FaultN(Code := PL_ModuleReasons.SEP_NO_CARRIER_AT, Text := 'std.error.separatorNoCarrierAt'). The HMI resolves it per operator language (§3.13); a literal English string in a library is a defect the cross-artifact gate rejects.


Two separators, same type, different name + HAL mapping + recipe source:

VAR
Separator1 : FB_SeparatorCM;
Separator2 : FB_SeparatorCM;
END_VAR
// composition root, once
Separator1.Setup(Name := 'Separator1', HalRef := Hal.Sep1, Recipe := LineRecipe);
Separator2.Setup(Name := 'Separator2', HalRef := Hal.Sep2, Recipe := LineRecipe);

Setup sets the name (= OPC UA browse name = schematic name, §4.8), sets the presentation keys, binds the HAL by reference, publishes the two commands for the HMI, and runs the recipe prepare/commit transaction (§3.8). It defines no interlocks — see A.2.

Recipe := 0 is supported and means “no provider”: ParCfg is used as-is. That is what the test suite does, and what a station without a recipe source does.

A step in an Equipment Module (Annex B) commands this CM through the standard handshake:

IF NOT Separator1.Busy AND NOT Separator1.Done THEN
Separator1.Command := E_SeparatorCommand.SEPARATE;
Separator1.Execute := TRUE;
END_IF
IF Separator1.Done THEN
Separator1.Execute := FALSE; // advances the step (§6.5)
END_IF

The Flutter app discovers the instance and renders it generically from the node sub-structure — no per-station screen building:

Station ▸ Infeed ▸ Separator1
Identity : { Name, ModuleType=CONTROL_MODULE }
State : ExecState (READY/BUSY/DONE/ERROR/ABORTED) + Held
Commands : SEPARATE, OPEN_CLOSE (Features-gated, §3.9; release-gated, §7.6)
ParCfg : Mode, CheckAfter, UsesOpenFb, MaxOpenTime, SOnMaxTime … (recipe view)
OutImm : CarrierAt, CarrierAfter, OpenedFb, ValveOpen, Diagnostic
View Binding
Tile name; state LED ← ExecState; carrier LED ← OutImm.CarrierAt; open LED ← OutImm.ValveOpen; quick buttons Separate / Open·Close.
Detail manual Separate / Open / Close (each inhibited unless its §7.6 release is TRUE); status LEDs for CarrierAt/CarrierAfter/OpenedFb/ValveOpen with their interlock descriptions; the live Diagnostic.Description line (the first-out reason); the recipe (ParCfg) panel.

When a SEPARATE stalls — say a carrier never clears SAt — the Detail view shows “Separator1: Carrier did not clear separator” directly from Status.Diagnostic, and on timeout the same text becomes the Error with ErrorID = 10002. That is the §6.9 walk landing on the operator’s screen with no per-step diagnostic code.

Because the interlock descriptions come from the application’s DeclareCondition calls, the drill-down names the station’s own condition — “Downstream conveyor not ready” — rather than a generic library phrase. Provenance travels with the record (§7.2.1).


FB_SeparatorCM only ever touches _hal. Whether _hal is fed by the real Hardware Driver or by the DI/DO SIM is a driver-level choice; the CM is unchanged:

IF GVL.SimEnabled THEN
// SIM: a test model writes the HAL inputs (e.g. clear CarrierAt shortly after ValveOpen)
Hal.Sep1.CarrierAt := SimModel.Sep1CarrierAt;
Hal.Sep1.CarrierAfter := SimModel.Sep1CarrierAfter;
ELSE
// HARDWARE: the driver maps terminals to the HAL
Hal.Sep1.CarrierAt := _Sep1_SAt; // %I* via driver (invert/debounce per config)
Hal.Sep1.CarrierAfter := _Sep1_SOn;
_Sep1_Valve := Hal.Sep1.ValveOpen; // %Q* via driver
END_IF

There are no SIM-only force hooks in the module (§5.7, lint rule C8). The suite drives the shipped surface: it declares conditions the way an application does and writes the HAL the way a driver does, so what the tests exercise is what ships.


Row Where
T1 handshake, Execute-drop reset FB_Base_Tests — once for all inheriting types
T4 abort, no self-resume FB_Base_Tests — once for all inheriting types
T2 first-out reason + SourcePath No_carrier_at_the_separator_faults_10001
T3 interlock withholds output Interlock_withholds_the_valve_and_holds_rather_than_faults
T5 recipe migrate-or-fault PrepareRecipe faults RECIPE_INVALID; provider-less path covered by Setup
Ownership (§7.2.1) Library_declares_no_interlocks_and_application_conditions_are_fail_closed

Executed 2026-08-17: 6/6 in SeparatorTests, within 112/112 across 32 suites.


End of Annex A — realized against Fraktal_Modules 0.5.0.0.


Built from Specification/Annexes/Annex_A_Separator_ControlModule.md at revision a1163c7 of the Fraktal repository.