Fraktal HMI Contract — what a generic client binds (Core §3.10(a′), §3.13)

The HMI never binds PLC-language properties or calls PLC methods: everything it renders is data in the Fraktal Self-Description Service repository. A binding may obtain that data from a native namespace or reconstruct it from a validated live manifest. A station adds zero HMI code (O1); the same logical structures serve every binding (O8).

All displayed strings follow LOCALIZATION_AND_MODULE_CONTENT.md: PLC display fields carry stable std.*/project.* keys, never operator prose. Standard and project catalogs, first-run language selection, CSV administration, module PDF content, and per-section view policy are part of this contract.

In the TwinCAT binding, externally written request/configuration data is VAR_INPUT and published result/status data is VAR_OUTPUT; implementation VAR is private. This IEC access classification is a transport mapping, not authorization: every write listed below is still release-gated and re-checked by the PLC.

The generic Part card renders Part.Parents as ordered, selectable component UIDs alongside the current Part/result. UIDs are identifiers and are displayed verbatim. A binding may publish an aggregate string array or indexed scalar Part/Parents[i] leaves; the client consumes the published extent, including native array browse layouts, without a station-specific capacity or history. An absent/empty parent set clears the display on the next snapshot. The PLC owns genealogy and its lifecycle; the HMI neither accumulates consumption nor reconstructs historical parent sets. Optional AB HostEvents V5 records carry a captured Parents list independent of the current Part context.

Walk the canonical hierarchy returned by the Self-Description Service (§3.10). A record is a module iff it declares the standard module Status contract. Status.Name = qualified identity/tile caption, Status.ModuleType = tile kind (Unit / EM / CM), Status.TileEnable = render on the parent’s child view. Children are the records whose declared parent is that module. In a native hierarchical namespace such as Fraktal/TC3, that relation is the instance tree; in a manifest binding such as Fraktal/AB, the gateway reconstructs the identical repository hierarchy from stable module/parent IDs (§4.8).

UI element Symbol
Caption / kind instance Status.Name identity plus optional DisplayNameKey, Status.ModuleType
State LED Status.State (READY/BUSY/DONE/ERROR/ABORTED)
Message line Status.Diagnostic.Description (+ SourcePath, IoTag, IoAddress, Since, TimeSynchronized) — the §6.9 first-out; IoTag is rendered verbatim/monospace and never localized; an unsynchronized stamp is visibly marked untrusted; on a Unit this shows the live stall (Pending) whenever no fault is active
PLCopen strip Busy, Done, Error, Aborted, ErrorID
Command timing table (detail) Timing.Rows[i] = {Id, Label, Count, Last, Minimum, Maximum, Avg}, Timing.LastCmdTime, Timing.Truncated (§8.11.4(a))

Tabbed module detail and administrator customization

Section titled “Tabbed module detail and administrator customization”

Every module detail offers the built-in card tabs: Overview, Hardware (safety, system health, control power, device link, motion, nameplate), Statistics (counters, OEE, shift, cycle analysis; Units only), Events (active events, event history), Description (module information, documents) and, for a module with editable values, Configuration. A card tab is a flow of cards, not a grid: each card goes into the currently shortest column (ties go left), so the columns stack independently and a tall card leaves no row-high gap beside it; a card with nothing to show takes no place, and a column is dropped when a card would be narrower than it can be read. The Overview carries every card, two columns by default, with the description, documents and configuration cards present but hidden; every other card tab carries its own cards in one column. The tab strip is omitted when only one tab is visible. A tab with nothing to show this session - a card tab none of whose cards is shown (hidden, above the session’s level, or without data on this module), or a custom view with neither controls nor a picture - is left out of the strip; in edit mode every tab is shown, so an empty one can still be arranged.

Admin edit mode on Station A: a scope switch between this module and every Clamp & inspect station, a toolbar, a draggable tab order, and cards with access, hide and remove controls.

An administrator arranges tabs and cards on the HMI itself, for one module or for its whole type.
  1. Scope: this module only, or every module of its type (here every Clamp & inspect station).
  2. The tab order, by dragging.
  3. Per card: the access level needed to see it, hide, remove.
Browser HMI simulation at revision a1163c7 · try it

Large detail tables are requested for the selected tab’s visible cards, using the same card and section access rules. Closed tabs and hidden cards do not consume periodic ring/trend reads; an initially empty table still has an owning view that can request it. Authored controls derive demand from their bindings. Budgeted tiered transports stream the demanded tables through their slow tier; closing the view excludes them again. Other transports use bounded targeted reads. Source freshness remains independent of the live station sample (see transport read tiers).

An empty forest caused by temporary data withdrawal preserves the selected module path and local tree scope. It clears usable module data and permissions; the connection owner still blocks interaction on STALE/DOWN. Recovery between frames retains the mounted tab and its presentation filters instead of silently opening the plant overview. A populated replacement forest that no longer contains the selected module resets selection to the overview as usual.

The selected tab ID and each view’s time/severity filter choices are HMI-local presentation state. They survive a painted connection screen and the resulting detail-widget remount. No module samples, permissions or commands are retained with these choices: recovery renders newly accepted data, and STALE/DOWN still withdraws the interactive shell. A removed module discards its presentation state.

Filter selection changes geometry immediately. Controls and cards isolate their repainting so selection/ink animation does not redraw neighbouring charts on every frame. These presentation changes issue no PLC command.

In edit mode an authenticated ADMIN arranges each card tab - adds or removes cards, drags them into order, hides or shows each, sets the minimum AccessLevel to see each (on top of the module’s section policy) and sets the column count - and drags the tabs themselves into order. Any tab, a custom one included, may be made the default tab: the module opens on it, and it stays first. Each tab has an HMI-local minimum AccessLevel; only an ADMIN may change that threshold, title, order, trigger, or content. Like section policy, tab and card visibility is defense in depth rather than transport read authorization.

Typed/category capabilities add reusable detail tabs without station screens:

  • a motion facet adds position/target/velocity/error and axis-state presentation;
  • FB_TcpVisionCM-shaped data adds judgement, result, trigger, and optional-image presentation;
  • FB_TcpCodeReaderCM-shaped data adds decoded value, no-read/match state, link state, statistics when published, and a catalog-routed trigger;
  • RFID-shaped data adds current UID, tag-present/read-quality, link state, and a catalog-routed read action.

These are standard category renderers, not vendor or station pages. Missing optional values render as unavailable; they are never synthesized. High-performance defaults use neutral surfaces and reserve strong colour for abnormal/judgement state.

In ADMIN edit mode, a custom or guidance tab may contain localized text, scalar value outputs, Boolean LED indicators, bounded local trend charts, PLC-validated action buttons, configuration text inputs, and embedded images. The control editor presents an autocomplete/search selector populated only from scalar repository values owned by the selected canonical module; it never accepts an invented free-text path. Values below child module nodes belong to that child. OPC.UA.DA := '0' therefore removes a TC3 value from custom binding just as it removes it from every OPC UA client; other bindings enforce the same exclusion through their manifest/access gate. Value, LED, and configuration-input controls link one compatible value; a chart links up to eight numeric values and renders them as distinct series. Chart periods are clamped to 250–60000 ms and histories to 20–600 points; these are volatile display samples, not a historian or a control-time source. A temporarily unavailable imported link is shown as unavailable and retained for reconnect/change-resistant import rather than silently discarded.

Each selected scalar retains the repository value envelope’s quality, source/server timestamp, synchronization flag, and logical runtime type. A TC3 OPC UA adapter maps its DataValue into that envelope; an AB adapter maps the CIP sample and gateway receipt state into the same fields. Only Good-severity values are usable. Bad or Uncertain values are shown with an explicit quality/status indication; LEDs do not imply an ON/OFF state, charts do not append a sample, and configuration inputs are disabled until Good data returns. The flat snapshot value map remains a Good-only compatibility surface.

Controls have portable responsive width presets (quarter, third, half, two-thirds, full). Narrow displays collapse them to safe full/half-width rows; wide displays use a wrapping grid. Edit mode supports drag reordering plus keyboard-accessible move actions. Layouts remain flow-based and responsive rather than persisting fragile pixel coordinates.

A custom tab with a background image is an overlay container (LOCALIZATION_AND_MODULE_CONTENT.md §7.2): a control may carry a placement whose position and size are fractions of the image’s own painted box, computed with the same fit/alignment/margin arithmetic that draws the image, so a lamp placed on a sensor stays on it on every panel size and fit. Unplaced controls stay in a flow list beside the picture, never over it. An ADMIN drags a control from a palette onto the picture, drags a placed control to move it and its corner to resize it; each completed gesture is one draft step. Two kinds exist for pictures: a state shape (rectangle, rounded rectangle, circle) and a level bar (vertical when drawn taller than wide, over a declared minimum/maximum). Their colour comes from at most four ordered rules - binding, comparison (is TRUE, is FALSE, =, ≠, >, <) against a constant, semantic state token - and a default token (§7.3): the first match wins, a non-numeric value never matches, and any Bad/Uncertain or missing binding renders the control unavailable instead of a state. A stored rule that names a binding the control no longer has rejects the control rather than dropping the rule.

A layout is authored against a module type (Status/TypeKey, LOCALIZATION_AND_MODULE_CONTENT.md §7.1), and a module’s own layout is the override: the HMI resolves a module’s tabs from its path, else its type key, else the defaults, and an override replaces the type’s layout whole (no partial merge). The editor publishes to “this module” or “every module of this type”; dropping an override falls back to the type and is recorded as a revision. A type layout is stored under the scope type:<TypeKey>, travels in the customization profile, and is never remapped as a module path on import. A module that publishes no type key keeps per-path layouts.

Every custom view declares a display class (§7.4) - operating, maintenance or engineering - shown as a badge on the view and recorded in the export. An operating view is refused a picture at publish; a view stored without a class takes maintenance if it carries a picture and operating otherwise. Every view is also refused at publish above its read budget (§7.3): the standard 200 bound reads, or a lower readBudget the view declares (a declaration above 200 reads as the standard). On an operating view an ok state token draws neutral: colour is reserved for the abnormal.

A custom view without a picture may use a grid container (§7.2) instead of the flow: grid.base is a column and row count (at most 12 × 24) and the cell of each control it places, by control id — a column/row origin and span, drawn as that fraction of the tab. grid.variants may re-place the same controls for a control-scale preset (compact, medium, large); a scale with no variant shows the base, scaled rather than reflowed. A control with no cell in the grid in force is listed beneath it. A cell outside its grid, or for a control the view does not hold, is dropped on load rather than drawn somewhere nobody placed it; resizing a grid takes off the cells that no longer fit; a view with a picture places on the picture and keeps no grid. A placed control is drawn at its cell’s width and scaled down, never clipped mid-row, when the cell is shorter.

Every control may name a layer (§7.2): controls sharing it form a show/hide set the viewer toggles with chips (per panel, never while editing). Z-order is control order; the placement toolbar brings a control to the front or sends it to the back. A control may carry a bound visible - one tag, a comparison and a constant - and stays shown while that tag is unavailable, so missing data never hides an indicator; it is presentation, never enforcement. A button or input may also carry a bound enabled of the same shape; there an unavailable tag disables, because Bad/Uncertain data never enables an input. A state rule may blink while it is the rule in force, and holds steady when the platform asks for reduced motion. A state rule, and the default state, may name an icon from the bounded ModuleGlyph set, drawn in the state’s token colour. A shape may carry a bound rotation: one numeric tag whose range maps linearly onto two angles within ±360°, clamped at both ends, upright while the tag is unavailable. Any control may carry a bound opacity (dimmedWhen, the visible shape) and draws at 35 % while it holds; unavailable data never dims. A view may bind a layer’s visibility (layerConditions, one condition per layer name): the whole set is shown only while it holds, never hidden on unavailable data, and the viewer’s chip still applies on top. Every condition, rotation and layer tag counts toward the read budget. Every state token, off included, is measured at 3:1 on a card in every theme (theme_contrast_test.dart), which is what “contrast enforced at publish” (§7.4) reduces to when authored colour can only be a token.

Configuration values are edited in the control their type calls for. A BOOLEAN value is a checkbox; a value with an EnumDomain is a dropdown whose labels come from the catalogs as <EnumLabelKey>.<value> (the raw value when the entry names no prefix or the catalog has no entry); anything else is a text field. The unit is a code, UnitCode (E_EngUnit, ordinals mirrored by the HMI’s EngUnit and checked by lint E1): the HMI shows its own translated symbol (std.unit.<name>) after the value, in the reading direction, and shows nothing for NONE. A controller that publishes no UnitCode keeps its legacy Unit text, which a current PLC derives from the code.

The station tile (§7.5) keeps its fixed geometry - identity, state, the built-in chips, the message line - and adds authored slot contents: up to three metrics (value controls) and two badges (state shapes), authored per station or per type (type:<key> scope) from a root Unit’s edit bar and published directly, outside the tab draft. Metric N always occupies column N, an unavailable metric shows a dash in its column, and a badge’s OK state draws neutral because the tile is an operating view by definition. A profile is refused whole if any slot is invalid, travels in the customization profile as tiles, and an older bundle without it imports unchanged.

An administrator may select a whitelisted portable icon preset for each custom or guidance tab. A custom tab may also carry an embedded background image with contain/cover/fit-width/fit-height aspect-ratio presets, nine-point alignment, and independent bounded margins. The image remains presentation-only behind the tab’s live controls; it cannot replace the PLC-owned status contract. The card tabs, the Overview included, carry none: a picture stored on one by an older HMI is dropped on load.

Layout editing cannot create an arbitrary write path. Buttons map only to the existing manual-command catalog, Unit start/stop/reset, or DecisionAnswer; inputs use the existing acknowledged configuration mailbox. The PLC remains authoritative for publication, type/range validation, access, releases, interlocks, audit, and acceptance. Rejected actions follow act-or-explain and no write is queued across reconnect. Manual-command and decision buttons store only a value selected from the current PLC catalog and execute against their current canonical module/root; an older imported free-form target path is ignored. State-changing buttons may require an operator confirmation and disable while one acknowledged request is in flight. A missing catalog entry disables the button rather than guessing or sending an obsolete value.

The editor is derived only from writable §3.10.2 manifest entries. Each field carries Scope, display/browse Item, stable WriteKey, non-zero WriteRevision, ConfigKind, ValueType, optional bounds/exact enum domain, unit/label, and RequiresReady. The HMI shows Apply only when that complete capability is valid, belongs to the current canonical module, the required root state is satisfied, and the current session permits DATA_WRITE. Missing metadata, duplicate (Scope, WriteKey) entries, older manifests, and arbitrary scalar tags are read-only. A custom configuration-input binding must match the capability’s Item; it may not manufacture a field from the final browse segment.

The Configuration tab: Model config for model A100 and Station config, each value with its own write button.

The configuration editor, built only from the writable entries the station publishes.
  1. The model whose recipe is shown: the running one unless another is picked.
  2. Each value is written on its own.
Browser HMI simulation at revision a1163c7 · try it

The repository re-resolves the current capability immediately before sending WRITE_CONFIG: TargetPath=Scope, NameValue=WriteKey, IntValue=WriteRevision, TextValue=candidate, then Sequence last. Client type/range checks provide immediate feedback only; the PLC repeats them and remains authoritative. A stale revision or reconnect never falls back to a browse write and is never queued for replay.

A value published with ModelScoped = TRUE (Core §3.8a, Core 0.19+) belongs to the root’s model record. The model-data card offers every AvailableModels entry beside the running one: QUERY_CONFIG and WRITE_CONFIG carry the chosen model in DurationMs (0 = running, n = AvailableModels[n]), and the card reads the record back after each accepted write because another model’s values are not in the live tree. A query for another model answers with its model-scoped values only - normally one page - never the station manifest. DurationMs is 0 for every other value. Model config, station config and line config are separate cards (modelData, stationData, lineData); a stored layout naming the former single configuration card expands to the three in place.

Set operations are separate from field edits in both directions. The HMI offers save/load/list only when the session permits CONFIG_SET (a model set also requires CHANGEOVER) and the owning root is READY; a load is presented as replacing the machine’s parametrization, not as an edit. Because the PLC stages and validates the whole set before applying any of it, a rejection returns the offending (Scope, WriteKey) and the HMI shall show that identity rather than a generic failure — the operator’s next action is to fix one value, and they cannot if the client hides which. Durability is displayed, never assumed: PersistPending and PersistFailed from the root drive an explicit indication, and a restore failure reported at startup stays visible until acknowledged. The client never serializes or repairs a set itself; it names one and reports what the PLC did.

A Unit may have one or more guidance tabs. A guidance tab can match an exact CurrentStep.StepNo, an exact CurrentStep.StepName, or *; the wildcard opens only for WAIT_OPERATOR steps. On entry to a newly matched step the HMI opens a full-screen operator guide containing the live step/awaited conditions, any Decision prompt, and the administrator-authored controls. Dismissing it does not complete or acknowledge the sequence. Completion still comes only from published PLC conditions or the typed DecisionAnswer; the same step is not reopened repeatedly until the step identity changes. This supports changeover/cleaning/tooling instructions without a press-specific HMI page or PLC-authored prose.

An ADMIN can export/import one versioned UTF-8 JSON customization bundle. It includes all persistent administrator-owned presentation state: module tabs and controls, per-tab and per-section access policy, tab icon choices, guidance triggers, embedded control and tab background images with layout settings, module PDF documents/metadata, canonical repository control bindings (including their binding-specific transport locator where required), and both standard/project localization overrides for every language. Import validates the complete bundle and explicitly confirms a merge: imported IDs/keys update matching items while target-only customization is preserved. It reconciles module identities conservatively: exact paths first, then a mapped parent plus unchanged local name, then a unique longest dotted-path suffix. A uniquely remapped descendant may establish a root-rename hint. Ambiguous or absent modules do not fail the import and are not discarded; their profiles remain stored under the original path as deferred, and the administrator receives an exact/remapped/deferred report. Malformed schemas or payloads still fail closed.

Administrator edits are drafts: add/edit/delete/reorder operations update only an in-memory working copy with undo/redo. Operators continue to see the last published layout until Publish succeeds. Publishing records the previous layout, UTC time, administrator identity, and optional change note. At most 20 revisions per module are retained; restoring a revision first records the layout being replaced. Revision history is part of customization schema 4 and follows the same deterministic module path reconciliation during import. Connection endpoint/transport, proven-connection state, selected Unit scope, credentials/session state, and language selection are connection/bootstrap settings and are deliberately excluded. The shipped native and Web stores remain device-local; the bundle is the portable commissioning/backup path. Native storage replaces files through a flushed temporary generation and retains a last-known-good backup; Web uses IndexedDB and migrates the older local-storage record when encountered.

UI element Symbol
Current step CurrentStep (StepNo, StepName, AwaitingLabel, TimeClass, ExpectedTime, Conds[] with per-condition Label/Ok — §6.5/§6.9(b))
Model catalog optional AvailableModelCount + AvailableModels[]/ModelCode; render a selector when present, otherwise validated free text (§3.8)
Live stall reason Pending (Low; distinct from a fault)
Cycle waterfall Profiler.LastCycle — ordered Steps[] {StepNo, StepName, TimeClass (color), Started, Duration}; header: Total, WorkTime (real cycle time), WaitTime, ByClass[0..4] (§8.11.4(b)/(f))
Step Pareto Profiler.StepStats[] (Avg/Max per StepNo, class-tagged), Profiler.Current for the live bar
Counters GoodCount, NokCount, Starved, Blocked (§8.11)
Fault history History[1..MAX_DIAG_RING], newest at HistoryHead (§6.9(a) ring — shift post-mortem)
Operator decision read Decision (Prompt/Options/Default/Timeout); write DecisionAnswer (1-based option; 0 = none) (§6.11)
Alarm/event list sparse AlarmLog.Active[1..MAX_ALARM_ACTIVE] slots whose State is ACTIVE/WAIT_RESET (Severity, Reason, Source, optional exact IoTag/IoAddress, ComeAt + time-quality flag, ResetClass) — WAIT_RESET rows render as “cleared, awaiting reset” (§8.3(b))
Event history AlarmLog.Ring[], newest at AlarmLog.RingHead — each closed event with optional exact IoTag/IoAddress, Duration, ComeAt/GoneAt/ResetAt and their time-quality flags (§8.3(a)/(d)); unsynchronized records are marked untrusted, never discarded; full history via an I_EventSink historian adapter (deferred by design)
Blocked banner AlarmLog.Blocking — Unit will refuse Start until OperatorReset (write, release-gated §7.6/§14)

The cycle timing charts expose selectable legend chips and Show all. Cycle trend, Gantt and step Pareto filter by the published time class. Each chart’s selection is local presentation state. Hidden classes are excluded from its bars/rows and the axis fits the remaining data. Filtered Gantt uses a linear elapsed-time axis starting at zero: visible steps are concatenated and hidden durations contribute neither offsets nor axis extent. Its Start cells use that same filtered axis and retain the original cycle start in their tooltips. The filtered axis is explicitly labelled. Full-cycle totals and PLC aggregates remain unchanged. The trend labels the selected-class sum as Shown, retains the full cycle’s readout, and omits the full-cycle best reference while filtered. Empty selections are explicit and retain the chips/Show all; a class disappearing from the data releases its hidden state so it can return visible. Command timing aggregates do not carry time classes, so no work/wait attribution is inferred for them.

Any module may publish Safety : ST_SafetyStatus and ControlPower : ST_ControlPowerStatus; Present=FALSE hides the card. A root Unit additionally publishes read-only Domain : ST_ControlDomainStatus and Status.ControlDomainId ('' = no arrangement). Its application-fed ControlDomain input is private and excluded from the Self-Description Service; clients bind only Domain (TC3 realizes the exclusion with OPC UA publication attributes). One domain may serve several root Units; mirrored cards with the same ID are one shared domain, not independent power controls. Safety rows are read-only and include device kind/state, demand, safe-state feedback, reset-required, fault, muting, keyed bridge, fieldbus health, and affected power groups. Muting/bridge are conspicuous and never rendered as normal bypass controls. Control power shows domain Control On/Off state, affected member Units, and each named power group’s request, feedback, safety permit, fieldbus health, reaction, and rearm requirement. Start is unavailable when an assigned domain is not ReadyForStart; an unassigned Unit adds no gate. The ordinary HMI never writes safety reset, bridge, muting, or guard unlock.

Control On/Off is data-driven through the selected root Unit’s HmiRequest mailbox (CONTROL_ON / CONTROL_OFF). The base acknowledges only after applying the POWER_CONTROL access gate, then emits one-scan ControlOnRequest / ControlOffRequest outputs. A one-Unit application may consume those pulses locally; a shared-domain application shall route every member request to the single domain coordinator. Reconnection never replays either request.

System health, clock quality, and signal tower (§2.7/§8.12/§8.13)

Section titled “System health, clock quality, and signal tower (§2.7/§8.12/§8.13)”

A Unit with SystemHealth.Present=TRUE renders the bounded live health card from task cycle/jitter/overrun, explicit controller/IPC/fieldbus/DC availability and values, and SystemHealth.TimeQuality. Unavailable is distinct from zero and a clock that is unavailable, unsynchronized, or outside the configured tolerance is conspicuous. Within the IPC group, FanAvailable/StorageAvailable say whether FanHealthy/StorageHealthPct are measurements; LostFrameCount/SlaveErrorCount count the current or last complete 10 s window, not the master’s lifetime totals. SignalTower renders the semantic Red/Amber/Green/Blue/White/Horn and TestActive state beside it; no HMI code knows electrical output addresses.

The System health card: HEALTHY, a lamp test button, clock PTP 12 µs, task 1000 µs, jitter 28 µs, CPU 23.8%, memory 2048 MB, and a five-lamp signal tower.

System health, clock quality and the signal tower, from the station’s published facets.
  1. Clock synchronization: PTP, 12 µs.
  2. The station’s signal tower.
Browser HMI simulation at revision a1163c7 · try it

Lamp test writes only append-only mailbox request LAMP_TEST := 26. The control is shown through the existing act-or-explain path, requires the Unit’s MANUAL access gate and an idle Unit, waits for acknowledgement, and is disabled while TestActive. The PLC owns the bounded timeout, so disconnect never leaves the test latched. Health/tower fields are generic Unit facets and shall not create a station-specific page.

Status as any module; link detail: LastSeen/Reaction are on the connector’s mirror/diag (Status.Diagnostic = link first-out when unlinked).

While a station’s engineering-gate register is non-empty the PLC raises one COMMISSIONING_GATE_ACTIVE (reason 2030) event per active gate: LOW severity, SYSTEM category, AUTO_RESET, and rationalized not shelvable. The client shall render a permanent, non-dismissible indication for as long as any such event is active, listing each gate’s localized description.

A commissioning notice: Commissioning build, this station is not running its production software. Simulation driver active: physical outputs are held off while the plant is simulated. Output forcing enabled: fieldbus outputs can be driven by hand from the HMI.

A commissioning build says so on every screen and lists each gate that is open.Browser HMI simulation at revision a1163c7 · try it

It is deliberately a separate strip from the global alarm banner. That banner shows the single worst active event, and this is the lowest-priority event the framework raises — so during commissioning, the phase that produces the most process alarms, a severity-ordered banner would bury the one message that says the machine is not running its production software. For the same reason the strip is warning-tinted rather than error-tinted: the station is not faulted, and dressing a build statement as a fault trains operators to ignore real ones.

Three things the client shall not do: offer a close/dismiss control (no operator action closes the underlying event, so a dismissible banner would give that capability back); filter the event by Shelved (the reason is not shelvable, and honouring a shelf would defeat the clause); or infer the gate set from anything but these events. The strip disappears when the PLC stops reporting gates, which — gates being build constants — means a new download.

The physical topology binds Topology : ST_FieldbusTopology: NodeCount, Nodes[] : ST_BusNode, MappingValid, and MappingDiagnostic. An invalid mapping is a commissioning fault and shall be displayed rather than treated as an empty/healthy bus. Discovery reads NodeCount and each active node’s ChannelCount before traversing the bounded arrays; unused fixed-array elements are not part of an HMI snapshot. For every ST_IoChannel, the client maps Name, DescriptionKey, Address, Path, ModulePath, Dir, Kind, values, Unit, Forced, Quality, FaultActive, Diagnostic, and Forceable. Name is the exact approved electrical/I/O-list tag and is shown verbatim in monospace; DescriptionKey and Diagnostic are localized by the project catalog. Address shows the terminal/channel locator. Path remains the unique forcing/audit identity, while ModulePath opens the owning module and defines the HMI assignment boundary. Forceable is an explicit PLC capability and defaults false when absent; output direction by itself never creates a force control. It is additionally FALSE on every channel unless the deployed image carries an active §7.5 OUTPUT_FORCING commissioning gate, so on a production station the client renders no force affordance at all — absent, not greyed (§3.9). The client shall not offer a local switch to reveal it: the capability is a property of the controller image, and a client that could turn it on would be exactly the authority §7.5.1 denies. The force dialog states both why the control exists (a commissioning gate) and how far it reaches (only while the owning Unit is idle in MANUAL; starting it or leaving MANUAL withdraws every force), so it can never be mistaken for the manual-command path that goes through a module. A snapshot marked truncated=true is rejected before mapping and shall never produce a LIVE repository or an empty-but-healthy fieldbus view.

The Fieldbus view: an EtherCAT tree with terminals named by reference designation, and the channels of terminal =A1+S1-A11, a Beckhoff EL1008, each with its sensor designation, description, channel and module signal.

I/O identity in the fieldbus view: the cylinder fault’s sensor, =A1+S1-B41, is channel 1 of this terminal.
  1. The terminal, named by its reference designation.
  2. Each channel: the sensor’s designation, its description, the terminal channel and the module signal it feeds.
Browser HMI simulation at revision a1163c7 · try it

When FaultActive is true the channel and its diagnostic are highlighted. A module alarm simultaneously shows ST_Diagnostic.IoTag/IoAddress, so a cylinder timeout can read, for example, “press did not reach DOWN” plus _101B202A · EL1809 Ch5; the same exact tag is highlighted in the fieldbus tree. Transport adapters shall copy these fields without normalizing case, stripping the leading mapping marker, translating, or substituting a friendly label.

The manual-command card also displays the physical I/O whose ModulePath exactly equals the selected module identity, grouped as Inputs and Outputs. It uses the same channel records, preserves electrical tags verbatim and localizes descriptions. Analog signals show value and unit; forced and fault indications remain visible. Missing, non-Good or disconnected data displays unavailable quality rather than an assumed OFF value. This is a read-only surface; commands continue through the existing release-gated module path.

While that card is visible, the repository demands the selected channels’ quality/diagnostic fields and their bus ancestors’ health. Hidden or access-gated cards and other tabs withdraw that demand. The full bus view independently owns its broader demand; closing either consumer shall not stop the other. An HMI root assignment also bounds module I/O demand. The industry-inspired theme draws circular white down/up arrows for inputs/outputs, light green/red active fills and gray inactive fills. Unavailable quality has a distinct neutral mark.

Inline spacing: chips, badges, card-heading items and compact action groups use the unit card’s spacing. The shared kInlineItemGap visual token owns the horizontal gap, wrap-run gap and separation between stacked status rows, so similar groups inherit one policy throughout the client.

Control size: the selected compact/medium/large preset applies to pressable controls, including time/event filters, choice chips, chip actions and deletion, checkboxes, radio selectors and switches. UiMetrics owns their dimensions; button themes, PresetChip and PresetToggle share those metrics. Glyphs and tap areas grow together, with layout space reserved for the enlarged control. Read-only status badges retain their compact layout. Timing filters and their Show all action have the same height at each preset. The time-quality badge is the first item in the system-health metrics row, before Task and Jitter.

Tree highlighting (§3.13): per node, effective severity = max(own active events, children’s) with HIGH > MED > LOW; tint every ancestor down to the source, strongest at the source. Derived purely from Status/AlarmLog — no extra PLC symbols. Themes: Material 3, selectable (light/dark/high-contrast). The picker lists the industrial standard themes first - flat colour, colour reserved for status, the ANSI/ISA-101 high-performance greys leading - and the modern decorated ones (glow, glass, grid, paper, reflection) after; the grouping is derived from each theme’s finish, and a selection is still stored by its unchanging index. Theme changing is an HMI-local setting gated by a configurable minimum Access.CurrentLevel (default NONE = open) — it is client config, not a PLC gated action. Transports: every UI platform binds the abstract repository. Fraktal/TC3 native clients may use OPC UA directly and Web uses the repository gateway; Fraktal/AB uses its EtherNet/IP/CIP gateway for native and Web clients. Transport choice changes only the adapter, never the domain or UI contract.

Settings displays the active PLC/gateway endpoint to every operator when the connection owner provides it. This is the endpoint used to create the current repository, with URI user information, query and fragment removed. An ADS target retains its AmsNetId and runtime port; a direct CIP target retains its host and port. A gateway URL identifies the service and does not claim to identify the controller behind it. Editing setup does not relabel an existing session. The administrator Disconnect action closes that session through the connection owner; a new endpoint takes effect only after Connect.

The first-run wizard, step 4 of 5, Connect Fraktal HMI: the connection type menu open with PLC / gateway endpoint and Built-in simulation.

First run, step 4: no operator screen until a connection is configured. The demo uses the built-in simulation.Browser HMI simulation at revision a1163c7 · try it

Connection ownership precedes the operator shell. On first use—or whenever settings exist but have never produced a LIVE repository state—the HMI shall open a connection wizard. Step 1 configures and proves the endpoint. After LIVE discovery, step 2 lists canonical root Unit repository paths and requires at least one Unit assignment for this HMI. The selected paths are saved locally and form both a display filter and a repository write boundary, including fieldbus branches through their channel-to-module paths; global connection status remains visible. EverConnected becomes true only after the repository is live and Unit assignment is complete; saving an endpoint alone is not proof.

When settings have previously connected, startup goes directly to a full-screen Connecting to PLC view. The interactive HMI is not built while the repository is CONNECTING, STALE, or DOWN. A transition away from LIVE removes operator interaction immediately; commands are never queued or replayed across reconnection. After 30 seconds without LIVE, and not before, the view exposes Edit connection settings. A successful LIVE transition cancels that timer and opens the shell only if every saved Unit path is rediscovered; missing/renamed assignments return to step 2 fail-closed. An authenticated ADMIN may edit the Unit assignment later from the shell. Native settings use a local JSON file; Web uses browser local storage. Both are HMI-local connection configuration, not PLC recipe/station config.

Access levels (§7.7) — how the Flutter client behaves

Section titled “Access levels (§7.7) — how the Flutter client behaves”

An asynchronous provider may also publish read-only integer Access.LoginTimeoutMs, present from discovery onward. The generic repository uses a value in 1..600000 as its result wait after mailbox consumption; an absent, zero, negative or excessive value retains the six-second default. This budget describes the provider’s bounded computation and transport margin, not the session idle timeout. It cannot confer a role: the published result still decides authentication. A provider shall bound its per-task work independently of this client wait.

A provider may publish optional read-only integer Access.LoginResultSequence, present from discovery onward. It identifies the sampled mailbox request whose authentication has completed, independent of other mailbox acknowledgements. The repository shall wait for its own LOGIN sequence before accepting success or rejection; an older failure or session shall not settle the pending attempt. Comparison uses the unsigned 32-bit sequence representation, including bindings with signed DINT counters. Providers without this field retain the existing outcome fields.

The result wait uses a monotonic clock and also bounds an individual result read. A timeout, lost connection or unconsumed LOGIN is an unavailable result; the dialog shall not describe it as incorrect credentials. Only the completed provider’s negative result produces the generic user/PIN error.

Per root Unit: read Access.CurrentLevel / Access.CurrentUser / Access.LoginFailed, Access.Policy.Required[0..11] (index = E_GatedAction, including append-only ALARM_SHELVE at 9, POWER_CONTROL at 10 and CONFIG_SET at 11), and Access.Policy.SessionTimeout. A blocked control remains pressable only to open its release explanation; it never issues the mutation. Login is data-driven through the root mailbox; the PLC clears the transported secret after each attempt. Idle auto-logout (T#0S = never) is rearmed by successful login and accepted authenticated operator mutations, never by snapshot/manifest/release polling. An asynchronous access provider may publish the optional Boolean Access.LoginBusy, present from discovery onward; while TRUE the generic repository waits for its bounded result and the mailbox remains available. Providers without this field retain synchronous behavior. A mailbox Accepted acknowledgement means the login request was consumed, not that credentials were accepted; login succeeds only when the resulting access snapshot has LoginFailed = FALSE, CurrentUser equal to the requested user, and CurrentLevel > NONE. On failure the dialog stays open, clears the secret field, and shows a localized generic user/PIN error (never reveals which credential was wrong). Shipped default policy is fully open (all thresholds NONE) — a station may require no login at all. The settings view edits the selected root’s persistent policy through append-only mailbox kinds SET_ACCESS_LEVEL=24 and SET_SESSION_TIMEOUT=25, serially; both are PLC-rechecked against ACCESS_POLICY, and the PLC rejects raising that threshold above the active session level to prevent retained self-lockout. The PLC re-checks all mutations, including decisions, power, shelving, force, and configuration writes. Accepted privileged mutations and denied attempts land in the §8.3 ring without secrets.

Alarm shelving & rationalization (§8.9/§8.10)

Section titled “Alarm shelving & rationalization (§8.9/§8.10)”

Units publish the generated rationalization catalog (Meta: per-ReasonCode priority, category, operator action, consequence, and shelvable flag) which the HMI joins onto events by reasonCode — the alarm row shows what to do. The HMI carries the same generated catalog as a deterministic fallback for a partial/older manifest, while the PLC remains authoritative for alarm behavior. A record with no operator action is an event and is not rendered as an actionable alarm. Active alarms carry Shelved; a shelved alarm is de-emphasized (never hidden) in lists and excluded from the banner — annunciation only: Blocking, interlocks, and release reports are untouched. Shelve/unshelve via shelveAlarm/unshelveAlarm (ALARM_SHELVE-gated §7.7, act-or-explain §7.8, PLC re-checks: SAFETY never shelvable, unrationalized reasons refuse). Shelves auto-expire in the PLC (time-bounded); every shelve/unshelve/expiry is a §8.3 event.

The Events tab: two information events and the error Cylinder did not reach the commanded position at StationA.ClampStation.CylB with its I/O identity, a hint and a shelve button, above an event history with severities, reset classes and durations.

Active events with their source and hint, and the event history below.
  1. Shelve: silences the annunciation, is logged, and leaves control unaffected.
  2. The I/O behind the event (the sensor’s reference designation, terminal and channel) and the hint shown with it.
  3. History: each event with its reset class and how long it lasted.
Browser HMI simulation at revision a1163c7 · try it

Units publish Oee (run/down/idle ms buckets + Availability/Performance/Quality/OEE, each with a validity flag) and OeeTrend (bounded sample ring). The HMI renders an OEE facet: factors + OEE% with exception-based colouring (muted at/above target, amber/red below) and a sparkline from the ring. Invalid factors render as ‘—’ and are omitted from the product — never assumed 100% (O7). resetOee is DATA_WRITE-gated (§7.7), audited (§8.3), and follows act-or-explain (§7.8). Long-horizon trending is the historian’s job, not the ring’s.

A module with a non-empty Nameplate (ST_Nameplate: product URI, manufacturer, designation, serial, year, HW/FW/SW versions, order code, documentation URL) renders a nameplate facet card on its detail view — identity, versions, and a tappable documentation link. Read-only by contract: identity, not configuration (outside §3.8/§7.7 entirely). Empty nameplate = no card. Root Units always publish one; any module may (a purchased CM keeps its own identity). Projection to AAS/IEC 63278 (IDTA 02006 Digital Nameplate et al.) is Annex K.

Release panel (§7.8) — “why is this blocked?”

Section titled “Release panel (§7.8) — “why is this blocked?””

Pressing a blocked control (Start, or a manual command) never silently no-ops: it opens a persistent bottom panel immediately in a localized “checking release conditions” state, then calls the pure query releaseReportStart(unitPath) or releaseReportManual(unitPath,targetPath,value) and renders the FULL rollup — every unmet precondition at once (mode, access, active alarm, and each failed interlock), each with its localized description, kind icon, numeric reason, and qualified owning SourcePath. The manual query includes the selected command value because directional interlocks may differ. The panel stays while blocked and can be dismissed; while open it refreshes at a controlled, non-overlapping interval, and when the action releases it shows a brief ‘now released’. A repository snapshot emitted by a query acknowledgement shall not itself trigger another query (that feedback loop can flood the PLC mailbox). The query computes the same predicate the gate uses (no drift). Interlock reasons reuse the §7.2 PermIntlk descriptions. Every gated control follows act-or-explain — Start/Stop/step/reset/changeover/manual open the release panel when blocked; channel force (fieldbus-scoped) explains inline. No gated control is ever a silent dead button. If a rejected action yields no reasons, the panel explicitly reports the contract/publication defect rather than rendering an empty area.

Right-side vertical bar controlling the selected module’s owning Unit: mode selector (current-mode icon on top, menu of supportedModes), play/stop at the bottom (play = start; while running it becomes a red stop = graceful stop, finishing the sequence — reads running), and an optional step toggle cycling CONTINUOUS→SINGLE_STEP→HOLD_TO_RUN for modes whose supportedRunStyles allow it (setRunStyle; SINGLE_STEP shows a step button → stepRequest; HOLD_TO_RUN shows a press-and-hold → setHoldRun). MANUAL shows no play/stop/step (no sequence). The stop button blinks while stopPending (stop requested, sequence still finishing) and is non-interactive during that window. Per-step steppable (default true) means some steps run through even in step mode (published on CurrentStep). Mode changes honour the per-mode modePolicy (§3.4.1): blockedWhileRunning refuses with a hint, confirm prompts (graceful “finish & switch” vs immediate “interrupt & switch”), interruptible proceeds. Hold-to-run is NON-SAFETY (§3.4.2/§9) — never a dead-man. All gated by MODE_CHANGE/START_STOP (§7.7).

Each CM/EM publishes a command catalog ({value,label} list); the HMI renders a button per entry — no per-type code. A command is issued via manualCommand(unitPath, targetPath, value) and accepted only when the owning Unit is in MANUAL mode (§3.4) and the user holds MANUAL access (§7.7); it routes through the module (interlocks/first-out/timing still apply — the opposite of a fieldbus force). Every accept/reject is a §8.3 event. The panel is visually distinct from the fieldbus force (bordered ‘Manual commands’ card on the module) so the two risk levels are never confused. Single path only — no mode-bypass override.

Writes are limited to module Command + Execute/Abort, DecisionAnswer, Unit mode/run-style/start/stop/step/hold, release-gated manual commands and bounded lamp test, alarm reset/shelving, model/configuration changes, and explicitly authorized channel force. Every path is gated and re-checked by the PLC; commands are never queued across connection loss.

For a guided model change, the HMI writes CHANGEOVER mode, submits the selected model through the transactional model request, then starts the Unit sequence. The live CurrentStep and Decision records drive the instructions and confirmation buttons; no press- or station-specific page is used.

Every transport adapter shall issue those operations through the root Unit’s typed request/response mailbox; it never calls PLC-language methods or exposes a generic symbol/tag write. Arguments are written first and the nonzero commit sequence last. The Unit samples a new sequence once, routes it through the same operations and release gates used internally, clears transported secrets, and writes the matching acknowledgement only after processing. TC3 names these records HmiRequest : ST_HmiRequest / HmiResponse : ST_HmiResponse; AB uses the logical schema in Part III §7.7 and freezes its physical layout after S9/S12. See OPCUA_TRANSPORT.md for the TC3 mapping.

The repository shall serialize each mailbox transaction, shall not allow a periodic refresh to starve its writes, and shall wait for any already-running refresh before evaluating acknowledgement data. Control success means the exact Sequence was acknowledged and Accepted=TRUE; rejection and timeout are different results, and the PLC’s localizable Diagnostic is logged/displayed for a rejection. Static browse discovery should be cached for the session; cyclic updates use subscriptions or bounded batch reads rather than recursively rediscovering the complete hierarchy every refresh interval. The repository gateway exposes the same tier capability as any direct adapter through versioned path discovery, compact tier indices, and bounded targeted reads. The gateway intersects every connected browser’s slow/on-demand sets before changing its one shared PLC session, so one client can never reduce another client’s live surface. Optional deployment read-root subtrees filter snapshots, discovery, tier setup, and targeted reads consistently; the selected PLC/transport authorization remains the primary confidentiality boundary when no additional gateway read scope is set. Discovery shall canonicalize module identity before rendering. Status.Name is the qualified dotted identity (Root.Child); a real module’s declared local segment equals the final segment of that identity. Candidates are deduplicated by the complete Status.Name, and declared parent/root identity must agree with its dotted prefix. TC3 chooses the shallowest matching OPC UA path and rejects a REFERENCE TO/owner alias whose local browse segment disagrees; AB rejects an inconsistent manifest ID/path/parent row. Duplicate root identities are a contract/deployment diagnostic and shall never be passed unchanged into station selectors.

Line calendar and shift history (Core §3.8e / §8.5.2)

Section titled “Line calendar and shift history (Core §3.8e / §8.5.2)”

Calendar V3 adds line.shift.<index>.productionTarget (good parts, 0 unset) and may increase the declared shift capacity; the weekday editor recognizes any positive declared row index, including the fifth row. Configuration is still read from the complete PLC page and written through its capability gates. ShiftProductionTarget is the PLC-latched target for the current interval; ShiftHistory[index]/ProductionTarget is its immutable closing snapshot. The Shift card renders current GoodCount / target, attainment percentage and a bar capped visually at 100%, while percentages may exceed 100%. Its history table shows each record’s own target and attainment. NOK/rework do not count toward the good-part goal. Zero shows an unconfigured target and no progress bar; absent target leaves legacy binding presentation unchanged. The client never looks up today’s calendar to assign targets to old records.

The Shifts card: shift 1 since 06, next boundary 14, 919 of 1200 good parts, and a table of past shifts with their targets and counts.

Shift history on the Statistics tab: the running shift against its target, and past shifts from the line calendar.Browser HMI simulation at revision a1163c7 · try it

Line config uses the normal LINE_CFG capability editor. For calendar V2, line.shift.<1..MAX_SHIFTS>.activeDays is an integer mask 0..127 rendered as seven translated weekday checkboxes, Monday bit 0 through Sunday bit 6. The controls use the selected interaction preset and shared inline spacing; effective PLC read/write permissions still govern their input and Save action. Start and duration remain bounded number capabilities in minutes. A parameter set is a complete calendar transaction, validated on the PLC before commit.

A root publishes CurrentShift, ShiftStartedAt, the bounded ShiftHistory/ShiftHistoryCount and ShiftHistoryTruncated. Calendar V2 may also publish ShiftEndsAt, ShiftTimeSynchronized and ShiftCalendarPending. The facet exists when CurrentShift is present, including 0 (Unscheduled), and is absent when the root has no line. Show the next boundary and pending calendar changes. Relative elapsed/remaining display is an approximate clock view, shown only with verified clock quality; it never accumulates production.

Each closed row carries its controller-owned boundary times, time-quality and manual-reset flags, good/NOK/rework counts, run/down/idle milliseconds and OEE factors with their validity flags. The generic table displays those quantities; an invalid factor is shown as an em dash, and unverified or partial records are marked. The UI never reconstructs shift history from polls or clears totals. Version 1 producers retain their existing daily calendar and history shape; missing V2 optional fields do not invent a boundary or pending edit.

§8.3(d) I_EventSink historian implementations (OPC UA A&C / SQL / MES adapters — interface is normative and shipped; adapters are deployment work) and external §11.6 I_HostEventSink deliveries. The fixed bounded HostEvents Self-Description projection (OPC UA in TC3), HMI hydration, and §8.8/§8.9 generated catalog are shipped and freshness-checked; historian/MES/REST/MQTT delivery adapters remain deployment profiles. Core §8.10’s optional Alarm-performance profile (long-window rate/standing/stale/chatter/flood analytics) is likewise owned once by the chosen station/line aggregator or historian, not duplicated in every root HMI. Unknown external/application reasons still fall back to the PLC diagnostic description and require a complete runtime rationalization before they may be shelved.

The topology subtree is on-demand — identity, addressing and diagnostic text are large and only feed the bus page. The channel value is the exception and is live: Channels[i]/BoolValue and Channels[i]/AnalogValue are classified live even though they sit inside an on-demand container, because an operator watches an interlock that will not clear or a sensor that never comes on without opening the bus page at all. It is one leaf per channel, so the promotion costs a fraction of the subtree it lives in; Address, Path, Diagnostic, Forced and Quality stay gated.

A leaf-level liveLeaves rule is checked before the container rules, which is what lets it outrank the subtree it belongs to.

PLC symbol Type HMI use
<module>/StateFlagCount INT published length of the table below
<module>/StateFlags[i]/Key STRING localization key. Empty ⇒ the slot was never published: skip it, do not render a nameless chip
<module>/StateFlags[i]/Value BOOL the fact, as of this scan
<module>/StateFlags[i]/Since DT when Value last changed — not when it was last written. Render as a duration (“closed · 4s”)
<module>/StateFlags[i]/Stale BOOL the PLC stopped publishing this flag. Render as unknown, never as a confident “off” — the PLC has already forced Value false, and showing that as a claim would be inventing one

These are OutImm-role values: facts recomputed every scan from what is actually true underneath, as opposed to OutCmd, which is what a command produced and stays latched until the next one. Any module of any tier may publish them, so the HMI renders them generically from the key — it never needs to know the module type.

PLC symbol Type HMI use
<module>/SequenceViewEnabled BOOL shows or hides the Sequence tab for that module. The PLC owns this: a type too simple to be worth drawing leaves it FALSE, a Unit defaults TRUE and may vary it per mode. The HMI never infers it from the module type.
<unit>/SequenceStepCount INT published length of the rows below; a row beyond it is ignored even if present on the wire
<unit>/SequenceSteps[i]/StepNo INT row label (N100) and the key matched against CurrentStep/StepNo to find the active row
<unit>/SequenceSteps[i]/StepName STRING localization key for the row title. Served by the §3.10.2 config manifest, not cyclically — see below
<unit>/SequenceSteps[i]/Branch INT §6.12 concurrent leg. 0 = the chain’s main line; >0 indents the row under the fork and shows a ∥n badge
<unit>/SequenceSteps[i]/Active BOOL this row is running now. With a parallel step several rows are Active at once, which is why liveness may not be derived from CurrentStep
<unit>/SequenceSteps[i]/Elapsed TIME that row’s own clock
<unit>/SequenceSteps[i]/TimedOut BOOL that row outran its own ExpectedTime — a leg’s guard, since the §6.9 stall watchdog follows the main line only
<unit>/SequenceSteps[i]/AwaitingLabel STRING secondary line, e.g. PressRam.EXTEND. Manifest-served
<unit>/SequenceSteps[i]/AwaitsPath STRING drill-down target. Non-empty ⇒ the row is click-through and selects that module. Empty ⇒ tapping opens the step detail instead
<unit>/SequenceSteps[i]/TimeClass E_TimeClass shown in the step detail
<unit>/SequenceSteps[i]/ExpectedTime TIME the guard drawn beside the elapsed time (1.4 s / 2.0 s); 0 = no guard
<unit>/SequenceSteps[i]/Visited BOOL dims rows the chain has not reached yet
<unit>/SequenceSteps[i]/LastDuration TIME elapsed shown on an inactive row
<unit>/SequenceSteps[i]/ErrorActive BOOL this row raised an error (§6.9(d)). Marks the row red whether or not it is still the active one, unlike a timeout. This flag is authoritative — see the annotation table
<unit>/SequenceSteps[i]/WarningActive BOOL this row raised a non-blocking message (§6.9(e)). Steady mark, never the error blink — nothing stopped
<unit>/CurrentStepElapsed TIME elapsed shown on the active row
<unit>/CurrentStepTimedOut BOOL active row blinks between surface and error container

The Sequence tab: steps N10 to N80 with their commands and times; N40 Clamp the part is highlighted red at 4.0 s against 2.5 s, and N50 and N55 run as parallel branches.

The Sequence tab: the step chain the station publishes, each step with its command and its time against the expected time.
  1. The step that faulted: 4.0 s against 2.5 s expected.
  2. Parallel branches ∥1 and ∥2 under step N45.
Browser HMI simulation at revision a1163c7 · try it

Liveness is per row (§6.12). A chain with a parallel step has one Active row per leg, so the HMI shall highlight every Active row and show each one’s own Elapsed. When no row reports Active — an older runtime that does not publish it — the HMI shall fall back to matching CurrentStep/StepNo, which is the pre-§6.12 behaviour, so the tab never goes blank against an older PLC. CurrentStepElapsed and CurrentStepTimedOut remain the main line’s clock and guard.

A row arrives from three places, and the HMI joins them. The row was split by how often each part changes, so that a 128-row chart costs ~47 kB per Unit instead of ~145 kB:

part where it comes from changes
StepNo, Branch, TimeClass, ExpectedTime, StepName, AwaitingLabel, AwaitsPath the §3.10.2 config manifest, published under these same SequenceSteps[i]/… repository paths never, after first visit
Active, Elapsed, TimedOut the ActiveSteps cursor, one entry per concurrent leg, joined by RowIdx — live tier per scan
Visited, LastDuration, ErrorActive, WarningActive the SequenceSteps array (on-demand read) over time, per row
the text and link of an error/message the SequenceAnnotations table, joined by RowIdx rarely, and sparse
PLC symbol Type HMI use
<unit>/ActiveSteps[b]/RowIdx INT the SequenceSteps row leg b is running. 0 ⇒ that leg has no active step. A row is Active exactly when some leg’s cursor points at it
<unit>/ActiveSteps[b]/Elapsed TIME how long that row has been running
<unit>/ActiveSteps[b]/TimedOut BOOL it outran its own ExpectedTime — the leg’s own guard

The cursor is indexed by branch (0 = main line), so it is ~10 entries however long the chain is. It is small enough to stay in the cyclic read, which is what makes the chart correct the instant its tab opens instead of after the first on-demand read.

What the HMI shall NOT reconstruct. Visited, LastDuration, ErrorActive and WarningActive stay per-row and PLC-authoritative, and a client shall not derive them by watching the cursor. The HMI polls at a few Hz; the PLC steps at scan rate, so a step shorter than one poll interval is never observed. A chart that accumulated these client-side would silently skip fast steps, mistime visits, and lose transient errors entirely — it would show what the client happened to catch rather than what the chain did (§1.1 O3).

Because the manifest reproduces the live half’s repository paths, the mapper reads SequenceSteps[i]/StepName without knowing it arrived by a different route. The HMI should cache manifest values and re-fetch on Status/ConfigRev.

PLC symbol Type HMI use
<unit>/SequenceAnnotationCount INT published length of the note table
<unit>/SequenceAnnotations[i]/RowIdx INT the SequenceSteps row this note belongs to. 0 ⇒ a freed slot: skip it, it is not a note
<unit>/SequenceAnnotations[i]/IsError BOOL TRUE = §6.9(d) raise (the chain stopped), FALSE = §6.9(e) message
<unit>/SequenceAnnotations[i]/Key STRING localization key of the reason or message
<unit>/SequenceAnnotations[i]/SourcePath STRING module to drill into; empty ⇒ the Unit itself

The row flag is authoritative, not the note. The note table is small on purpose; if it fills, the PLC keeps ErrorActive/WarningActive and drops only the text. The HMI shall therefore colour a row from its flag and treat a missing note as “nothing more to say” — deriving the mark from the note would silently unmark a real failure.

The rows are an on-demand subtree. SequenceSteps is bounded at MAX_SEQUENCE_STEPS (128) × 17 fields = 2176 nodes per Unit and feeds exactly one view, so it shall be read by a targeted batch while the Sequence tab is open and never in the cyclic snapshot — the same treatment as the rings and trends (§3.10, §1.1 O4). SequenceViewEnabled, SequenceStepCount, CurrentStepElapsed and CurrentStepTimedOut are leaves at the module root and stay live.

Consequently the tab’s existence is decided by SequenceStepCount, not by the rows. Gating it on the rows would deadlock: no tab → no on-demand read → no rows → no tab.

The chart belongs to the ACTIVE mode. The PLC clears the row table when a mode commits, so SequenceStepCount drops to 0 and rebuilds as the new chain runs. The HMI therefore renders whatever is published without filtering by mode, and must tolerate the count going to 0 and back up — that is a mode change, not a lost connection.

The inventory is discovered, not authored. The PLC registers each step the first time it runs, so a chain author writes nothing and a step not yet reached is simply absent — the chart shows what the chain has actually done, never a hand-maintained drawing that can drift from the code.

A raised error supplies the link Awaits could not. When a step raises an error explicitly (Core §6.9(d)) — a child commanded behind an IF, or an application rule — the PLC stamps that row’s ErrorActive and ErrorSourcePath. The HMI shall resolve a row’s target most-specific-first — ErrorSourcePath, then WarningSourcePath, then AwaitsPath: the operator wants the module that actually went wrong, not the one the step nominally commands. A row with neither stays non-click-through and opens its detail, where the raised error is listed. The marks are cleared by the PLC when the error state ends, so a stale red row is a PLC contract violation, not something the HMI ages out.

A message is not an error. WarningActive reports a condition the chain handled — press AUTO N180 (two-hand released while the door closes) and N200 (the ram did not reach, which the chain confirms and scraps) both use it. The row is tinted steadily and carries an info marker; it shall never blink, never be coloured error, and never be counted as a fault. It still supplies a drill-down link through WarningSourcePath, which is how N200 stays click-through to the ram with AwaitsPath empty. The PLC clears the mark when the step is entered again, so an amber row means “this is what happened on the last pass”.

AwaitsPath is the “direct wiring” rule. A row is click-through only when the step declared the module it commands through Awaits; no IF/CASE chose it. A step that drops its await — to own that child’s failure and disposition it itself, as press AUTO N200 does — publishes an empty path and is deliberately not click-through. The HMI must not guess a target from the label.

Optional runtime model catalog and current-value export

Section titled “Optional runtime model catalog and current-value export”
Published value HMI use
ModelCapacity > 0 Show New model with the current catalog count and capacity.
AvailableModels[*].ModelCode Source-model selection, uniqueness feedback and the existing edit/changeover selectors.
Features/ExportCurrentConfig = TRUE Show Export current values on each supported configuration card.

New model sends CREATE_MODEL (37): NameValue is the new code; IntValue selects the source model (0 = running); BoolValue = TRUE selects a saved Model set named by TextValue. The dialog states that creation is inactive, remains open on refusal, and closes only after acknowledgement. It requires CONFIG_SET and DATA_WRITE to offer the action; the PLC rechecks every copied value’s read and write permissions. Creating an inactive model does not require READY. A Model set offers Create model from set when the root advertises capacity; this does not load into the running recipe. Activation uses ordinary Changeover.

Export current values sends EXPORT_CURRENT_CONFIG (38) with TextValue for the export name, IntValue for ConfigKind and DurationMs for the model index (0 = running). Header line zero and successive EXPORT_CONFIG_SET lines form one immutable, connection-scoped document. The client generates a fresh 128-bit hexadecimal token in NameValue for the header and every continuation. TC3 binds its cursor to that token, the PLC session generation and the exact next line. Logout, an intervening operation, a foreign token or an out-of-order line invalidates the cursor. Saved-set exports keep NameValue empty. Any missing/refused line rejects the entire export. A current export does not consume a saved-set slot. Current and saved exports offer Download file (.jsonl, UTF-8) and Copy.

Missing/zero ModelCapacity hides creation; a missing/false export feature hides current export. Capability absence never implies a platform-specific fallback.


Built from Specification/HMI_CONTRACT.md at revision a1163c7 of the Fraktal repository.