Annex G — Worked Example: Motion Control Module (PLCopen Motion)

Companion to Fraktal Core (Part I) exercised through the Fraktal/TC3 binding (Part II); slots under Core §12. Core concepts demonstrated: motion CM behind the handshake (§10.6), target validation (§5.6), read-only safety & no auto re-enable (§9), base-class inheritance (§2.2). / TC3 mechanics used: TwinCAT NC PLCopen Motion MC_*/AXIS_REF (NcToPlc), OPC.UA.DA pragmas (TC3 §3.10). Reference implementation — illustrative, not compile-tested; validate against the pinned TwinCAT version and your axis/drive.

This annex builds a motion Control Module (§10.6) and shows what the pneumatic CM of Annex A can’t: an axis driven through the PLCopen Motion MC_* blocks behind the same handshake every other CM uses, with target validation before motion (§5.6) and a safe stop on a dropped safety alias (§9). To the Unit, a servo indexer looks identical to a cylinder — named commands in, Busy/Done/Error out.

It slots under the Annex A–C station as the infeed indexer:

InfeedUnit (FB_InfeedUnit : FB_Unit) ← Annex C
└─ Indexer (FB_AxisCM, Control Module) ← here
└─ MC_Power / MC_Home / MC_MoveAbsolute / MC_Stop / MC_Reset (PLCopen Motion)

G.1 Reasons (per-module-type block — register in §8.8)

Section titled “G.1 Reasons (per-module-type block — register in §8.8)”
// E_Reason — axis CM band 10200–10299 (per module-type, §8.8)
// AXIS_TARGET_OOR := 10201 // commanded target outside soft limits (rejected, §5.6)
// AXIS_MOVE_TIMEOUT := 10202 // MC move did not complete within MoveTimeout
// AXIS_DRIVE_FAULT := 10203 // MC_* .Error / drive fault
// AXIS_NOT_HOMED := 10204 // MOVE_TO before a valid home
// AXIS_JOG_NOT_ENABLED := 10205 // teach jog asked with no enabling device held (G.4a)
// AXIS_JOG_RELEASED := 10206 // the held jog request stopped arriving (G.4a)
{attribute 'qualified_only'}
// JOG_POS/JOG_NEG are HELD commands (§7.6.1a): two entries rather than one plus a
// direction, so a generic HMI renders two hold-buttons with no axis-specific code.
// They never reach _M_Dispatch — a jog is not an Execute/Done command.
TYPE E_AxisCommand : (NONE := 0, HOME := 1, MOVE_TO := 2, JOG_POS := 3, JOG_NEG := 4) DINT;
END_TYPE

G.2 The axis CM (PLCopen Motion behind the handshake)

Section titled “G.2 The axis CM (PLCopen Motion behind the handshake)”

The CM holds the standard AXIS_REF and the MC_* instances; soft limits and scaling live in the driver/axis config (§10.3), not in sequences.

// Publication is inherited from the explicitly marked deployed root instance.
// Execute/Abort arrive through the base's ExecuteCommand/AbortCommand, and
// Busy/Done/Error/Aborted/ErrorID plus first-out stamping are base-owned (§2.2):
// the type is only its device logic.
FUNCTION_BLOCK FB_AxisCM EXTENDS FB_ControlModuleBase
VAR_INPUT
Command : E_AxisCommand;
ParCfg : ST_AxisParCfg; // SchemaVersion, SoftMin/Max, Vel, Acc, Dec, MoveTimeout, HomeTimeout
ParCmd : ST_AxisParCmd; // Target — latched by the base on the Execute rising edge
END_VAR
VAR_OUTPUT
OutCmd : ST_AxisOutCmd; // InPosition, Homed — valid on Done
OutImm : ST_AxisOutImm; // ActPos, ActVelocity, Homed, DriveEnabled, Diagnostic
Intlk : FB_PermIntlk; // e.g. "STO cleared" / "Zone2 safe" (read-only, §9.2)
END_VAR
VAR
_axis : REFERENCE TO AXIS_REF;
_step : INT; _homed : BOOL;
_pwrFb : MC_Power; _homeFb : MC_Home; _moveFb : MC_MoveAbsolute;
_stopFb : MC_Stop; _resetFb: MC_Reset;
_tMove : TON;
END_VAR
METHOD Setup : BOOL
VAR_INPUT Name : STRING(80); AxisRef : REFERENCE TO AXIS_REF; Recipe : I_RecipeProvider; END_VAR
THIS^._axis REF= AxisRef;
// This type declares NO interlock of its own: safe motion lives in the certified
// system and a library cannot name "STO cleared" for a station it has never seen.
// The application supplies that status through DeclareCondition/SetCondition (§9.2).
// recipe wiring (limits, velocities) as Annex A …

OnCyclic is the type’s device logic only — the Execute edge, ExecState, the Busy/Done/ Error/Aborted/ErrorID outputs, first-out stamping and reset are all base-owned (§2.2) and proven once in FB_Base_Tests (§5.7):

METHOD PROTECTED OnCyclic
// power + safety: enable only while the application's safety condition is healthy (§9.2/§9.3)
_pwrFb(Axis := _axis, Enable := TRUE, Enable_Positive := Intlk.AllOk, Enable_Negative := Intlk.AllOk);
IF NOT Intlk.AllOk AND Busy THEN
_M_SafeStop(); // G.4
END_IF
OutImm.ActPos := _axis.NcToPlc.ActPos;
OutImm.ActVelocity := _axis.NcToPlc.ActVelo;
OutImm.Homed := _homed;
OutImm.DriveEnabled := _pwrFb.Status;

G.3 The move command — validate target first (§5.6), map MC_* to the handshake

Section titled “G.3 The move command — validate target first (§5.6), map MC_* to the handshake”

Validate the request before the state, and both before commanding motion: a target outside the soft limits is malformed whether or not the axis is homed, and reporting “not homed” for an impossible target sends the operator to the wrong problem. It also makes both rejections provable without a licensed NC axis, since neither issues an MC_* call.

METHOD PROTECTED _M_Dispatch
IF (ParCmd.Target < ParCfg.SoftMin) OR (ParCmd.Target > ParCfg.SoftMax) THEN
_M_FaultN(Code := PL_ModuleReasons.AXIS_TARGET_OOR, Text := 'std.error.axisTargetOutOfRange');
RETURN;
END_IF
IF NOT _homed THEN
_M_FaultN(Code := PL_ModuleReasons.AXIS_NOT_HOMED, Text := 'std.error.axisNotHomed');
RETURN;
END_IF
IF NOT __ISVALIDREF(_axis) THEN
_M_FaultN(Code := PL_ModuleReasons.AXIS_DRIVE_FAULT, Text := 'std.error.axisNotBound');
RETURN;
END_IF
CASE _step OF
10:
OutCmd.InPosition := FALSE;
_moveFb(Axis := _axis, Execute := FALSE);
_tMove(IN := FALSE);
_step := 20;
20: // issue the PLCopen move; map its outputs onto the CM handshake (§6.1)
_moveFb(Axis := _axis, Execute := TRUE, Position := ParCmd.Target,
Velocity := ParCfg.Velocity, Acceleration := ParCfg.Acceleration,
Deceleration := ParCfg.Deceleration);
_tMove(IN := TRUE, PT := ParCfg.MoveTimeout);
IF _moveFb.Done THEN
_moveFb(Axis := _axis, Execute := FALSE);
_tMove(IN := FALSE);
OutCmd.InPosition := TRUE;
_M_Complete();
ELSIF _moveFb.Error THEN
_M_FaultStopped(Code := PL_ModuleReasons.AXIS_DRIVE_FAULT, Text := 'std.error.axisDriveFault');
ELSIF _moveFb.CommandAborted THEN
// Another motion command took the axis: that is an abort, not a defect —
// route it through the base's own abort path rather than inventing a fault.
AbortCommand();
ELSIF _tMove.Q THEN
_M_FaultStopped(Code := PL_ModuleReasons.AXIS_MOVE_TIMEOUT, Text := 'std.error.axisMoveTimeout');
END_IF
ELSE
_M_Fault(E_Reason.STEP_STALLED, 'std.error.undefinedStep'); // defined ELSE (§5.6)
END_CASE

MC_MoveAbsolute’s Busy/Done/Error/CommandAborted map one-to-one onto the CM handshake, so the parent Unit commands MOVE_TO exactly as it commands a cylinder EXTEND — it neither knows nor cares that a servo is involved (§6.1).


Safe-motion stays in the safety system; the CM only reads its status and reacts:

METHOD PRIVATE _M_SafeStop
_stopFb(Axis := _axis, Execute := TRUE, Deceleration := ParCfg.Deceleration); // controlled stop
_M_FaultStopped(Code := PL_ModuleReasons.AXIS_DRIVE_FAULT, Text := 'std.error.axisSafetyDropped');

The condition itself is not declared by this type: a library cannot name “STO cleared” for a station it has never seen, so the application supplies it through DeclareCondition/SetCondition and the type only reads Intlk.AllOk (§9.2).

The motion is brought to the §6 defined safe stop; re-enable after the alias returns is a deliberate reset (MC_Reset, then re-home if required), never automatic (§9.3, §9.4).


G.4a Teach jog under an enabling device (§7.6.1a, §9)

Section titled “G.4a Teach jog under an enabling device (§7.6.1a, §9)”

An axis has no teach pendant. Where a robot arrives with its own enabling device and its own jog, a servo axis has neither — so if Fraktal does not offer a conformant way to move one by hand, there isn’t one, and the gap gets filled per station with something worse.

The axis therefore publishes two held commands and accepts them through RequestHeldCommand:

_M_PublishHeldCommand(Value := TO_DINT(E_AxisCommand.JOG_POS), Label := 'std.command.jogPositive');
_M_PublishHeldCommand(Value := TO_DINT(E_AxisCommand.JOG_NEG), Label := 'std.command.jogNegative');

Every gate is weighed once per scan, in one place, so there is one thing to review:

drive := (_jogReqDir <> 0)
AND NOT _tJogStale.Q // the request is still arriving (§7.6.1a, O10)
AND _jogEnabled // a safety-rated enabling device is permitting (§9)
AND Intlk.AllOk // the module's own interlocks — NOT bypassed for teaching
AND NOT Busy // a commanded move owns the axis (§6.1)
AND __ISVALIDREF(_axis);

Four things about this are deliberate:

  • Interlocks are not bypassed. The station is expected to have wired its guard condition so the safety system’s teach grant satisfies it. If it has not, the axis simply does not jog. The enabling device is an additional requirement layered on the interlock, never a replacement — so a mis-wired station fails safe rather than gaining a back door.
  • ParCfg.JogVelocity is defence in depth, not the protection. The safety-rated reduced speed is the drive’s SLS or the cell’s safe-speed monitor. A limit a scan overrun or a download can remove is not what keeps a person safe.
  • Stopping is not a fault. A jog that ends because the operator let go is the designed behaviour, so it publishes OutImm.JogStopReason as status and raises no alarm — the same argument §6.1 makes for HELD. Filing it as a fault would fill the record with events that were never faults.
  • A functional stop stops the jog too. WithdrawOutputs withdraws it like any other output; otherwise an abort would stop the commanded move and leave a jog running.

The MC_Jog realization is [TC3]; another binding supplies its own level-driven jog behind the same RequestHeldCommand contract (O8).


G.4b Teaching the position — the other half of the jog (§3.8c)

Section titled “G.4b Teaching the position — the other half of the jog (§3.8c)”

Jogging an axis is only useful if where you got to can be kept. The axis therefore registers a taught position as an ordinary editable value and offers a capture for it:

M_RegisterConfigNumber(Key := 'axis.taughtPosition', Kind := E_ConfigKind.STATION_CFG,
Storage := E_ConfigStorage.AS_LREAL, pTarget := ADR(_station.TaughtPosition),
Minimum := ParCfg.SoftMin, Maximum := ParCfg.SoftMax, ...);
M_RegisterCapture(WriteKey := 'axis.taughtPosition',
pSource := ADR(OutImm.ActPos), SourceStorage := E_ConfigStorage.AS_LREAL);
  • STATION_CFG, not PAR_CFG. A taught position is what this machine is, not what the current product needs. It also could not live in ParCfg even if one wanted it to: I_RecipeProvider has Load and no Store, so the next changeover would overwrite a number an operator spent time teaching.
  • The capture rides the field it writes. M_RegisterCapture refuses a key that is not already registered as editable, so §3.8c(a)’s “a capture reaches only an already-editable field” is structural rather than a check someone could forget. The source is OutImm.ActPos, which the module already publishes, so the operator sees the number before storing it (§3.8c(b)).
  • Validation is the write path, unchanged. The capture resolves the live value to text and then goes through the same revision check, the same _M_OnConfigWrite invariant hook, the same range and domain validation and the same storage as a typed write. A machine-supplied number is not more trustworthy than a human-supplied one (§14).
  • Schema-versioned restore, written once in the base. ST_AxisStationCfg carries SchemaVersion first (§3.8b), and the axis calls M_RestoreStationCfg rather than carrying its own copy of the rule: version 0 is a first boot and initializes silently; any other unrecognized version means a real image was rejected, so the module runs on its declared defaults and the loss is reported to the root, which annunciates it with the axis’s own canonical path and the framework reason CONFIG_RESTORE_LOST (§8.8 band 2040–2049). Running on defaults while presenting itself as a commissioned machine is the failure that rule exists to prevent.
  • The axis does not decide what a loss costs. The consequence is the deployment’s, through E_ConfigRestorePolicy: DEFAULTS_AND_ANNUNCIATE runs the station with the annunciation standing, BLOCK_UNTIL_ACKNOWLEDGED refuses START_STOP until an operator of at least ENGINEER level acknowledges the loss. An axis that faulted itself — which this annex previously described — would impose the strictest reading on every station that instantiates one.

Durability is now behind this (§3.8b). An accepted write is marked pending and driven to non-volatile storage within a declared bounded window, and the root publishes PersistPending / PersistFailed; the taught position takes part in named parameter sets as an ordinary (Scope, WriteKey) record, so a commissioned axis position can be saved, listed, exported as a JSON document, carried to another machine and replayed through this same validation. What remains unbuilt is the model-set load: a PAR_CFG set must be applied through the §3.8 changeover transaction rather than as per-field writes, which needs a recipe provider that can store as well as load, so that load is refused rather than performed the forbidden way.


Station ▸ Indexer (CM tile: state LED ← ExecState; pos 124.80 mm; Homed ●)
View Binding
Tile name; state LED ← ExecState; live ActPos; Homed LED.
Detail manual HOME / MOVE_TO <target> (release-gated, §7.6; target validated per §5.6); jog; the live Diagnostic.Description (e.g. “Target outside soft limits”).

  • An axis expressed through PLCopen Motion MC_* blocks, vendor-neutral, mapped onto the standard handshake so a motion CM is indistinguishable from any other CM to its parent (§10.6, §6.1).
  • Target validation before motion (AXIS_TARGET_OOR, AXIS_NOT_HOMED) — defensive coding (§5.6) producing a clean first-out reason instead of a drive crash.
  • Limits/scaling in the driver/axis (§10.3), not in sequences.
  • Safe-motion read-only: a dropped safety alias triggers MC_Stop and a fault, with no automatic re-enable (§9.2–§9.4).
  • A held manual action (§7.6.1a): jogging under a safety-rated enabling device, level-driven because PLCopen models it that way, stopping when the request stops arriving — including when it stops because the transport died rather than because the operator let go.
  • A new per-module-type reason block (axis CM 10201–10206) registered per §8.8.

End of Annex G (draft).