Fraktal/TIA — Siemens TIA Portal binding (working tree)
Press bridge/topology milestone (2026-10-17): the separate saved FraktalBench exchanges ordinary I/O with the physical 1214C. The generic HMI observes 3 live nodes and 14 fresh inputs; 10 DQ channels remain unconfirmed demands. Output gates stay FALSE. Both-family native checks and live/recovery evidence are in the report. P8 native PROFINET health/forcing and physical output acceptance remain open.
Line profile milestone (2026-10-17): generator 0.25 admits complete V3 Line declarations through the public entry point and integrates the local owner, calendar/targets, atomic Line sets and persistence in the wired press. The Line press fixture passes 37 Line checks and 64 GRAPH regression checks; the report records native read-back and the remaining scope. Partial engine experiments retain the explicit workbench API. OUC TCP remains the separate P12 phase.
Runtime model milestone (2026-10-17): generator 0.24 adds bounded root catalogs, inactive cloning from models or complete model sets, shared typed admission and atomic LOAD_DB catalog/data checkpoints. BUSY creation leaves the running and prepared recipes unchanged. The model fixture and qualification report record 31 PLC assertions, 110 live checks, actual restart/corruption recovery and fresh-project read-back. The press advertises capacity 4 over its three seeds; GRAPH sequences and ST permissives remain wired. Complete Line integration, manual held actions, OUC, module/connectivity and deployment work remain.
Status: Phase0 runtime evidence; Phase2 tooling started. The binding is
Specification/Fraktal_TIA_Part_IV.md;
the plan is Specification/Siemens/SIEMENS_PORT_PLAN.md.
There is no released runtime library yet. The tree contains the engineering
driver, bench tooling, spike fixtures, declaration/frame generator and a shared
command-kernel prototype.
Do not describe it as a conforming implementation.
Latest qualification (2026-10-16): generator0.23 adds root data-class policy, raise-only minima and consistent manifest/write/capture/set/export admission. Separate class documents preserve the existing action-policy image. The class-policy report records16 PLC assertions,97 live/restart checks,254 tool tests and clean native runtime/press builds. See the fixture for the declaration grammar. Full Line integration remains; model creation is qualified below.
Operations qualification (2026-10-16): generator0.22 adds shared OEE/shifts/work
degradation, health/nameplates/build gates, shelving/tower/lamp test, pacing,
typed teach capture and fixed host-event rings. The254-source press now wires
GRAPH AUTO/HOME/CHANGEOVER/LoadPosition with ST permissives; ST/LD twins remain
unwired. The operations report
binds native compile/read-back,93 PLC assertions,46 live config/health/capture
checks and press jump/pacing checks. The fresh-project gate
creates only a reserved unmapped test CPU and always releases it. The saved
Fraktal image remains Press_Complete_20261015. P7 class/model work,
complete Line integration, module/connectivity expansion and deployment/physical
qualification remain open; host rings do not yet implement durable MES delivery.
Current continuation: generator0.21 adds typed configuration and complete
current-value exports through the existing provider, mailbox and generic HMI.
The selected two-root LOAD_DB runtime is
%LOCALAPPDATA%\Fraktal\TiaStations\Config_Types_Runtime_20261015\FrkS12\FrkS12.ap20;
the separate wired press is Config_Types_Press_Offline_20261015 under
the same station directory. See the typed configuration fixture
and qualification.
Earlier image names below describe dated gates. Shared recovery was qualified by
generator0.20 with the selected LOAD_DB/view/diagnostic/profile runtime.
See the recovery fixture,
the recovery report,
the profiling fixture,
the profiling report
and the diagnostic report
and the earlier integration/error report.
Fault recovery retains the failed step and rearms its command, delay and event state. A deliberate Start resumes or restarts according to project policy; the press restarts. Shared GRAPH adapters preserve the native transition boundary and reset pulse, release child commands while frozen and suppress inactive step publication. MAIN retains three calls. Provider/line config, baseline/reset/OEE, module/HAL expansion and deployment/physical acceptance remain separate gates.
After a VM restart, first inspect the registered instances. If the saved Fraktal CPU is unregistered, use Resume-TiaSimOwner.ps1 in a hidden persistent PowerShell process. It requires the existing storage, isolated adapter and expected identity, and refuses unexpected instances. Keep its keeper alive. Verify the pinned Web API certificate before writes; preserve the saved image rather than starting a new blank CPU with another name.
The owner retired 33 obsolete October11–13 AppData test-project copies on 2026-10-14, recovering 3.16 GB of physical disk space. Current projects, baseline, credentials, simulator storage and sealed evidence remain preserved. Older local project names below identify historical runs; their sealed sources and native exports remain in Evidence/Archives.
VS Code selects Fraktal.TIA.sln for this Siemens workspace. Historical evidence snapshots are excluded from Dart analysis/project discovery. The separate Allen-Bradley offline probe still requires the installed Rockwell SDK; selecting the Siemens solution avoids restoring that unrelated project. Reload the editor window after changing these workspace settings.
The implementation now has Framework/Core, Framework/Modules,
wired GRAPH/ST press demo and optional ST/LD examples, Tests, Spikes,
tools and immutable evidence payloads. The
Siemens specification working set
contains documents only. The relocation verifier preserves historical hashes.
The press demo now wires GRAPH AUTO/HOME and ST permissives in the owning Unit.
Main remains three calls. AUTO includes TC3 recovery choices, backwards jumps and
the native parallel join; ST/LD twins remain uninstantiated examples. The isolated
wired project is %LOCALAPPDATA%\Fraktal\TiaStations\Config_Sets_Press_Offline_20261012\FrkS12\FrkS12.ap20.
The Fraktal simulator runs the separate config-set/decision bench.
Generator0.9 adds bounded root decisions; its native checks and config/state/access
regressions are recorded in
the current evidence.
Physical press qualification and full sequence frontier conformance remain open.
S12/S4 on simulated1516 V3.0 now compile the complete Core-derived type layout and pass269-source canonical reimport. After the owner installed Advanced7, native symbolic Web API reads work on the preserved image. The reference timestamp mapping is now LDT: the candidate passes1081/1081 native witnesses, 1146/1146 SDK type witnesses and43/43 SDK scalar checks, retaining all88 types, 610 fields, Core capacities and full-width strings. The real HMI transport/date parser passes36 checks across99 Good leaves. Full Unit rendering and commands remain the Phase3 gate. See fixture workflow and upgrade evidence.
Earlier Advanced5 symbolic denial and its isolation controls remain frozen history. The upgrade changed the manager, compatibility DLL and virtual adapter; the comparison establishes recovery on this host without isolating one cause. The prior one-hour host-time comparison failed; simulator-time consistency passed separately. Hardware drift and synchronized UTC quality remain unproven.
Phase2 has started with the reference declaration model:
reusable types and root instances derive a registration inventory, validated
against Core widths and tiers. The frame/registry generator
now emits typed contracts, HAL bundles/calls, identity setup and compact registry
services. The two-root fixture passes103 runtime checks and native public/private
read checks;36 blocks/19 interfaces round-trip canonically. Its begin/end FCs are
test probes. The separate Lifecycle fixture now uses
the actual shared command kernel and passes238 assertions in55 cases, including
STOP/RUN replay, plus100 native public reads and7 private refusals.47 blocks and
18 interfaces round-trip canonically. --shared-runtime includes the kernel;
every type then declares its command catalog and ParCfg timeout. Full Unit
facets, alarms/state/recipe services and Phase3 HMI remain open.
The subsequent Unit control bench now passes103 native
checks for modes, mailbox, release/reset and local Part services, including
STOP/RUN.79 blocks/34 interfaces compare canonically. The current saved image
belongs to TiaStations/Unit_Runtime_20261011/FrkS12/FrkS12.ap20 at that scope.
The subsequent nested Unit/manual bench passes
120 native checks across24 instances, including three Unit levels, reset and
STOP/RUN.104 blocks/40 interfaces round-trip warning-free. Generator0.4 owns
typed manual routes, catalogs and pure release predicates. The current saved
image is TiaStations/Routing_Runtime_20261011/FrkS12/FrkS12.ap20.
The static manifest/native HMI bench now passes241
native manifest checks and120 routing checks with generator0.5. The real HMI
hydrates492 entries for24 modules, renders the manual controls and commands the
simulated CPU from the rendered button. Mailbox payloads stay off cyclic reads.
117 blocks/41 interfaces round-trip warning-free; production114/41 compiles0/0.
The current saved image is TiaStations/Manifest_Runtime_20261011/FrkS12/FrkS12.ap20.
This GUI gate uses an explicit test-only display policy at NONE; authentication,
full alarm/release/retention services and sequence/GRAPH integration remain open.
The access/session bench now passes122 native checks and120 routing regressions with generator0.6. Salted local hashes, asynchronous login/session enforcement and gated policy edits compile0/0. The HMI authenticates an operator and commands the rendered button under its normal OPERATOR display policy.129 blocks/42 interfaces round-trip; production125/42 compiles0/0. User/policy persistence and full MESSAGE/alarm audit remain open. Current image: TiaStations/Access_Runtime_20261011/FrkS12/FrkS12.ap20, owner instance Fraktal. See evidence.
The state/alarm bench adds generator0.7 derived states, nearest-Unit fault capture, AUTO_RESET/MANUAL_RESET active/closed events, recursive blocking/reset and an optional event callback. Native96/96 plus23/23 nested ownership checks and122/122 authentication regressions pass. The real HMI renders the fault and clears it through the reset button.148 blocks/45 interfaces round-trip0/0; production142/45 compiles0/0. Current owner Fraktal image: TiaStations/Alarm_Runtime_20261011/FrkS12/FrkS12.ap20. Shelving, durable sinks, retention, full diagnostics/releases and sequence/GRAPH integration remain open. See evidence.
The config transaction bench adds generator0.8 editable station config/model config, a local-retain provider and atomic model changes. Native120 config checks,122 authentication and96 state/alarm regressions pass; 190 authored blocks/52 interfaces round-trip0/0, production183/52 compiles0/0. The HMI/spec names now consistently read Station config, Line config and Model config. Current Fraktal image: Config_Runtime_20261011/FrkS12/FrkS12.ap20. Named sets, line config replication, other media and remaining Core services are open. See evidence.
What is proven (2026-10-08, evidence): the S2 fixture builds headless through Openness, compiles 0 errors / 0 warnings (software and hardware), downloads to the physical CPU 1214C, and its 17 self-test assertions pass on three consecutive download-and-restart runs.
And since 2026-10-08 evening (evidence):
the ASCII sources pass 17/17 on three more runs, and the CPU’s licence-free Web
API is on — HTTPS with a pinned project certificate, one UMAC user fraktal with
read/write-process-data rights only. tia_webapi.py browses the spike Unit (126
leaves, private state absent), reads it, is refused every write except the mailbox,
and commits mailbox requests acknowledged in ≈ 140 ms. Throughput on the 1214C is
≈ 57 ms per request + 15 ms per leaf.
S11 continued on 2026-10-09 (evidence): GRAPH supervision/acknowledgement/skip probes, OB100 and local invalid-index handling compile 0/0; 28/28 on PLCSIM after download and direct STOP→RUN; 19/19 on the physical 1214C after download/start. Native bench STOP→RUN and two code-only downloads in RUN also passed 19/19 (evidence); the second delta preserved DB, OB100 and mailbox state. The temporary diagnostics mode right is removed; gateway access and 19/19 verified (cleanup evidence).
Active GRAPH recovery continued on the simulated 1516 on 2026-10-10 (evidence): 16 checks passed, with 28/28 in fifteen completed baseline harvests. Reset while BUSY, STOP→RUN and reset after completion withdraw outputs and require a fresh Arm in the test owner. An FC delta preserves observed BUSY/step/DB state. A GRAPH body delta requests native sequence turn-off and DB reinitialization despite unchanged exported interfaces; uninterrupted GRAPH updates remain unpassed. The cylinder applies its interlock to outputs outside the idle guard.
S9 read/session probes also passed on the 1214C: two clients, pinned reconnect, idle-token invalidation with re-login and retained-token reads through STOP→RUN. One Web API batch spans multiple PLC scans (ten counter-read batches); snapshots stay eventually consistent (evidence).
S3 2026-10-10 measured the Unit idle guard and Core-derived optimized storage
(evidence).
The guard saves about 0.202 ms/idle Unit; both five-Unit/ten-CM variants passed
19/19. All compact tables together use 96.89/150 KB including the spike code.
Eight compact write definitions alone add 5.49 KB: share immutable metadata
instead of repeating dense maximum-sized tables per module. Candidate widths
and capacities live in Spikes/S3_Budget; complete
runtime/press fit and the released family profile remain open.
The gateway reaches it with --plc-endpoint s7web://192.168.0.10 --plc-certificate <pem> (WebApiSessionClient, OPCUA_TRANSPORT “Siemens S7 Web API transport”), and
the unchanged Web HMI served by that gateway discovered, rendered and commanded
(Start/Stop) the spike Unit on 2026-10-08 (S7 PASS, spike scope; evidence §10).
Decisions that shape this tree: TIA Portal V20 only; sequences in S7-GRAPH (SFC) + SCL (ST), with unwired LD examples and ST/LD release examples added by the owner on 2026-10-11; the press bench is ported without power control; self-description through the CPU’s licence-free Web API (JSON-RPC over HTTPS) into the Fraktal gateway, the embedded OPC UA server only as an optional licensed projection (Part IV §1). S7-1500 is the reference family; the S7-1200 is a constrained family.
Current implementation target: the simulated S7-1500 (Fraktal, CPU1516-3
V3.0, PLCSIM Advanced 7.0), with full Core/modules/press scope, SCL and generated
GRAPH. The physical 1214C’s 150 KB budget and compact S3 candidates apply to its
secondary compatibility profile. They do not gate or reduce the S7-1500 work.
tools/ TiaCli/ Fraktal.Tia.Cli — TIA Portal Openness V20 driver (C#, net48) s7_probe.py read-only: identify a CPU (SZL), dump an SZL, harvest test results tia_webapi.py Web API probe (S1W): pinned HTTPS, login, browse, snapshot, mailbox tia_lint.py source gate (Part IV §5.3 T-rules) + test_tia_lint.py; pre-commit fraktal_tia_graph.py S7-GRAPH writer (from a chain declaration + TIA's exported template), reader (canonical dump) and SCL rendition parity + its tests Invoke-PlcSimInstance.ps1 S7-PLCSIM Advanced instance: host/status/run/stop, read-only tag read plcsim_results.py validate a Runtime API read log against exact case IDs → JUnit s7_bench_mode.py guarded classic mode probe for the named bench (refused by V4.7.3) Enable-TiaOpenness.ps1 admin setup: Openness group, and whitelisting of a driver buildSpikes/ S2_Shape/ module FB frame, FRK_Begin/FRK_End/FRK_Hold, CM ×2, Unit, mailbox, SCL AUTO chain with parameter instances, self-test harness, TCP result server; station/build/download/webapi plans for the bench S11_Graph/ generated AUTO chain; Semantics/ (supervision/skip), Errors/ (local/OB121) S11_Scl/ physical 1214C startup and local-error observations, 19 rows total S9_WebRecovery/ concurrent/idle sessions, reconnect, batch coherence, retained-client STOP/RUN| Item | Value | Source |
|---|---|---|
| CPU | 1214C DC/DC/DC 6ES7 214-1AG40-0XB0, FW V4.7.3 |
s7_probe.py ident (SZL 0x0011) |
| Address | 192.168.0.10; TIA PG/PC interface Intel(R) 82574L Gigabit Network Connection #2 (adapter Ethernet1, 192.168.0.123/24) |
interfaces --scan |
| Station project | %LOCALAPPDATA%\Fraktal\TiaStations\FrkSpikeS2\FrkSpikeS2.ap20 — holds the certificate the CPU trusts |
see below |
| Running image | S2 + S11_Scl test image (ASCII sources), 19/19; result table TCP 2000, Web API HTTPS 443 | S11 evidence |
| Security (bench only) | access control via access level, anonymous = full access (no password), lowered protection accepted on download; web user fraktal (password DPAPI-protected in TiaStations\FrkSpikeS2.webapi.secret) |
Part IV §14 |
| Use | nothing connected; may be downloaded/stopped/reset for Fraktal work (owner, 2026-10-08) |
The bench is S7-1200: no S7-GRAPH, no REF_TO, no named value types, 150 KB
work memory. GRAPH renditions are proved on S7-PLCSIM V20 (S7-1500) until an
S7-1500 exists.
Engineering workstation prerequisites
Section titled “Engineering workstation prerequisites”- TIA Portal V20 (STEP 7 Professional) with Openness V20 — installed.
- Account in the
Siemens TIA Opennessgroup, then a new logon. - Every driver build whitelisted in the Openness firewall — it gates headless
instances too, by the exe’s hash; a rebuild fails with
EngineeringSecurityException: The operation has timed outuntil approved. Both:tools/Enable-TiaOpenness.ps1 -WhitelistExe <built exe>in an elevated shell. - .NET SDK (any recent) to build the driver (net48 via the reference-assemblies package; no Developer Pack).
- Python 3 for
s7_probe.pyandtia_webapi.py(standard library only).
Build the driver
Section titled “Build the driver”dotnet build FraktalCore/PLC/Siemens/tools/TiaCli/TiaCli.csproj -c Release --output FraktalCore/PLC/Siemens/tools/TiaCli/bin/candidate# Never overwrite an approved build. Whitelist the exact candidate (prerequisite 3).# Current approved driver: bin/candidate_s11_enumeration; hash in plan §11. Preserve its bytes.Run the S2 spike
Section titled “Run the S2 spike”$st = "$env:LOCALAPPDATA\Fraktal\TiaStations"; $src = "<repo>\FraktalCore\PLC\Siemens\Spikes\S2_Shape"$pc = 'pc=Intel(R) 82574L Gigabit Network Connection'# 0. ONCE per target: station project (hardware, bench security posture, certificate)Fraktal.Tia.Cli plan $src\station_1214c.plan --set work=$st# 1. every build: delete program, import sources, compile 0/0, export (no controller access)Fraktal.Tia.Cli plan $src\build_1214c.plan --set work=$st --set src=$src# 2. CONTROLLER-CHANGING: download to 192.168.0.10 (needs current authorization)Fraktal.Tia.Cli plan $src\download_1214c.plan --set work=$st --set $pc --set pcnum=2 --set um=keep --set protection=# (um and protection have no default: an unset one stops the plan before TIA starts)# 3. ~40 s later: harvest the self-test rows from the test image's result serverpython FraktalCore/PLC/Siemens/tools/s7_probe.py harvest --tcp 2000 --junit s2.xmlWeb API (S1W, licence-free self-description)
Section titled “Web API (S1W, licence-free self-description)”# ONCE: web server on (HTTPS only), its certificate, the gateway's web user.# The password is read from the environment only - never a plan, an argument or a log.$env:FRAKTAL_TIA_WEB_PASSWORD = '<from the site secret store>'Fraktal.Tia.Cli plan $src\webapi_1214c.plan --set work=$st# then download_1214c.plan (CONTROLLER-CHANGING) carries it to the CPUpython FraktalCore/PLC/Siemens/tools/tia_webapi.py --trust-first probe # pins the certificate oncepython FraktalCore/PLC/Siemens/tools/tia_webapi.py tree --root SpikeUnitpython FraktalCore/PLC/Siemens/tools/tia_webapi.py snapshot --root SpikeUnit --repeat 10python FraktalCore/PLC/Siemens/tools/tia_webapi.py mailbox --root SpikeUnit --kind 3 --int 1One manual step on S7-1200 V4.7: Openness V20 cannot set the web server’s
certificate type (neither getter nor setter). Set it once in the TIA editor —
PLC_1 > Properties > Web server > Security, “certificate loaded via the software” —
and save; the station project keeps it. Until then the hardware compile fails and
download refuses. The first download into the new posture needs --set um=reset
and --set protection=--accept-lower-protection; later ones um=keep and an empty
protection=.
The pin lives in %LOCALAPPDATA%\Fraktal\TiaStations\<host>.webapi.pin; a changed
certificate fails closed until someone deliberately re-pins it. mailbox writes the
arguments, then Sequence alone, and waits for AckSequence; it never replays.
Every driver run prints one JSON object per line — keep the log with the
evidence record. download refuses unless --confirm-target equals the CPU
address configured in the project, and answers security-relevant questions only
when an explicit flag says so.
If the bench refuses to connect (“Connect to module failed” / “Changing to
online mode failed”): the CPU holds a certificate from a project you are not using.
Use the station project. Recovering a CPU that holds a foreign certificate is a
deliberate, logged trust decision: add --trust-plc PLC_1 to one download.
Rules that already apply
Section titled “Rules that already apply”- Sources are ASCII text (
.udt,.scl,.db, GRAPH SimaticML) imported through Openness in file-name order — the numbered prefix is the dependency order. OneTYPEper.udt, nothing before the keyword. TIA reads BOM-less files as ANSI. (The S2 sources are ASCII since 2026-10-08; the image running on the bench was built before that conversion, until the next build replaces it.) - The TIA program is a build output; the TIA project is per-station
engineering state (certificate) kept under
%LOCALAPPDATA%\Fraktal\TiaStations. Never commit*.ap20. - Contract members sit directly on the module instance (the HMI finds a module
by its
Statuschild).Statusand the rootHmiRequestare published statics; outputs are written, never read, by their own block. Private state carriesExternalAccessible/ExternalVisible/ExternalWritable := 'False'; onlyHmiRequestisExternalWritablefor operator commands. The optional sink adapter exposes its metadata-onlyFRK_EventDeliveryReceipt.Requestseparately; status/replies and all implementation storage remain protected. - Every module FB calls
FRK_Beginfirst andFRK_Endlast, inside a generated quiescent guard (Part IV §3.14): an initialised, READY module with Execute/Abort low and nothing pending skips the lifecycle (≈ 0.20 → 0.053 ms per idle CM on the 1214C, measured); identity setup and derivedOutImmrun outside the guard, every scan. The S2 Unit uses two fences driven by one predicate after its mailbox; children, chain-result clear and mirrors stay outside (about 0.202 ms saved per idle Unit, S3 2026-10-10). Every child is called exactly once per scan by its owner. Full mode-hook quiescence remains a generator/runtime gate. - Identity comes from
#w := GetInstancePath(SIZE := 0);at setup, never from a typed string. A member namedNameis declared quoted ("Name"). - An open interlock during a command is HELD (busy, outputs off, reason at LOW, self-resume), as in the TC3 reference — never a fault.
Generator 0.10 adds named station/model config sets, with PLC-owned save/list/load/delete and JSON-lines export/import through the existing generic HMI. Typed owner handlers validate the entire set before a recursive commit; catalogs and transfer work are allocated per deployed root. The press demo opts into four station config slots and remains compiled offline. The current owner image is Config_Sets_Runtime_20261012/FrkS12/FrkS12.ap20. See the current set evidence. File/database media, line config and user/policy/alarm retention remain subsequent work. This continuation does not release a conforming runtime library.
Generator 0.11 adds user and access-policy retention with whole-image validation and volatile sessions. The current owner image is Access_Persistence_Runtime_20261012/FrkS12/FrkS12.ap20; the wired press remains offline in Access_Persistence_Press_Offline_20261012/FrkS12/FrkS12.ap20. See the current retention evidence. Alarm retention, other persistence media and broader provider forms remain open.
Generator 0.12 adds optional closed-event history retention for explicitly selected Unit scopes. Shared Core services own validation, restore and append. The current owner image is Alarm_Persistence_Runtime_20261012/FrkS12/FrkS12.ap20; the separate wired press is Alarm_Persistence_Press_Offline_20261012, compiled offline. See history evidence. Active-alarm restart policy, external durable sinks and other persistence media remain later gates.
Generator 0.13 adds optional manual-reset alarm recovery for a subset of history-selected Units. Shared services preserve ACTIVE/WAIT_RESET latches, reconcile fresh faults, fence descendant startup and complete interrupted closes. Commands, outputs and sessions stay volatile. Current projects are Alarm_Recovery_Runtime_20261012 and Alarm_Recovery_Press_Offline_20261012; the press remains compiled offline. See recovery evidence.
Generator 0.14 adds optional retained event delivery for selected Units, with framework-owned FIFO capture and a SQLite collector that commits before sending a gated metadata receipt. Current simulator project is Event_Delivery_Runtime_20261012; the wired press compiles offline in Event_Delivery_Press_Offline_20261012. Independent service authentication, other persistence media and physical loss commissioning remain open. See delivery evidence.
The S16 persistence spike qualifies asynchronous load-memory reads/writes, independent RAM/load values, optimized UNLINKED banks, restart and private access boundaries. Current diagnostic runtime is Load_Memory_Only_Runtime_20261013; its framework matches the event-delivery image. Config, named sets, users and policy continue using LOCAL_RETAIN while the shared keyed document adapter is integrated. The separately compiled press is unchanged. See S16 evidence.
Generator 0.15 adds the selected shared LOAD_DB document medium. Station config, all offered model config, named sets, private users and root policy restore through the generated composition barrier. Confirmed load-memory documents replace cached values; native read-back precedes durability. Current runtime is Persist_Medium_Runtime_20261013 and the separate offline GRAPH/ST press is Persist_Medium_Press_Offline_20261013. MAIN remains three calls in the press, and optional ST/LAD examples remain unwired. See the consumer evidence. The original S16 diagnostic projects above are preserved.
Generator 0.16 adds the optional shared sequence view: Core definitions served by the manifest, per-leg cursors, PLC-owned history and sparse annotations. The owning frame controls scan/mode boundaries; projects add no scheduling call. Current runtime is Sequence_View_Runtime_20261013 (synthetic events, LOCAL_RETAIN config); the separate Sequence_View_Press_Offline_20261013 compiles the view with LOAD_DB. Native 122 checks and press readback pass; native HMI table rendering and combined boot qualification remain work. See evidence.
Built from FraktalCore/PLC/Siemens/README.md at revision a1163c7 of the Fraktal repository.