Fieldbus diagnostics adapter — Fraktal/TC3 profile (TC3 §10.6)
How Fraktal/TC3 combines real EtherCAT health, reviewed engineering identity, and live HAL values without creating a second I/O authority. Binds Core §10.5.1.
The base profile is implemented: FB_EcBusHealth reads the master, the project
catalog owns electrical/channel semantics, and FB_IoTopologyPublisher validates
and publishes the join. I_FieldbusScanner remains an optional compatibility
seam for deployments that genuinely need richer vendor-specific discovery; its
fail-closed skeleton is not the default and is not a base-conformance gap.
Fixed contract
Section titled “Fixed contract”| Layer | Artifact | Where |
|---|---|---|
| PLC types | ST_FieldbusTopology, ST_BusNode, ST_IoChannel, E_NodeState, E_ChannelDir, E_ChannelKind |
Fraktal_Core/DUTs |
| Runtime health | FB_EcBusHealth (FB_EcGetAllSlaveStates) |
Fraktal_Core/Connectivity |
| Catalog/join | project FB_<Project>IoCatalog + FB_IoTopologyPublisher |
application + Fraktal_Core/Connectivity |
| Optional extension | I_FieldbusScanner + fail-closed FB_EcFieldbusScanner skeleton |
Fraktal_Core/{Interfaces,Connectivity} |
| HMI model/view | BusNode, IoChannel, FieldbusTree |
FraktalCore/HMI/lib |
E_NodeState ordinals (OFFLINE=0 … OPERATIONAL=4, FAULT=5) are the PLC/HMI
wire contract. NodeCount and each ChannelCount define the active bounded
surface; unused array capacity is not discovered or streamed.
Base profile — one validated composition
Section titled “Base profile — one validated composition”EtherCAT master ──Tc2_EtherCAT──▶ FB_EcBusHealth ─┐XAE/ESI/TMC + electrical list ──▶ project catalog ├─▶ FB_IoTopologyPublisherHardware Driver / HAL values ─────────────────────┘ │ ST_FieldbusTopology │ ADS / OPC UA / gatewayThis is the objective-aligned path: it works on every HMI platform, keeps bus knowledge out of the UI, and preserves the sole project Hardware Driver as the live-value authority.
- Reference
Tc2_EtherCAT; instantiateFB_EcBusHealthonce per master. - Import/generate one project I/O catalog from reviewed XAE/ESI/TMC and
electrical/I/O-list data. Do not repeat those literals in
MAINor CMs. - Configure
FB_IoTopologyPublisher, then map the master’s ordered slaves to catalog nodes. A count/order/identity mismatch is visible and keeps mapping invalid; it is never guessed away. - The sole project Hardware Driver copies live values from its HAL/process-image symbols into the publisher.
- Publish the single topology variable with the standalone OPC UA marker. ADS, native OPC UA, and Web gateway clients consume the same model.
EtherCAT runtime health
Section titled “EtherCAT runtime health”Master identity. FB_EcBusHealth accepts an explicit EtherCAT-master
AmsNetId and otherwise derives the conventional local master NetId from the
local runtime NetId. Multi-master or remote deployments shall configure it
explicitly.
Topology and state. FB_EcGetAllSlaveStates performs one asynchronous bulk
read. Its nSlaves output validates the catalog count and its zero-based
ST_EcSlaveState buffer supplies deviceState and linkState in master order.
The low state values map to INIT/PREOP/SAFEOP/OPERATIONAL; any high
diagnostic flag, including configured vendor/product/revision/serial mismatch,
maps to FAULT. An ADS/read failure marks the mapped segment offline. The first
scan is unconditional for control-health validity; later diagnostic refreshes may
be demand-gated while retaining the last published state.
Channels and scaling. Channel identity, direction, kind, unit, approved tag,
physical address, and owning module come from the configured PDO/XAE/ESI/TMC plus
the electrical I/O list—not from a generic live read. Live values come from the
same process-image/HAL fields consumed by control logic. Analog scaling comes
from the engineering configuration or the owning CM’s ParCfg. CoE reads may
enrich an optional vendor-specific adapter, but cannot replace the reviewed
catalog.
Mapping. FB_IoTopologyPublisher rejects invalid bounds, duplicate paths,
duplicate tags/addresses, missing module ownership, or unresolved diagnostic
tags. Failures set MappingValid=FALSE with a diagnostic instead of silently
guessing a relationship.
Force — output-only, opt-in, and project-resolved
Section titled “Force — output-only, opt-in, and project-resolved”Forceabledefaults false. A project enables it only for a reviewed mapped output and supplies the resolver in its output-authority layer.- The PLC checks Core §7.6/§7.7 and logs the §8.3 event. The resolver repeats path/direction/capability validation and rejects unknown, input, and safety channels.
- The resolver writes the mapped application output—never a raw master/process- image force. It cannot lie to input logic or reach TwinSAFE/FSoE.
- A running module may reassert its output. A runtime force is effective only in the documented stopped/MANUAL conditions; this is intentional.
The Press reference enables no force capability and supplies no resolver, so the HMI correctly exposes no force button.
Optional richer-scanner extension
Section titled “Optional richer-scanner extension”I_FieldbusScanner and FB_EcFieldbusScanner are retained for compatibility and
additive extension. A deployment may complete them when it needs vendor-specific
runtime identity or channel enrichment unavailable in the base profile. It shall
still validate against the project catalog, source live values from the Hardware
Driver/HAL, and use the project force resolver. Until qualified, the skeleton’s
Scan=0, RefreshValues=FALSE, and ForceChannel=FALSE are deliberate
fail-closed behavior—not a partially enabled feature.
HMI projection
Section titled “HMI projection”The HMI reads ST_FieldbusTopology through the selected repository:
- node state uses the aligned
E_NodeStateordinal; - digital and analog values retain quality, unit, exact
Path, andModulePath; - module↔fieldbus navigation uses the qualified module path and exact I/O tag;
forceChannel()always uses the PLC mailbox and never writes a fieldbus or process-image address directly.
Acceptance checklist
Section titled “Acceptance checklist”- Unplug a slave: its node becomes
FAULT/OFFLINE, ancestors tint, and the same source raises a System alarm. - Fit the wrong configured terminal: identity mismatch becomes
FAULTandMappingValidis false. - Digital inputs toggle; analog inputs retain quality, scaling, and unit.
- Every channel resolves to the owning module and approved I/O-list tag.
- If a project opts into output force, MANUAL/access/capability checks and audit logging pass; input and safety channels remain unreachable.
- Native and Web clients render the same published topology.
Honest boundary
Section titled “Honest boundary”The base adapter and Press composition compile, and the Press fixture has run on
the local runtime. Unplug/mismatch/DC-loss behavior and any explicitly enabled
force resolver remain deployment acceptance evidence for the selected master,
terminals, wiring, and pinned Tc2_EtherCAT version. No generic runtime scanner
can infer approved electrical tags, engineering scaling, or Fraktal module
ownership; those facts remain generated/imported project engineering data.
Built from Specification/Guides/FIELDBUS_ADS_ADAPTER.md at revision a1163c7 of the Fraktal repository.