fraktal-core — Framework Library (Fraktal Core §2.2)
The Fraktal Core base classes, contract types, FB_PermIntlk, the base TcUnit suite, and the test-first scaffold — the “lifecycle written once” of Core §2.2/§6.1. Part I (the platform-neutral normative standard) is Fraktal_Core_Part_I.md; this library is its reference implementation on the TwinCAT 3 binding (Part II, fraktal-tc3).
Core 0.25.0.0 puts retained data behind a project-chosen persistence medium
(I_PersistMedium: files in a folder, or a retentive pool): a root’s live station,
line and model configuration, its parameter sets and the local user table, restored at
start and rewritten after every accepted change (IMPLEMENTATION_NOTES §163; the Press
bench keeps them in C:\ProgramData\Fraktal\PressDemo\). Core 0.24.0.0 added
the user table outside the symbol table, controller/IPC health from the Beckhoff
Device Manager and the EtherCAT master’s own state, frame and CRC counters (§160-§162).
The Windows clock adapter observes the target’s existing time service and expires
missing quality; see the build and installation guide.
Modules 0.11.0.3 pins that Core dependency. The latest source audit is
Core and Press TC3 feature gaps.
Baseline (2026-08-02): Core
0.4.0.0/ Modules0.3.0.0build clean and their TcUnit gates are green. All three PLC projects returnedLastBuildInfo=0with an empty Error List and regenerated their TMC files, and both isolated-runtime gates pass — 92/92 tests across 28 suites (Core+Modules 84/26, internal Press bench 8/2), repeated on a Windows 10 x64 VM. Summaries, runner identities and artifact SHA-256 hashes are archived in../../../Specification/Evidence/.Separately, an earlier snapshot was deployed to a development runtime and exercised end-to-end over TF6100 (Press bench cycling; generic HMI commanding;
QUERY_CONFIGconfig manifest andOPC.UA.DApublication obscuring confirmed). That live result is framework-integration evidence on a development runtime — not a machine acceptance, safety or production claim, and not re-run against this snapshot. See../../../Specification/Reports/OBJECTIVES_AUDIT.md. Per Core §2 / TC3 §2.1 pin your exact XAE/XAR build; the plcproj files target 4024+ (ABSTRACT FBs/methods). The sources are kept source-compatible with TwinCAT 3.1.4024: no optional/defaulted method inputs (a 4026+ feature) — every method input is passed explicitly at every call site (seeIMPLEMENTATION_NOTES.md§62/§64/§69). File an issue for anything a pinned compiler rejects.
Layout
Section titled “Layout”Framework/ Fraktal_Core/ the Core library (save/install as a versioned library) Params/PL_Fraktal.TcGVL framework constants DUTs/ E_ExecState · E_Reason (§8.8 framework bands) · ST_Diagnostic · step/condition/decision records (§6.5, §6.9(b), §6.11) · part context (§3.16) · mode/module enums Interfaces/ I_Module · I_Unit · I_EquipmentModule · I_ControlModule · I_RecipeProvider (§3.8) · I_DeviceConnector (§3.15) · I_PartCarrier (§3.16) · I_VerdictProvider PermIntlk/FB_PermIntlk the §7.2 container (Define / SetBypass / ClearBypass / Diagnostic) BaseClasses/ FB_ControlModuleBase · FB_EquipmentModuleBase · FB_UnitBase (template method: a type overrides ONLY _M_Dispatch — §2.2; the Unit base adds modes/cascade, the step chain + stall walk, and the wired-in cycle profiler §6.2/§6.9/§8.11.4) Connectivity/ FB_DeviceConnectorBase (§3.15, T7 once) · FB_LocalRecipeProvider (§3.8) Platform/F_Now [TC3] synchronized-clock read (§2.7) Platform/F_TimingUpdate §8.11.4 timing aggregate math (pure, unit-tested) BaseClasses/FB_CycleProfiler §8.11.4 cycle waterfall + per-step stats + time-class split (WorkTime = real cycle time; fed by _M_SetStep) Fraktal_Modules/ reusable module library FraktalCore.tsproj XAE solution for the Core library alone FraktalModules.tsproj XAE solution for the module library alone TwinCAT Fraktal.tsproj XAE solution loading both libraries togetherExamples/ example applications, one solution folder each CoreDemo/Fraktal_Demo/ two-root smoke application (§3.1a; sources only, no .tsproj — add it to a solution to build) PressDemo/ internal Fraktal feature-testing bench PressDemo.tsproj the XAE solution (PressDemoX32 = 32-bit variant) Fraktal_Press_Demo/ simulated test-bench PLC project (not a real project) PressTests.plcproj the bench's integration gate (own solution) PressTests/ FB_PressDemoUnit_Tests · FB_FaultRecovery_Tests _Config/IO/ exported physical I/O configurationTests/ the aggregate Core + Modules gate, self-contained Fraktal_Tests.plcproj its manifest (every Compile path downward) FraktalTests.tsproj/.slnx its XAE solution (ADS port 851) Fraktal_Tests/ aggregate TcUnit test sources (§5.7) FB_ProbeCM / FB_ProbeEM minimal concrete probes for the bases FB_Base_Tests T1 · T2 · T4 (+ rollup/T6 at base level) proven ONCE FB_PermIntlk_Tests first-out ordering · bypass rules FB_Timing_Tests §8.11.4: exact math · classified cycle publication · command rows PRG_TcUnitRunner TcUnit.RUN() — driven headless by TcUnit-Runner (TC3 §5.7) tools/ source audits (e.g. Test-OpcUaPublication.ps1)tools/ this binding's gates and generators. They live here, beside the sources they check and mirroring `PLC/Allen-Bradley/tools/`, so a binding carries its own toolchain and neither can silently drift from it. plc_lint.py 18 source rules, both build profiles (§1.5/§5.5/§6.8) ld_rung_gen.py LD rungs by clone or declaration; ld_dump/sfc_dump read the generated body back as a graph (the gate) Invoke-TwinCatBuild.ps1 hidden-XAE CheckAllObjects on all five solutions Invoke-TwinCatLibraryInstall.ps1 save-as-library + install, in dependency order Invoke-TwinCatTcUnitGate.ps1 / tcunit_to_junit.py runtime gate + result validation test_*.py their own suites; they import flat, so run them with `python -m unittest discover -s <this dir> -t <this dir>` (cross-tree gates stay in the repository-root `tools/`)scaffold/FB_TemplateCM/ "new CM type in 30 minutes" — pre-wired, initially RED (§5.7)IMPLEMENTATION_NOTES.md every reconciliation vs. the drafts + proposed Core §3.2 amendmentsBring-up (first compile)
Section titled “Bring-up (first compile)”The authoritative interaction and evidence procedure is
../../../Specification/Guides/TWINCAT_XAE_WORKFLOW.md. It records the exact
Core→Modules save/install order, nested-build versus CheckAllObjects boundary,
hidden-XAE automation, isolated-runtime download/run sequence, and the 2026-08-01/02
execution history.
A
.plcprojis not opened directly like a solution — it is added into a TwinCAT XAE project. Verified on TwinCAT 3.1 4024.x (TcXaeShell): create/open a TwinCAT solution, then right-click the PLC node → Add Existing Item… → select the.plcproj. x32 vs x64 XAE does not matter for compiling; it only selects which local runtime (TwinCAT System Service) the shell pairs with. 4024.75 is fine — 4024+ is required (ABSTRACT FBs/methods).
- Open the dedicated 4026 wrapper
Framework/FraktalCore.slnx, or in TcXaeShell create a TwinCAT XAE Project and addFramework/Fraktal_Core/Fraktal_Core.plcprojbeneath itsPLCnode. The referenced Beckhoff libraries (Tc2_Standard,Tc2_System,Tc2_Utilities,Tc3_Module) resolve from the local repository automatically (they are placeholder references,*version). - Build warning-clean (Core §2), then Save as library and install; consumers pin the
version (§2.2/§5.4). If the compiler rejects a construct, check the watch-item list in
IMPLEMENTATION_NOTES.md§8 — these are known first-compile candidates, fix at source. - Close the Core wrapper, then open
Framework/FraktalModules.slnx, or addFramework/Fraktal_Modules/Fraktal_Modules.plcprojto another otherwise-empty XAE solution. It references the installedFraktal_Core; build it, then save/install it as a library. It deliberately has no task orMAIN. - Add either executable fixture:
Examples/CoreDemo/Fraktal_Demo/Fraktal_Demo.plcproj, orExamples/PressDemo/Fraktal_Press_Demo/Fraktal_Press_Demo.plcprojfor the pneumatic press. The ready-made 4026 system project isExamples/PressDemo/PressDemo.slnx(PressDemo.tsproj);PressDemoX32.slnis the legacy XAE-shell wrapper. Open one wrapper only—both point at the same Press PLC source project. For the VS2017-based x32 Shell, useFramework/FraktalCore.sln, thenFramework/FraktalModules.slnfor library preparation:.slnxis a modern IDE format. Save/install updated exports underFramework/Release/x32and reopen Press before compiling. The x32 IDE supports x86 and x64 PLC targets; select the PLC’s target architecture. See the workflow guide §4.0 for the matching 32-bit PowerShell automation. If a consumer reports unknown Core types or missing base classes insideFraktal_Modules, check the Modules library’s ownFraktal_Corereference. Adding Core directly to the application cannot repair an installed Modules library that omitted its dependency. Restore the reference, save/install the libraries in dependency order, then reopen the consumer to reload its graph. - Open the dedicated
Tests/FraktalTests.slnx, or create a separate XAE solution and addTests/Fraktal_Tests.plcproj; install TcUnit (tcunit.org) first. Then run the press gate too:Examples/PressDemo/PressTests.slnx. Never loadPressTestsbeside the Press Demo project: it links the exact Press source objects and duplicate GUIDs make TwinCAT rewrite those files. EachPlcTask.TcTTOcalls its runner. Run only on an isolated test runtime/ADS port and leave Autostart Boot Project disabled. Start it deliberately, harvest the result, and stop it; never make it the machine boot application. All suites green is the M1 acceptance bar. - Wire TcUnit-Runner into CI so the JUnit results gate the merge alongside lint (Core §6.8, §1.5).
Writing a sequence: ST, SFC or LD
Section titled “Writing a sequence: ST, SFC or LD”A chain is a chain: it extends FB_SequenceBase, records steps with M_Step, and
progresses through the shared result _retVal. Only who evaluates the
transition differs, and everything else follows from that one fact.
| ST | SFC | LD (integer state machine) | |
|---|---|---|---|
| Owns the transition | M_Advance |
the SFC runtime | the rungs |
| Body of the POU | CASE _step OF |
the chart | rungs gated on _step |
| Step body lives in | a CASE branch |
an ACTION | an ACTION |
Calls M_Advance? |
yes, ends every branch | no | yes, from the action |
| Transition condition | (inside M_Advance) |
_retVal = E_StepResult.ADVANCE |
(inside M_Advance) |
| A jump is | OnJump1 := <step> |
a branch whose condition is _retVal = E_StepResult.JUMP1 |
OnJump1 := <step> |
Clears _retVal |
M_Advance, on commit |
FB_UnitBase per scan |
M_Advance, on commit |
Overrides M_ChainRun? |
yes (that is the body) | no — its body is the chart | yes |
The per-scan clear is never a project’s job: a chain registers itself in
M_Attach and FB_UnitBase._M_BeginSequenceScan resets every attached chain
before _M_Dispatch runs (§1.1 O1). An SFC chart needs no wiring at all to be
safe against a stale ADVANCE.
Fraktal_Press_Demo ships the AUTO chain in ST (FB_PressDemoAuto) and SFC
(FB_SFC_PressDemoAuto) so the two can be compared side by side. The FB_SFC_
prefix is not a naming convention — it exists only so two renditions of one
chain can coexist in one project. A real project has one chain per mode and names
it FB_<Thing><Mode>.
Building an SFC chart
Section titled “Building an SFC chart”The chart graph is drawn in XAE. A .TcPOU SFC body is a serialized object graph
(SFCImplementationObject → SFCSegment → SFCElementList), and synthesising
one by hand is not worth attempting — a malformed archive is worse than none
because it still looks like a finished file. Draw the steps and transitions; the
rest is mechanical and can be scripted.
- Write the step bodies as ACTIONS.
MainActionresolves to an action of the POU, never a method. Each action is the ST branch minus itsM_Advancecall: an action only produces_retVal. - Name a step
N<StepNo>, and its actionA<StepNo>_<What>. The step carries the same number the step record publishes (M_Step(StepNo := 200)→ stepN200→ rowN200on the §3.13 chart →200:in the ST twin), so one step number reads identically in the chart, the code, the operator’s flow chart and a stall message. The action keeps theAprefix precisely so the two never blur: in the archive a step and itsMainActionare different objects, andN200bound toA200_RamDownsays which is which at a glance. A step’s “wait at the join” placeholder follows the same rule (N250→_aN250_active). - Every transition is
_retVal = E_StepResult.ADVANCE, except a jump branch, which is_retVal = E_StepResult.JUMP1(JUMP2/JUMP3for further branches). - Bind each step’s
MainAction. The attribute is{700a583f-b4d4-43e4-8c14-629c7cd3bec8}. - Use the inherited native Reset flag. In the chart SFC settings, disable
defaults and enable
ResetwithUse=true,Declare=false.FB_SequenceBaseownsSFCReset:M_Restart/M_ChainResetrequest the graph reset, and the initial action’s mandatoryM_Stepconsumes it. Do not redeclare the flag or add a project reset call. Resetting only_stepcannot restart a native graph.
Read the archive’s own descriptor table; never guess an attribute. Each step carries ten attributes and five of them are empty strings. The archive maps every GUID to an identifier and a description, so the binding target is a lookup, not an inference:
| Attribute | GUID |
|---|---|
Name |
{38391c6d-6d4a-42f8-8ee7-9f45e5adafa8} |
Comment |
{7d894980-aeea-405c-a0f6-e2b26429c58f} |
Exclude |
{01580b27-6378-448b-8ecb-0e4b795b58d6} |
InitStep |
{6844a48e-46c2-4cc8-a185-a478f3b99cc0} |
Duplication |
{62e1754b-7629-4e63-9cec-10ae0c536f1f} |
MinTime |
{cacf1a68-236e-47c2-b7b1-1cf9199718cb} |
MaxTime |
{b693554c-1b01-4a8d-afde-9e3a46f7465d} |
MainAction |
{700a583f-b4d4-43e4-8c14-629c7cd3bec8} |
EntryAction |
{a6b08bd8-b696-47e3-9cbf-7408b61c9ff8} |
ExitAction |
{a2621e18-7de3-4ea6-ae6d-89e9e0b7befd} |
MainAction, not EntryAction. Step bodies poll child Done flags and
timers, so they must run every scan the step is active. An entry action runs
once on activation, and a chain wired that way stalls at its first step forever —
which reads as a hung machine, not a wiring mistake.
Parallel branches (§6.12)
Section titled “Parallel branches (§6.12)”Two work positions that run at the same time and independently. There are two forms; prefer the first unless the chart itself is the clearest documentation.
Sub-chain fork — every language, including ST. Each leg is an ordinary chain, so it brings its own step pointer, transition result and step-scoped latches, and nothing about it has to know it runs beside another. One step forks and joins:
500: M_Step(StepNo := 500, StepName := 'project.step.bothPositions', Awaits := 0, AwaitingLabel := '', TimeClass := E_TimeClass.WORK, ExpectedTime := T#0S); M_RunPar(Chain := _positionA, BaseStepNo := 600, Branch := 1); M_RunPar(Chain := _positionB, BaseStepNo := 700, Branch := 2); _retVal := M_ParJoin(); M_Advance(OnAdvance := 999);M_ParJoin commits only when every leg run that scan reports Done. The leg list
is the calls themselves — nothing to register, nothing to forget when a leg is
added. Worked example: FB_ProbeParChain / FB_ProbeLeg / FB_SequencePar_Tests.
Native divergence — drawn in the chart. In XAE, select the transition after the forking step and insert a parallel branch. In the archive the two shapes are told apart by what each leg starts with:
| leg starts with | meaning | |
|---|---|---|
SFCBranch whose legs open with SFCTransition |
a transition | alternative (one leg runs) |
SFCBranch whose legs open with SFCStep |
a step | parallel (all legs run) |
Rules for a natively drawn leg:
- Every leg step names its leg on its own step record:
Branch := 1as the last argument ofM_Step. That is what keeps this leg’s issue latch, delay and message separate from the main line’s, so both can command their own children in the same scan. Main-line steps omit it — it defaults to this chain’s own leg, so a leg written as a sub-chain never mentions a branch either. (Under the legacyFRAKTAL_TC3_4024profile there are no defaulted method inputs, so a 4024 build writesBranch := 0at everyM_Step, as it already does forM_Advance.) - A leg’s transitions read
_conRetVal[n], not_retVal. The main line keeps_retVal. Both are cleared once per scan by the base. - Every leg needs a terminal step to wait in. A parallel branch joins only when
all legs have reached their last step, so the main line needs one too — that is
what
A250/A310are inFB_SFC_PressDemoAuto. - The join transition reads every result, e.g.
_retVal = E_StepResult.ADVANCE AND _conRetVal[1] = E_StepResult.ADVANCE. - Number every leg; none is “the main line”. A two-leg fork uses legs 1 and 2.
Leaving one on branch 0 makes the chart draw it unindented, as if the other leg
were subordinate, and leaves
_retValmeaning one thing inside the fork and another outside it._retValis the line before and after; between them there are only legs. - A composite step inherits its leg.
M_RunSubtakes no branch argument — the sub-chain runs on whatever leg the calling step is on, becauseM_Stepalready set that. Press AUTOA240runs the load-position chain from leg 1 and its four steps publish as leg 1. - The fork sits on a chain’s main line. Nest by making a leg a sub-chain instead — that form nests without limit.
Writing a Ladder sequence rung by rung
Section titled “Writing a Ladder sequence rung by rung”A ladder chain is an integer state machine: one rung per state, dispatched on the
inherited _step, and the rung writes the next state itself. FB_LD_PressDemoAuto is
the worked example; it extends FB_SequenceBase, the same base an ST or SFC
chain uses.
Use EN/ENO, not a Run facade. A ladder box only executes on power flow, and
XAE already supplies that for any method box: enable EN and the box gains an
EN input and an ENO output. The base method is called directly —
BOX "M_Step" params=['EN', 'StepNo', …] returns=['ENO'] EN=trueBOX "M_StepLd" params=['Run','StepNo', …] returns=[] EN=false— so M_Step, M_Await, M_RunSub and every method on every developer-written FB
are callable from a rung with no library change at all. This is the only approach that
scales: a project may define or extend module types freely, and adding a hand-written
…Ld twin per method per type does not.
FB_SequenceBaseLdhas been deleted. Its 27Run : BOOLfacades were reinventingEN. They existed because adding an input to an override isC0094: Interface of overridden method doesn't match declaration, which forced the distinctLdnames — butEN/ENOadds no parameter, so the signature never changes, so no facade and no renaming was ever needed. A ladder chain now extendsFB_SequenceBase, exactly like an ST or SFC chain;FB_LD_PressDemoAutois the worked example.convert_ld_boxes()intools/ld_rung_gen.pyperformed the migration and is kept for any chain still carrying the old form.Removing a type from a released library is a breaking change. Core’s version was not stepped for it because no shipped chain outside this repo consumed the facade; a downstream project that did must migrate with
convert_ld_boxes()before resolving Core again.
Two consequences worth knowing before editing an EN-gated box:
- A value-returning box has TWO outputs:
ENOfirst, then the return value.M_Awaitreportsreturns=['ENO','M_Await']. Wiring the result into slot 0 puts it onENOand leaves the real output dangling; wiring the wrong variable into slot 1 compiles clean and silently strands the intended one. That is a defect no gate catches — see the_partReady/_airReadytrap below. EN := FALSEmeans the box is not executed at all, so its output variable keeps its previous value. ARun := FALSEfacade call still ran and wrote its fail-closed default. Inside a rung gated onEQ(_step, N)the two are equivalent, because the variable is only read by that same rung — but a value read outside the rung differs.
The two rung shapes. Everything in a chain is one of these.
Pure logic (initialise, wait on conditions, complete):
[EQ(_step, 100)]──┬──[M_StepLd StepNo:=100, StepName:='…', Awaits:=0, │ AwaitingLabel:='', TimeClass:=…, ExpectedTime:=…, Branch:=0] ├──[_partReady := M_AwaitLd(Idx:=1, │ Label:='project.condition.partPresent', │ Ok:=sensor.OutImm.Value AND sensor.OutImm.Quality)] ├──[_airReady := M_AwaitLd(Idx:=2, Label:='…', Ok:=…)] ├──[_twoHandReady := M_AwaitLd(Idx:=3, Label:='…', Ok:=…)] ├──[_startReady := NOT requireTwoHand OR _twoHandReady] └──[_partReady AND _airReady AND _startReady]──[MOVE 110 → _step]Commanding a child (most steps — this is the N110 shape):
[EQ(_step, 110)]──┬──[M_StepLd StepNo:=110, …, Awaits:=_pressRam, │ AwaitingLabel:='PressRam.RETRACT'] ├──[M_TryIssueLd Steppable:=TRUE]──┬──[_pressRam.Command := E_CylinderCommand.RETRACT] │ ├──[_pressRam.Abort := FALSE] │ └──[_pressRam.Execute := TRUE] └──[_pressRam.Done]────────────────┬──[_pressRam.Execute := FALSE] └──[MOVE 130 → _step]A jump is not a special construct: it is a second MOVE under a different contact
in the same rung (_pressRam.Error → MOVE 210 → _step beside Done → MOVE 220).
A terminal step calls M_Complete()/sets Done and does not MOVE.
Never nest a value-returning facade box. Assign each M_AwaitLd,
M_PartReceivedLd, decision, or other value-returning call to a declared variable of
the exact return type, then combine those variables in a separate logic box. Run is
the box’s rung-power/execute input; it is not an accumulator for the previous call’s
Boolean result. Every active named wait must execute independently on every scan so
the complete diagnostic set remains published.
Why this is a hard rule: XAE lowers a nested graphical output to a temporary named
ImpVar<BoxId>_<output ordinal>. In the broken N100 archive,
ImpVar597_1 is the return of M_AwaitLd box ID 597 feeding OR box 612, and
ImpVar616_1 is the return of M_AwaitLd box ID 616 feeding the Run pin of outer
M_AwaitLd box 614. TwinCAT could not type those nested method temporaries. The
names were editor-generated, but they were not opaque: their box IDs locate the
offending nodes in <NWL><XmlArchive>. Flattening the calls also restores the ST/SFC
semantics—three independent result assignments followed by one combined transition.
Rules that differ from ST.
M_TryIssueLdis what re-arms per step — the issue latch is cleared byM_Stepon a step-number change (a chart language never reachesM_ClearTransition).- No
M_Advance, no_retVal. The rung writes_stepdirectly; that is the idiomatic ladder transition and rule S1 accepts it (it requires a step record plus some way to move, not a nominated one). - Drop the child’s
Executein the same rung that leaves the step — §6.1’s Execute-drop reset is what returns the child to READY.
Do not synthesise the body from nothing. A <NWL> network is a serialized object
graph of BoxTreeBox/BoxTreeOperand/BoxTreeDemux/BoxTreeAssign nodes with Id
identities and VarId power-rail nodes — roughly 40 kB per rung. Hand-writing one is
not viable and cutting nodes with a regex has produced a file that stayed plausible
while ceasing to be well-formed XML. What is viable is cloning a rung that already
compiles — see the next section. After any edit, verify with CheckAllObjects (see
Specification/Guides/TWINCAT_XAE_WORKFLOW.md) — the press demo resolves only once Core and
Modules are installed as libraries.
Generating a rung by cloning a worked example
Section titled “Generating a rung by cloning a worked example”tools/ld_rung_gen.py generates rungs; tools/test_ld_rung_gen.py is its gate. The
method is deliberately narrow, and the narrowness is what makes it safe:
- Split, never parse. The archive carries
xml:space="preserve", so an ElementTree round-trip rewrites indentation that is real content.split_networksscans<o>depth and returns the raw blocks plus the separator between them — rejoining without it yields</o><o>on one line, which is still valid XML and therefore fails silently. - Clone a rung of the shape you want and renumber every
Id/VarIdinto a fresh range above the file’s maximum. A duplicatedIddoes not fail to parse; it silently shadows a node. - Rewrite only leaf operands.
subst()matches theOperand+Typepair, so a short name cannot match inside a longer one and the type can never drift away from the value — that mismatch is exactlyCannot convert type 'BOOL' to type 'E_VERDICT'.subst_string()additionally derivesSTRING(INT#n)from the new literal, so a renamed step cannot keep the previous name’s declared length. - Every substitution asserts its hit count. A rewrite that matches nothing reports
success and changes nothing;
subst()raises instead._pressRam.Executeoccurs twice in a command rung (Set coil and Reset coil) — assertingcount=1there is a bug the assertion catches. - Fix
BranchCounter. It is the archive’s monotonicVarIdallocator; leaving it below aVarIdthat now exists lets XAE hand out a duplicate the next time someone opens the chart. - Compile after every rung.
ImpVar<BoxId>_<n>in an error message maps directly to that node’s<v n="Id">…L</v>, which locates the fault in seconds — but only if you know which rung you just added.
Worked example — the whole of N130 is N110 with nine operand substitutions:
rung, next_id, next_var = clone(template_N110, id_base=…, var_base=…)rung.subst("130", "150", count=1) # MOVE target FIRST: doing the gate firstrung.subst("110", "130", count=1) # would collide with the template's MOVErung.subst_string("project.step.pressRamUp", "project.step.pressDoorOpen")rung.subst_string("PressRam.RETRACT", "Door.RETRACT")rung.subst("_pressRam", "_door", count=1) # the Awaits operandrung.subst("_pressRam.Command", "_door.Command", count=1)rung.subst("_pressRam.Abort", "_door.Abort", count=1)rung.subst("_pressRam.Execute", "_door.Execute", count=2)rung.subst("_pressRam.Done", "_door.Done", count=1)Cloning had one hard limit — it can only produce box types that already exist
somewhere in the file — so every rung needing M_Delay, M_AskDecision, M_RunSub,
M_RaiseWarning, M_ReportFromChild or a child method such as WithdrawOutputs used
to stall on “draw one in XAE first”. That limit is gone; see the next section. Cloning
is still the shorter route when a rung of the shape you want already exists.
Declaring a rung instead of cloning one
Section titled “Declaring a rung instead of cloning one”A BoxTreeBox is fully determined by the declaration of the method it calls, so
nothing about it has to be copied from anywhere:
| Archive field | Comes from |
|---|---|
InputParam.Names |
EN, then the VAR_INPUT names in declaration order |
InputParam.Types |
BOOL, then their types |
OutputParam |
ENO : BOOL, then — only if the method returns a value — the method’s own name and return type |
OutputItems |
<n /> when void; otherwise an empty ENO slot then the return slot |
CallType / EN / ENO |
Method / true / true |
A method on another FB folds the instance into the box type
(method("_pressRam.WithdrawOutputs", …)). The operator boxes, the power rails and the
coils are equally mechanical, so tools/ld_rung_gen.py provides a small node algebra
and a whole rung is written down:
alloc = Allocator.above(source) # Ids above everything in the filerail = Rail(alloc.take_var())items = [ Wire(rail.var_id, compare("EQ", Term(), Value("_step", "INT"), Value("215", "INT"))), method("M_Step", rail, [("StepNo", "INT", Value("215", "INT")), …]), method("M_PartProcessed", rail, [("Verdict", "E_Verdict", Value("E_Verdict.NOK", "E_VERDICT")), …], returns=("M_PartProcessed", "BOOL"), result="_partProcessed"), Coil("_partDispositioned", rail, SET), # (S) Coil("_partInMachine", rail, RESET), # (R) move(rail, Value("240", "INT"), "_step", "INT"),]text = network(items, alloc, comment="N215")Term()is the left power rail;Wire/Railare a branch point and its taps, and a rung can only branch through them — power flow in the nestedENform is the nesting.ContactandValueare deliberately different types. Both serialize asBoxTreeOperand, but XAE marks a contactBoolean/Fixedand a plain BOOL argument (Steppable := TRUE) not, so the type alone cannot tell them apart — and in ladder they are not the same thing.Contact(x, negated=True)is--|/|--.Coil(x, rail, RESET)is whatx := FALSEmeans inside an active step. A plain coil driven from the step’s own rail would write TRUE.result=on a value-returningmethod()is what makes the ENO trap unrepresentable: the return can only land in slot 1.
The gate for all of it is tools/test_ld_rung_gen.py, which regenerates N999 —
a rung drawn by hand in the XAE editor — from a declaration and compares it against the
real one node for node, pin for pin and flag for flag. If the emitter can reproduce
what the editor wrote, a rung it emits for a box with no instance to clone is
trustworthy for the same reason.
Dump the result. A clean compile does not prove a generated node exists.
python tools/ld_dump.py <file.TcPOU> # every network, as a graphpython tools/sfc_dump.py <file.TcPOU> # the same for a chartThis is not a convenience, it is the verification step. Two failures it catches that nothing else does:
- an untyped
<o>— a node lifted out of a<l2 … cet="BoxTreeBox">list loses the type the list gave it collectively. It parses, it compiles, and the box is simply not there. (network()writesNetworkItemswith nocetso every item states its own type.) - a dead gate.
N215andN230both compiled while readingEQ(215, 0)andEQ(230, 0)— the step number compared against a leftover constant instead of against_step. Legal IEC, constantly FALSE, no warning from anything.
Rung order is execution order, and it matters. A forward transition re-enters any
rung below it in the same scan, because the MOVE writes _step before those rungs
are evaluated. That is normally harmless — the chain simply advances a scan earlier
than the ST twin would — but not when the two rungs command the same child: §6.1’s
Execute-drop reset needs one scan with Execute low, and a Reset coil followed by a Set
coil in the same scan never gives it one. The press AUTO chain has two such pairs,
and in each the later rung is placed deliberately above the earlier one: the
abort at N180 and the reopen at N185 both drive the door, so N185 sits above
N180; and N200 extends the ram while N240’s load-position sub-chain retracts
it, so N240 sits above N200. The second pair was missed until 2026-09-27: with
a zero dwell, N200..N240 ran in one scan, the retract’s Set coil landed in the
same scan as the extend’s Reset, the ram kept reporting the extend’s Done, and
the cycle finished with the ram still down. Everything else is in step order.
Reading and generating an SFC chart
Section titled “Reading and generating an SFC chart”An <SFC> body is a different archive from <NWL>, and simpler. The skeleton is
SFCImplementationObject└── o n="Root" t="SFCSegment" └── o n="ElementList" t="SFCElementList" └── l2 n="InnerList" ← the chart, in order ├── o t="SFCStep" ← EmbeddedMain/Entry/ExitAction, nested │ ElementList, and l2 n="Attributes" ├── o t="SFCTransition" ├── o t="SFCJump" └── o t="SFCBranch" ← l2 of SFCSegment legsEverything meaningful is a GUID-keyed attribute, and the archive ships its own
descriptor table — <d2 n="Attributes" ckt="Guid" cvt="SFCAttributeDescription"> maps
each GUID to an Identifier. Read it from the file rather than trusting this list;
these are the 14 it currently defines:
| Identifier | GUID | Notes |
|---|---|---|
Name |
38391c6d-6d4a-42f8-8ee7-9f45e5adafa8 |
step name (N200); on a transition this holds the CONDITION expression |
MainAction |
700a583f-b4d4-43e4-8c14-629c7cd3bec8 |
action run while the step is active |
EntryAction |
a6b08bd8-b696-47e3-9cbf-7408b61c9ff8 |
runs once on activation |
ExitAction |
a2621e18-7de3-4ea6-ae6d-89e9e0b7befd |
runs once on deactivation |
InitStep |
6844a48e-46c2-4cc8-a185-a478f3b99cc0 |
exactly one step per chart |
Parallel |
23bdaa98-72ec-41f7-817b-9dede5697086 |
on a branch: parallel vs alternative |
Qualifier |
e174fc0d-80b0-4a9e-a530-ca239c249a50 |
action association qualifier |
MinTime / MaxTime |
cacf1a68-… / b693554c-… |
step active-time bounds |
Monitoring |
8294df19-5962-4dee-a874-1051dabb0e3e |
transition monitoring |
Comment |
7d894980-aeea-405c-a0f6-e2b26429c58f |
|
Duplication |
62e1754b-7629-4e63-9cec-10ae0c536f1f |
copy implementation vs reference |
Symbol |
bc882c11-1e91-4dd8-a6b8-2075724ed18b |
EnumValue, not a string |
Exclude |
01580b27-6378-448b-8ecb-0e4b795b58d6 |
hidden; excludes from build |
A real step carries ten of these — Name, Comment, Exclude, InitStep,
Duplication, MinTime, MaxTime, MainAction, EntryAction, ExitAction — and
four are normally empty strings. A transition carries only Name, Comment, Exclude.
Values are typed wrappers: StringValue, BoolValue, or EnumValue (which carries a
TemplateGuid before its Value, so a regex written for the string form silently
skips it).
Two traps that cost real time:
MainActionvsEntryAction. Putting the body onEntryActionruns it once and the chart stalls at its first step forever.MainActionis the one you want.- The action is a separate POU object.
<Action Name="A200_RamDown">is a sibling of<Method>under<POU>; the step attribute only holds its name as a string, so a renamed action and a step still naming the old one both parse and neither warns.
Fraktal’s naming makes the step number the same token everywhere: step N<StepNo>,
action A<StepNo>_<What> (N200 → A200_RamDown), matching the ST twin’s CASE
label and the §3.13 row. The differing prefix is what keeps a step distinguishable from
its action object inside the archive.
Because steps and transitions are flat attribute records rather than a wired graph,
an SFC chart is materially easier to clone than a ladder rung — retargeting a step
is two StringValue edits (Name, MainAction) with no Id/VarId renumbering and
no power rails. The same discipline still applies: assert every substitution’s hit
count, keep Id/IdParent consistent, and compile after each step.
Reading an archive is far easier than writing one: dump a body’s structure before
touching it (python tools/sfc_dump.py <file>, python tools/ld_dump.py <file>). Note
that the descriptor <d2> is a dictionary — alternating <v> key and <o> value
children, and the values are typed collectively by cvt, so none of them carries a
t=. A dumper that filtered on t="SFCAttributeDescription" printed an empty table and
an empty chart, and looked like a file with nothing in it. The <NWL> node grammar
ld_dump prints is
DEMUX var=N (DEF) ← defines a power node; its <o n="Input"> is what drives itDEMUX var=N (ref) ← every later use of that same railOPERAND "x" : "T" ← Flags 1 = negated contact, 0 = plainASSIGN -> "x"{flags=N} ← 2 = Set coil (S), 3 = Reset coil (R), 0 = plainBOX "M_Step" params=[EN, StepNo, …] ← InputItems positionally match paramsTraps that cost real time here
Section titled “Traps that cost real time here”-
A
.TcPOUedit must target one CDATA section. A method’s declaration and implementation are separate CDATA blocks. A replacement written against the two concatenated matches nothing and reports success — a silent no-op. This bitM_Resettwice. -
_retValis a one-scan signal. In a chart the runtime evaluates the transition after the step action, so the value must survive the scan and be gone before the next one. The framework does this; do not add a manual clear. -
A chart POU must not override
M_ChainRun. Its body is the chart. Only a chain used as a composite sub-step (M_RunSub) overrides it, and such a sub-chain must therefore be ST. -
FUNCTION_BLOCK INTERNAL FB_X EXTENDS FB_Yis legal; any combination ofABSTRACT/FINAL/INTERNAL/PUBLIC/PRIVATE/PROTECTEDmay precede the name. -
IEC standard function names are reserved as identifiers —
SUB,ADD,DIV,LEN,SELand the rest. A method input namedSubparses as the subtraction operator and yields ~40 cascading errors on innocent lines. Rule C2 now rejects them; a qualified enum member (E_CylinderPosition.MID) is still fine. -
M_TryIssueused to fire once per chart RUN in SFC/LD. A chart language never callsM_ClearTransition— its engine owns the transition, so there is no commit point to hang it on — and nothing else re-armed the issue latch. The re-arm now lives inM_Step, the one call every step of every language makes. If you are reading an older chart that only ever commanded its first child, this was why. -
A parallel leg is not a place to fault quietly.
CurrentStep, the §6.9 stall walk and the profiler follow the main line only: a first-out has to name one step. A leg is timed and guarded on its own §3.13 row instead, and a leg that must fault does it through §6.9(d), which stops the whole chain — one leg failing is a failure of the step. -
Owning a child’s failure is not the same as hiding it. A step that drops
Awaitsto disposition the failure itself (below) is one case; a step whose command sits behind anIF/CASEis the other, and that one has no rollup at all. Raise it explicitly (Core §6.9(d)):IF M_RaiseFromChild(Source := _gauge) THEN_gauge.Execute := FALSE; // §6.1 drop-reset frees the child to recoverRETURN;END_IFM_RaiseCustomdoes the same for a condition no module reports — an application rule, an out-of-band measurement — with the step choosing the text, severity, category and drill-down link. Both stop the chain on the step, mark that row of the §3.13 flow chart, and re-arm the step’s latches when the error clears, so the command is re-issued and re-tested rather than resumed mid-handshake. Both are one call in ST, an action line in SFC, and a power-flow-gated box in LD. Worked example:FB_ProbeRaiseChain. -
Do not fault a condition the step already handles.
M_RaiseWarning(a rule the step states) andM_ReportFromChild(a child’s first-out, published but not adopted) record the occurrence and leave the chain running — press AUTON180andN200. They are AUTO_RESET come+gone events, so they can never block the nextStart, and the base emits each once per step visit so an unguarded call in a step body is correct. Reach for the raising pair only when the machine must stop. -
Owning a child’s failure means not awaiting it. An awaited child fault is adopted by
FB_UnitBase.OnCyclic—_exec := ERROR,_step := 0— before_M_Dispatchruns, so a chart can never jump on it. A step that wants to disposition the failure itself passesAwaits := 0and names the wait withM_Awaitinstead (N200in the press AUTO chain does exactly this).
Rule S1 knows the difference: for an <SFC>/<LD>/<FBD> body it requires
the chart contract (_retVal, M_Step() rather than the ST skeleton, so a
correct chart is not forced to pretend it is ST.
Building an LD chain (integer-based state machine)
Section titled “Building an LD chain (integer-based state machine)”This section used to describe a second, incompatible ladder form: a
FB_SequenceBaseLd base whose methods took Run : BOOL, and rungs that ended in
M_Advance with an OnJump1..3 mapping. Neither is how the ladder works. The
facade has been deleted (EN/ENO replaces it) and a rung has always written _step
directly. The authoritative description is § “Writing a Ladder sequence rung by rung”
above; this heading is kept only so an old link still lands somewhere truthful.
Rule S1 knows the difference between the three faces: an <SFC> chart must not
need M_Advance, a <NWL>/<LADDER> chain must carry some way to move (writing
_step counts), and an ST chain needs the full CASE _step OF skeleton.
Two TcUnit gates, and why they are separate
Section titled “Two TcUnit gates, and why they are separate”There are two test projects and you must run both:
| Gate | Covers | Solution |
|---|---|---|
Tests/Fraktal_Tests.plcproj |
Core + Modules (30 suites / 98 tests, simulated HAL) | Tests/FraktalTests.slnx |
Examples/PressDemo/PressTests.plcproj |
Internal Press feature bench (2 suites / 8 integration tests: FB_PressDemoUnit_Tests, FB_FaultRecovery_Tests) |
Examples/PressDemo/PressTests.slnx |
Accept a runtime result only when both its count and runner identity match the
selected gate: Core/Modules output is rooted at PRG_TcUnitRunner and reports
98 tests/30 suites; Press output is rooted at PRG_PressTestRunner and reports
8 tests/2 suites. If a Press attempt reports the Core identity, either the wrong
solution was downloaded or a previously created Core boot project restarted on
that target. Source BootProjectAutostart="false" prevents creating a new
autostart configuration; it does not erase boot data that already exists on a
runtime.
They are split because of a hard TwinCAT constraint: PLC Control inspects a raw
Compile Include path before it evaluates <Link> metadata, so a path
containing .. makes the importer try to create a project-tree folder literally
named .. and stop with “‘..’ is not a valid folder name.” Every Compile path
must run downward from its manifest.
A single aggregate would therefore have to sit at TwinCAT/ to reach both
Tests/ and Examples/ — cluttering the root that holds the platform’s
projects. Keeping each manifest beside the sources it owns is what lets Tests/
stay self-contained. The press suites still link the same physical objects
that deploy (Fraktal_Press_Demo/01_PneumaticPress/...), never copies.
Two rules keep this working, both enforced by plc_lint.py P1:
- no
..in any Compile path, and every include must resolve; - a
<Folder Include>list mirrors the Include directories, never the<Link>paths — XAE materialises those entries as real directories on disk, so a mismatch litters the tree with phantom empty folders.
Never load PressTests in the same solution as Fraktal_Press_Demo: both link
the same source objects and duplicate in-solution GUIDs make PLC Control rewrite
the shared files.
For a compiler-only local/CI check that does not activate or download a target,
run tools/Invoke-TwinCatBuild.ps1 (paths below are relative to this
directory) from the repository root. It opens each test
solution in a separate hidden XAE host, selects x64, asserts Autostart Boot Project
is false, and runs the nested IEC project’s CheckAllObjects. Runtime CI supplies
the separate isolated-target hook and validates its raw TcUnit summaries with
tools/tcunit_to_junit.py, including expected runner identity as well as counts.
Build order matters: save/install Fraktal_Core, then save/install Fraktal_Modules.
Fraktal_Demo, Fraktal_Press_Demo, PressTests, and Fraktal_Tests are executable applications, not libraries;
Tests additionally needs Fraktal_Modules and TcUnit installed.
Each manifest sits with the sources it owns, so every compile input is a downward
path. Keep it that way: do not reintroduce escaping .. compile paths, and do not
merge the two gates back into one manifest — that would force it up to TwinCAT/.
If a test runtime is accidentally saved as a boot project and reports a PLC
stack overflow during TwinCAT startup, keep outputs safe, return TwinCAT to
Config mode, remove/disable the Fraktal_Tests boot project for that ADS port,
and restart. The following PREOP→OP / ADS 1804 messages are consequences of the
crashed PLC runtime, not separate I/O mapping faults.
Commissioning gates (first power-up of a real machine)
Section titled “Commissioning gates (first power-up of a real machine)”Two gates in the VAR CONSTANT block of Examples/Fraktal_Press_Demo/00_System/MAIN.TcPOU deliberately hold
physical outputs off until the corresponding check is done. Until then the machine looks broken while
the software is healthy:
CONTROL_CIRCUIT_MAPPING_CONFIRMED(defaultFALSE) —FB_PressIoDriver.M_WriteOutputsforces_000K951_A1(SwitchControlOn) and_000K911_A1(EnableControlOn) FALSE every cycle. Control On cannot energize, so the hardwired N54 D2 relay chain never closes and K985/K986 never enable the valves — nothing moves at all, even though the cylinder coils are written unconditionally. Set it only after verifying the K951/K911 electrical semantics on the cabinet. Per the N54 D2 signal table these are distinct signals (momentary button coil vs. bus/air-OK enable), yet both currently receivePowerHal.EnableRequestOut; confirm that is correct for your wiring before enabling.USE_SIMULATION(defaultFALSE) — when TRUE,MAINcallsIoDriver.M_ClearOutputs()every cycle so no physical output is ever energized during virtual commissioning.
Demo-rig deviation: the E-stop mirror is NOT fail-safe
Section titled “Demo-rig deviation: the E-stop mirror is NOT fail-safe”_000K910A (=000+S1-K910A:14, “Emergency Switch 1 Pressed”) is wired normally open on the demo
rig — confirmed on hardware — so FB_PressIoDriver inverts it to produce the healthy mirror. A
normally-open E-stop contact cannot distinguish “not pressed” from a broken wire, a pulled terminal or a
dead input card: all read FALSE, and the mirror would report healthy. ISO 13850 / EN 60204-1 require
a normally-closed contact so any break forces the stop.
This is tolerable only because the mirror is diagnostic and the hardwired N54 D2 relay chain remains the safety authority (Core §9). A production machine must rewire to NC and delete the inversion.
These are constants, so they cannot be written online. Changing one is a source edit in MAIN plus
a download — deliberate and reviewable, rather than a live write from an HMI, XAE watch window or ADS
client. The trade-off is intentional: switching to virtual commissioning now costs a download.
MAIN still publishes read-only mirrors (UseSimulation, ControlCircuitMappingConfirmed) so the gate
state remains visible to diagnostics; they are reassigned from the constants every cycle and no logic
reads them, so writing a mirror online changes nothing.
Read both off a running PLC before suspecting the control logic:
cd FraktalCore/HMI/gatewaydart run tool/probe_sim_flag.dart <amsNetId> [port]If forcing the output in TwinCAT XAE works but the PLC never drives it, it is one of these gates — the terminal, wiring and process image are already proven good by that test.
Writing your first type (Quick-start, Core §1.1)
Section titled “Writing your first type (Quick-start, Core §1.1)”- Copy
scaffold/FB_TemplateCM/, renameTemplate→ your type, reserve a reason band (Core §8.8) and record it in the registry. - Declare your
E_<Type>Command,ST_<Type>Hal,ST_<Type>ParCfg(keepSchemaVersion— §3.8). - Write
_M_Dispatchonly (~15 lines): drive output → await sensor →_M_Complete()/_M_Fault(<band code>, …). Interlocks viaFB_PermIntlk; the lifecycle is inherited. - Turn the RED suite GREEN: fill the T2/T3/T5 expected values and run against the sim HAL (§2.6) — no rig. T1/T4 are already proven by
FB_Base_Testsfor every inheriting type. - Wire once in the parent’s
Setup(§3.11); the tile renders itself (§3.13).
Conformance mapping (Core §5.7)
Section titled “Conformance mapping (Core §5.7)”| Row | Where proven |
|---|---|
| T1 handshake + Execute-drop reset | FB_Base_Tests (once, for every inheriting type) |
| T2 first-out reason and SourcePath | base mechanism in FB_Base_Tests; each type re-proves with its reasons (scaffold) |
| T3 interlock withholds output | per type (scaffold, RED) |
| T4 abort, no self-resume | FB_Base_Tests (once) |
| T5 recipe migrate-or-fault | per type (scaffold, RED) |
| T6 rollup adopts child verbatim | base mechanism in FB_Base_Tests (FB_ProbeEM); composites re-prove per Annex H §H.5 |
| T7 link supervision | FB_Connector_Tests (once, in the connector base) |
| T8/T9 tier rows | per composite/Unit type (worked: FB_ClampEM_Tests rollup, FB_Unit_Tests) |
Fraktal_Modules/ ships reusable module types (including Annex A/B’s FB_CylinderCM and FB_ClampEM) with their §8.8 band constants, simulation models, and configured device presets; their suites run in the same gate.
Built from FraktalCore/PLC/TwinCAT/README.md at revision a1163c7 of the Fraktal repository.