TwinCAT XAE compile, library, and TcUnit workflow

Status: binding procedure and historical execution record for Fraktal/TC3. The normative architecture remains in Part I and the binding requirements remain in Part II. This document is the operational source of truth for the XAE interactions used to compile the reference implementation, install its two local development libraries, and execute its two isolated test applications.

Four different operations were used. They are not interchangeable:

Operation What it proves What it does not prove
Nested IEC project Build/Rebuild in XAE The selected PLC application compiles for the selected platform; updates compile information and, when enabled, the TMC Target configuration validity, runtime behavior
Check all objects on the nested IEC project Every POU/DUT/GVL in that PLC project is compilable, including unused library objects A full TwinCAT system build, target activation, download, or test execution
Save as library and install Saves the compiled PLC library and registers it in the local TwinCAT Library Repository A released/distributed package or proof that consumers were rebuilt against it
Activate → Login/Download → Start on the isolated runtime The selected compiled test application executes on that runtime Production-machine, hardware, safety, or site acceptance

Beckhoff documents these boundaries in Check all objects, Save as library and install, and loading, logging in, and starting the PLC.

The maintained repository automation, FraktalCore/PLC/TwinCAT/tools/Invoke-TwinCatBuild.ps1, performs the second operation only. It deliberately does not activate a target, download, start a PLC, or install a library. Do not call its green result a full system build or runtime test.

The recorded 2026-08-01/02 baseline used:

  • TwinCAT XAE/XAR 3.1.4026; the checked-in wrappers currently identify 3.1.4026.24.
  • Visual Studio/TwinCAT DTE automation through VisualStudio.DTE.18.0 for the maintained hidden object-check gate.
  • Debug|TwinCAT OS (ARMV7-A) for the initial Core, Modules, and internal Press bench nested builds associated with the saved target.
  • Debug|TwinCAT OS (x64) for the subsequent library/test reconciliation and the isolated Windows 10 x64 test runtime.
  • TcUnit installed in the local Library Repository.
  • An isolated Windows 10 x64 runtime identified by the operator as 192.168.1.11, using PLC ADS port 851. The event log records the initiating engineering AMS Net ID as 192.168.1.6.1.1; that is not the target identity.

Platform is an input to the evidence. Reproduce the build for every platform a release claims; do not copy an x64 result into an ARM acceptance record.

3. Solution isolation—the prerequisite that prevented GUID damage

Section titled “3. Solution isolation—the prerequisite that prevented GUID damage”

A .plcproj is a nested PLC project, not a standalone Visual Studio solution. Open the supplied .slnx wrapper, or create a TwinCAT XAE Project and use PLC → Add Existing Item….

Use these wrappers independently:

Order Purpose Wrapper
1 Core library FraktalCore/PLC/TwinCAT/Framework/FraktalCore.slnx
2 Modules library FraktalCore/PLC/TwinCAT/Framework/FraktalModules.slnx
3 Internal Press feature bench FraktalCore/PLC/TwinCAT/Examples/PressDemo/PressDemo.slnx
4 Core/Modules test gate FraktalCore/PLC/TwinCAT/Tests/FraktalTests.slnx
5 Internal Press integration gate FraktalCore/PLC/TwinCAT/Examples/PressDemo/PressTests.slnx

Close one wrapper before opening the next when source-library and consuming projects would otherwise coexist. In particular:

  • never load Core/Modules source projects beside an application that consumes their installed versions;
  • never load Fraktal_Press_Demo.plcproj beside PressTests.plcproj, because the test project links the same physical Press Unit/sequence/release objects;
  • after installing a changed library or editing a .plcproj reference, close and reopen the consumer solution so XAE discards its in-memory resolution.

This isolation was introduced after one combined solution produced duplicate object ownership, GUID/Line-ID rewrites, and more than one thousand warnings.

4. Full compile and local library installation

Section titled “4. Full compile and local library installation”

The VS2017-based x32 Shell (TcXaeShell.DTE.15.0) opens legacy .sln files, not .slnx. Use the single-library wrappers Framework/FraktalCore.sln and Framework/FraktalModules.sln, in that order, then close the library solution before opening Examples/PressDemo/PressDemoX32.sln. They point at the same authoritative PLC projects as the modern wrappers. IDE bitness does not select the PLC architecture: choose TwinCAT RT (x86) or TwinCAT RT (x64) for the target.

Run automation for this Shell from 32-bit PowerShell:

Terminal window
& "$env:WINDIR\SysWOW64\WindowsPowerShell\v1.0\powershell.exe" -NoProfile -File `
FraktalCore\PLC\TwinCAT\tools\Invoke-TwinCatLibraryInstall.ps1 `
-DteProgId TcXaeShell.DTE.15.0 -Platform 'TwinCAT RT (x86)' `
-OutputDirectory FraktalCore\PLC\TwinCAT\Framework\Release\x32

The installer selects the legacy library wrappers for this ProgID. Keep the Modules → Core reference and the consumer version pins. An installed Modules library that omits its Core dependency cannot be repaired by adding Core only to Press. Also refresh the exported .library files: reinstalling an older export replaces the repaired repository entry. The 2026-10-05 x32 repair found exactly that stale file under Release/x32, and verified both object checks and full offline builds in the actual x32 Shell. Download/activation still has the separate target/commissioning boundary in §1.

  1. Close any application or Modules solution that consumes Fraktal_Core.
  2. Open Framework/FraktalCore.slnx.
  3. Select the required Debug|TwinCAT OS (<platform>) combination.
  4. Under PLC → Fraktal_Core, select the nested Fraktal_Core Project.
  5. Run Build (use Rebuild when replacing an installed version). Also run Check all objects for a library, because unused public objects must compile.
  6. Open View → Error List. Accept only zero errors and zero warnings for the Fraktal source. In automation, the corresponding result was LastBuildInfo=0; that is DTE’s count of projects that failed in the last solution build, not a substitute for inspecting diagnostics.
  7. Confirm that Framework/Fraktal_Core/Fraktal_Core.tmc was regenerated when TMC generation is part of the build evidence.
  8. Confirm the PLC project properties before saving:
    • title Fraktal_Core;
    • company fraktal-automation;
    • project version 0.4.0.0 for the recorded baseline;
    • placeholder Fraktal_Core.
  9. Right-click the nested Fraktal_Core Project and select Save as library and install. Choose the local development artifact path in the save dialog.
  10. Open PLC → Library Repository, find company fraktal-automation, and confirm that exactly the intended Fraktal_Core version is installed.
  11. Save and close the solution.

The recorded libraries had <Released>false</Released> and were installed into the local development repository. The saved .library/.compiled-library file path was not archived, so the 2026-08-01 action is local-development evidence, not a claim that a signed release library was distributed.

  1. With the Core source solution closed, open Framework/FraktalModules.slnx.
  2. Expand References and verify that placeholder Fraktal_Core resolves to the just-installed intended version. If every Modules type is unknown, stop: fix this one reference rather than editing dependent POUs.
  3. Select the same claimed platform used for Core.
  4. Select the nested Fraktal_Modules Project; run Build/Rebuild and Check all objects.
  5. Require zero errors/warnings and, when applicable, confirm regeneration of Framework/Fraktal_Modules/Fraktal_Modules.tmc.
  6. Verify title/company/version/placeholder. The recorded baseline was Fraktal_Modules, fraktal-automation, 0.3.0.0, and Fraktal_Modules.
  7. Right-click the nested project → Save as library and install.
  8. Verify the intended version in PLC → Library Repository, save, and close.

TwinCAT’s Automation Interface exposes the equivalent ITcPlcIECProject.SaveAsLibrary(path, install), and tools/Invoke-TwinCatLibraryInstall.ps1 now automates the §4.1/§4.2 sequence above: it installs Core then Modules in that order (Modules consumes Core through an installed reference, so the order is not optional), opens each solution in its own isolated hidden XAE, and runs CheckAllObjects() first so a library that does not compile never replaces a good one in the repository. Its evidence boundary is exactly the GUI action’s — a local development install, not a released or distributed package, and no proof that any consumer was rebuilt against it (§4.3 still applies).

This step is not optional after changing a library. A consumer such as Tests/Fraktal_Tests resolves Fraktal_Modules as an installed placeholder, never from library source, so a newly added type stays invisible until the library is reinstalled. The symptom is the object-check gate failing the consumer with a wall of C0046: Identifier ... not defined naming everything except the real cause.

After both installs, open each consumer in its own solution, reload its placeholders, and compile the nested IEC project. The recorded sequence was:

  1. reopen the internal Press bench and build Fraktal_Press_Demo Project;
  2. open FraktalTests.slnx separately and check/build its nested test project;
  3. open PressTests.slnx separately and check/build its nested test project.

The initial direct nested Core, Modules, and Press builds returned LastBuildInfo=0, an empty Error List, and regenerated their TMC files. A full system-project build then stopped at Check config because its saved remote target was unavailable. That system-level result was not reported as a PLC compiler failure; the nested IEC build was the compiler authority.

5. Maintained hidden-XAE object-check gate

Section titled “5. Maintained hidden-XAE object-check gate”

From the repository root:

Terminal window
.\tools\Invoke-TwinCatBuild.ps1

For each test solution the script:

  1. creates a fresh hidden VisualStudio.DTE.18.0 process;
  2. opens only that .slnx;
  3. selects Debug|TwinCAT OS (x64);
  4. gets the TwinCAT System Manager from the first solution project;
  5. resolves TIPC^<PLC name>^<PLC name> Project;
  6. fails if BootProjectAutostart is true;
  7. calls CheckAllObjects();
  8. writes one log under artifacts/twincat-build/;
  9. closes the solution without saving, quits DTE, and releases COM objects.

An OLE message filter retries transient RPC_E_CALL_REJECTED responses while PLC Control is loading. It does not fix a broken XAE registration. If startup returns CO_E_SERVER_EXEC_FAILURE, close stale hidden XAE processes created by the failed attempt and retry from a clean interactive session; never kill an unidentified or operator-owned XAE process.

The command’s success means CheckAllObjects=TRUE and autostart false for both test wrappers. It does not regenerate every build artifact reliably and never contacts a target.

5.1 Diagnostic boundary when CheckAllObjects() returns FALSE

Section titled “5.1 Diagnostic boundary when CheckAllObjects() returns FALSE”

ITcPlcIECProject2.CheckAllObjects() returns a Boolean; the documented TwinCAT Automation Interface exposes no message collection on that method. Beckhoff also states that Check all objects performs no code generation and creates no compilation-information file. The Boolean and detailed diagnostics therefore come from separate automation surfaces.

Beckhoff documents reading the IDE Error List through EnvDTE80.DTE2.ToolWindows.ErrorList.ErrorItems. The DTE2 qualification is essential: a COM object created from VisualStudio.DTE.<version> is commonly seen by PowerShell as base EnvDTE.DTE; reading ToolWindows through that base wrapper can report no property or lead to an empty/incorrect probe. Load the envdte80.dll from the same Visual Studio/TcXaeShell installation, query the DTE2 COM interface, and read the collection only after synchronous CheckAllObjects() returns. The Build Output pane is a second useful source: on the pinned host PLC Control writes the full IEC compile transcript there.

Verified 2026-08-05 with Visual Studio 18 and TwinCAT 3.1.4026: a hidden check of FraktalTests.slnx returned FALSE; the corrected DTE2 access returned six ErrorItems, including description, project, file/object, line, and column, and the DTE Build pane contained the same six coded compiler messages plus Compile complete -- 6 errors, 0 warnings. The IDE window did not need to be visible.

Consequently:

  • FALSE is authoritative evidence that the all-object gate failed;
  • DTE2 ErrorItems and Build-pane text are diagnostic detail, not the pass/fail authority; zero captured rows never override FALSE;
  • base-DTE access, checking before the operation completes, or loading interop types from a different IDE installation can explain a misleading zero count;
  • a .compileinfo file is not a Check-all-objects error log. Build/Rebuild may create compile information, but checks only used objects and therefore cannot replace the library-oriented all-object gate.

References: Beckhoff’s Automation Interface call, Check all objects command, the official Automation Interface manual (Error List access and the DTE2 requirement), and PLC Error List; Microsoft’s Output-window automation and OutputWindowPane.TextDocument.

5.2 Automated capture and visible fallback

Section titled “5.2 Automated capture and visible fallback”

FraktalCore/PLC/TwinCAT/tools/TcXaeDte.ps1 loads the matching EnvDTE80 interop, captures the DTE2 Error List, and snapshots every readable Output pane. It is dot-sourced by both Invoke-TwinCatBuild.ps1 and Invoke-TwinCatTcUnitGate.ps1.

That sharing is not tidiness. Until 2026-08-16 each gate carried its own copy, and the copies diverged: the TcUnit gate reached the Output window by walking $Dte.Windows probing .Caption, and read panes through Selection.SelectAll(). Both hit exactly the late-binding failure §5.1 warns about — The property 'Caption' cannot be found on this object — so its capture threw on the first window and fell into a catch on every run. That gate had no Output-pane diagnostics at all, which is why an activation that silently did nothing was indistinguishable from a capture limitation for weeks. One implementation, so this section has one thing to be true about.

The per-solution log contains:

  • CheckAllObjects=True|False;
  • Dte2Interop=<loaded assembly> or an explicit capture-unavailable reason;
  • DteErrorListCount=<n> and one structured line per item;
  • the Build pane transcript, including TwinCAT compiler codes and the final error/warning count when XAE supplies it;
  • other DTE panes as host/package troubleshooting context.

This is the primary detailed-message artifact. If CheckAllObjects=False and the log has neither nonzero ErrorItems nor a compiler transcript, use the visible fallback without changing the project or platform:

  1. Record the failing log’s solution path, configuration, platform, IEC project path, and XAE build.

  2. Open only that wrapper in a visible XAE process and activate the same configuration/platform. Do not use an already-open solution with extra source or consumer projects.

  3. Open TwinCAT’s View -> Error List, clear its existing rows and filters, select the whole PLC project/solution scope, and enable Errors, Warnings, and Messages.

  4. Select the same nested <name> Project and run Check all objects again.

  5. Click inside the PLC Error List, select all rows, and use Copy from its context menu (or Ctrl+C after selecting the rows). Paste the tabular result into a UTF-8 text/TSV file beside the hidden log, for example:

    Terminal window
    Get-Clipboard -Raw | Set-Content -Encoding utf8 `
    artifacts\twincat-build\FraktalTests-check-all-objects-errors.tsv
  6. Retain the unedited export with the Boolean log. Add a screenshot only when the clipboard omits a column or related-position row; the text export remains the searchable diagnostic artifact.

Do not parse visible clipboard columns as a stable CI protocol: labels, localization, and related-position formatting can vary by XAE build. Prefer the documented DTE2 collection and raw Build-pane text. A version-pinned Windows UI Automation helper could scrape the grid, but it is unnecessary on the verified host and remains an undocumented UI dependency. It shall never turn an unreadable list into a pass.

  • TcXaeShell.exe /Log <path> (where that shell accepts the Visual Studio switch) produces the Visual Studio activity log. Use it for package loading, COM registration, extension crashes, and IDE startup failures—not for IEC source diagnostics. Microsoft documents /Log as an IDE troubleshooting log.
  • The DTE Build Output pane is the verified textual IEC diagnostic log for the direct CheckAllObjects() call on this host. Retain it with the Boolean. A separate devenv.com ... /Build ... /Out <file> invokes Build, not Check all objects, and therefore does not cover unused library objects.
  • TwinCAT Event Logger output belongs to activation, runtime, ADS, and TcUnit evidence. It does not contain an offline Check-all-objects error list.

Reference: Microsoft’s /Log switch.

6. Manual isolated-runtime TcUnit execution

Section titled “6. Manual isolated-runtime TcUnit execution”

The runtime part of the recorded acceptance was performed by the operator under agent instructions, not by Invoke-TwinCatBuild.ps1.

6.0 First check the host can run a gate at all

Section titled “6.0 First check the host can run a gate at all”

An engineering-only install compiles every solution and passes the whole object-check gate, so a host can look fully capable and still have nowhere to download to. One command settles it, and it is the ONLY one that does:

Terminal window
cd FraktalCore/HMI/gateway
dart run tool/probe_sim_flag.dart <amsNetId> 851

Distinguish the two ADS failures, because they send you to different places: error 6 is “the router answered, nothing is on that port” (no runtime, or the PLC is in Config mode); error 7 is “no such target” (routing or AmsNetId wrong). Only the second is a network problem.

Do not conclude “no runtime” from the filesystem. A TwinCAT 4026 usermode runtime is instantiated under

C:\ProgramData\Beckhoff\TwinCAT\3.1\Runtimes\<InstanceName>\3.1\

and not beside the shipped UmRT_Template under Program Files (x86), which stays empty however many instances exist. There is likewise no HKLM:\SOFTWARE\WOW6432Node\Beckhoff\TwinCAT3\Runtimes key to consult. This note previously recommended exactly those two checks and drew the wrong conclusion from them on a host that did have a working UmRT_Default instance: absence under Program Files proves nothing. TcSysSrv running only means the AMS router is up; the process that indicates a usermode runtime is TcSystemServiceUm.

The instance directory is also where the evidence lives: Boot/Plc/Port_851.* is the downloaded boot application, Boot/CurrentConfig.xml the activated configuration, and Boot/LoggedEvents.db the TcEventLogger store.

LoggedEvents.db does not contain TcUnit results. It is the §‑alarm/event API store and is empty on a test runtime. TcUnit reports through ADSLOGSTR, which reaches the AMS router log that XAE renders in its event view and which TwinCAT does not persist to disk anywhere on the target. That, not a missing hook, is why §9 records the runtime gate as un-automated: the numbers exist only in a live view, so a result is read by a person or by something that subscribes to the router log.

  1. Use only the isolated test VM/runtime. Confirm its route/identity before any activation; do not infer the target from the engineering AMS Net ID shown in the event log.
  2. Keep the local Press bench or any machine runtime out of scope.
  3. Confirm Autostart Boot Project is disabled in the selected test wrapper and on the target. The serialized false value prevents a new autostart selection; it does not delete old boot data already present on a runtime.
  4. If an older test application returns after restart, disable/remove that stale boot project on the isolated target before continuing.

Perform this sequence first for FraktalTests.slnx, then close it and repeat for PressTests.slnx:

  1. Open only the gate’s solution.
  2. Select the isolated TwinCAT target and TwinCAT OS (x64).
  3. Run Check all objects or build the nested test project and require an empty Error List.
  4. Select the test PLC as Active PLC Project.
  5. Select TwinCAT → Activate Configuration and confirm the restart into Run mode for the isolated target.
  6. Select PLC → Login. When prompted to create/load the application, answer Yes; this downloads the PLC application.
  7. Select PLC → Start, or press F5.
  8. Watch the TwinCAT Event Logger output from PlcTask, and capture the complete TcUnit runner lines and final summary.
  9. Stop the test PLC or return the isolated target to Config mode after harvesting evidence. Do not create a boot project.

Unattended alternative to steps 6-8 (2026-10-06, §9.2). Activation already writes the selected project’s boot application; with Autostart off, the restarted runtime holds none loaded and the PLC port reports ADS state Invalid. An ADS Run request then loads and starts that boot application. Invoke-TwinCatTcUnitGate.ps1 -StartBootProjectWithAds performs exactly this after its unchanged target, autostart and compile preconditions, refuses a port that is already running, verifies the loaded _AppInfo.ProjectName before reading any result, and stops the PLC over ADS when it is done. No Login, download prompt or Autostart is involved.

6.3 Prove the selected gate, not merely a green summary

Section titled “6.3 Prove the selected gate, not merely a green summary”

Accept a result only when runner identity, suite count, test count, and failure count all match the intended source inventory. For the archived 2026-08-02 baseline:

Gate Required runner in the log Archived result
Core/Modules PRG_TcUnitRunner 84 tests / 26 suites / 0 failed
Internal Press integration PRG_PressTestRunner 9 tests / 2 suites / 0 failed

These numbers describe that source snapshot; an intentional test inventory change must update the expected CI counts and evidence together. A first attempt at the Press gate reported PRG_TcUnitRunner and 84/26, proving that the Core test application was still selected. Selecting/downloading PressTests.slnx produced the correct 8/2 result.

The Core/Modules inventory has since grown to 30 suites / 98 tests. FB_SequenceRaise_Tests, FB_SequencePar_Tests and FB_StateFlag_Tests were added after the 2026-08-02 baseline and two of them did not compile, so Fraktal_Tests was carried as a known red and its runtime gate could not run at all — a project that does not compile cannot be downloaded. They compile now. Expect these counts for the next run:

Gate Required runner in the log Expected from current source
Core/Modules PRG_TcUnitRunner 235 tests / 49 suites (current inventory)
Internal Press integration PRG_PressTestRunner 9 tests / 2 suites / 0 failed

Derive them from source rather than trusting this table — the suite count is the VAR block of the runner POU, and the test count is the TEST('…') calls in the suites it instantiates. A suite that exists but is not instantiated does not run, and would make the log’s own totals self-consistent while silently under-testing.

Validate captured logs with:

Terminal window
python tools\tcunit_to_junit.py <raw-log> <junit.xml> `
--gate-name <name> --expected-tests <n> --expected-suites <n> `
--expected-runner <PRG_runner>

The validator fails on missing or multiple summaries, inconsistent totals, failures, wrong counts, and missing/mixed/wrong runner identities.

7. Warnings observed and their disposition

Section titled “7. Warnings observed and their disposition”
  • Persistent data of symbol 'PRG_TcUnitRunner.…' not restored appeared when the Press test application replaced the Core test application on ADS port 851. The old symbols did not exist in the new application, restoration was skipped, and the correct Press suites then passed. This was stale test-runtime metadata, not a Press implementation failure.
  • TwinCAT USB support could not be initialized. System start continued was non-blocking on the Windows VM and irrelevant to the simulated test gates.
  • A full solution Check config failure with an unavailable saved target did not invalidate a clean nested IEC build. It did mean target/configuration acceptance was still unproven.
  • A hidden-DTE timeout or COM startup failure is tooling/environment evidence, not a compiler result. Do not reuse an old artifact log as a new pass.
  • Specification/Evidence/2026-08-01_Core_Modules_TcUnit.md
  • Specification/Evidence/2026-08-02_Press_TcUnit.md
  • Specification/Evidence/2026-08-02_Press_TcUnit.raw.log
  • artifacts/twincat-build/<solution>-build.log for local object-check output
  • FraktalCore/PLC/TwinCAT/IMPLEMENTATION_NOTES.md §§83–94 for the chronological compiler/runtime reconciliation

For every future run, retain: repository revision, .plcproj/runner/TMC hashes, XAE/XAR build, platform, target identity and ADS port, autostart state, runner identity, all five TcUnit summary fields, raw log, and generated JUnit. A result without those identities is diagnostic information, not release evidence.

  • no hidden script selected or activated a runtime;
  • no hidden script logged in, downloaded, started, or stopped a PLC;
  • no script created or deleted a boot project;
  • no maintained script saved/installed the two libraries;
  • no test project was loaded on the local Press bench/machine runtime;
  • no internal Press result was treated as electrical, safety, SAT, or production evidence.

Future automation may use the official Automation Interface, but target identity and destructive-state checks must remain explicit. Library creation can use SaveAsLibrary(path, install := TRUE); online actions must stay isolated from all machine routes and preserve the same evidence boundaries.

9.1 Attempted automation and what it measured (2026-08-16)

Section titled “9.1 Attempted automation and what it measured (2026-08-16)”

Invoke-TwinCatTcUnitGate.ps1 automates the engineering half of §6.2 under those conditions: it refuses to activate a target it was not given by name, asserts Autostart is disabled, and requires a clean CheckAllObjects(). Everything up to and including activation works — activation reports Ready for download, the runtime restarts into Run, and the application instance exists, is active, and reports ADS port 851.

ITcPlcOnline.Login() does nothing. It returns immediately, writes no text to any of the ten DTE output panes, and leaves IsLoggedIn false with OnlineOperationState 0 indefinitely. Eliminated by measurement: all PLC_LOGIN_FLAGS combinations including SILENT and FORCEDOWNLOAD; 90 s of polling for asynchronous completion; an alternative DTE ProgID; the Unknown TMC file version warning, which also appears in successful manual runs and is therefore benign; releasing the tree item before use; and selecting the active application instance.

The working explanation is that login requires answering the create/load prompt of §6.2 step 6, and a hidden SuppressUI DTE cannot answer it — a suppressed prompt is declined. On that reading the second bullet above records a constraint, not a preference, and closing it needs a mechanism that does not drive the IDE (TcUnit-Runner is the known one), not another login flag.

Two rules follow, and they are the durable part:

  • A void automation call that succeeds silently is not evidence. Login() and Start() both return void and both complete without error while doing nothing. The gate now asserts IsLoggedIn and PLC_APPSTATE_RUN after them. Revisions before this date asserted neither and reported clean exits for runs in which no test executed — see the correction in Specification/Evidence/2026-08-15_Core_Modules_TcUnit.md.
  • Once the PLC is running by any route, the result no longer needs a human reader. Read-TcUnitResults.ps1 reads TcUnit’s own GVL_TcUnit.TestResults.TestSuiteResults over ADS — per-suite and per-test, with failure messages — and writes it in the summary format tcunit_to_junit.py already validates. It waits on TcUnit’s AllTestSuitesFinished flag rather than a fixed window, and reads by name through ADSIGRP_SYM_VALBYNAME so it consumes no symbol handles.

9.2 The runtime step without Login (2026-10-06)

Section titled “9.2 The runtime step without Login (2026-10-06)”

The mechanism §9.1 asked for does not need TcUnit-Runner. Measured on UmRT_Default, XAE/XAR 3.1.4026.24: after activation with Autostart off, port 851 reports Invalid (no application loaded), and WriteControl(Run) on that port loads and starts the boot application activation had just written - its SHA-256 matched the project’s compiled _Boot output. The gate’s -StartBootProjectWithAds switch is that route, guarded as described in §6.2; Login remains the interactive route. With it the aggregate gate ran 227/227 in 47 suites and the Press gate 9/9 for each of LD, ST and SFC, read back over ADS and validated by tcunit_to_junit.py (evidence: Specification/Evidence/2026-10-06_TC3_MissingFeatures.md). It still never enables Autostart, never targets a runtime it was not given by name, and a void call still proves nothing: the gate asserts the ADS Run state and the loaded project’s name. A runtime that is loading the application may refuse a state read for a moment (ADS 0x4, router mailbox, measured once); the poll retries until its deadline.


Built from Specification/Guides/TWINCAT_XAE_WORKFLOW.md at revision a1163c7 of the Fraktal repository.