Fraktal OPC UA transport

This document defines the deployment boundary behind the generic HMI PlcRepository. It does not change the module contract.

On a Windows/TwinCAT host the native default is now ADS, not direct OPC UA — it is the faster native path and needs no TF6100 server. OPC UA remains a first-class, selectable HMI transport for remote and non-Beckhoff PLCs. ADS is a drop-in OpcUaSessionClient that emits the identical fraktal.opcua.snapshot.v1 document, so the mapper, config-manifest, and mailbox contracts apply unchanged to both direct transports. Read-tier behavior is capability-negotiated: the current direct ADS/OPC UA clients provide targeted/tiered reads, while the Web gateway currently relays a complete server-side snapshot. The ADS transport is specified in ADS_TRANSPORT_MIGRATION.md; the summary is below.

Flutter target Transport Implementation
Windows (TwinCAT) direct ADS (native default) fraktal_ads.dll (TcAdsDll) through dart:ffi in the fraktal-ads isolate
Windows (remote / non-Beckhoff) direct OPC UA or the gateway native ws/wss client; open62541 through dart:ffi
Linux / Android Fraktal WebSocket gateway native ws/wss client; direct C ABI remains source-compatible where packaged
Web Fraktal WebSocket gateway browser WebSocket client; the gateway owns the OPC UA session
Gateway → Siemens S7 (Fraktal/TIA) S7 Web API (s7web://) WebApiSessionClient over one pinned HTTPS connection; licence-free (Part IV §11.1a)

Browsers shall never attempt raw OPC UA TCP. Every transport delivers the same flat fraktal.opcua.snapshot.v1 document to OpcUaSnapshotMapper, so discovery and UI behavior cannot drift by platform or by transport.

ADS transport (native Windows/TwinCAT default)

Section titled “ADS transport (native Windows/TwinCAT default)”

The native Windows client may connect over ADS with an ads://<AmsNetId>:<port> endpoint (default ads://127.0.0.1.1.1:851, the local runtime; the wizard seeds it and the operator confirms the machine’s AmsNetId). It is a dart:ffi client in the dedicated fraktal-ads isolate over fraktal_ads.dll, which wraps Beckhoff’s TcAdsDll using Beckhoff’s own headers so struct/datatype layout is version-correct. The build self-skips when not on Windows or when TcAdsDll is absent, so the HMI falls back to OPC UA and non-TwinCAT builds are unaffected.

  • Discovery is a datatype-table walk: SYM_UPLOADINFO2 (0xF00F) sizes the symbol and datatype tables, SYM_DT_UPLOAD (0xF00E) uploads the datatype table (members reference their type by namespaced name, e.g. Fraktal_Core.ST_ModuleStatus, resolved recursively), and SYM_UPLOAD (0xF00B) lists top-level symbols; each MAIN.* / fieldbus symbol is expanded to leaves. The resulting flat path set feeds the unchanged mapper — MAIN.PneumaticPress.Status.State becomes PLC1/MAIN/PneumaticPress/Status/State (synthetic PLC1/ prefix, dots→slashes), the same identity the OPC UA snapshot emits.
  • Reads use value handles (SYM_HNDBYNAME 0xF003 → SYM_VALBYHND 0xF005 → SYM_RELEASEHND 0xF006). The whole fast tier is read in one round trip by the ADS sum-command SUMUP_READ (0xF080); a per-symbol path is kept as a fallback for runtimes that lack the sum service. Measured: steady-state snapshot ~15 ms (vs ~2.3 s reading 1.6k symbols individually).
  • Writes are typed handle writes; mode-change round-trips ~86 ms median through the production repository path — the metric the OPC UA path only reached after the read-tier work, and with none of the TF6100 licensing/TOFU/handle-pool (0x710) failure classes.
  • Read tiers map directly: the fast/slow tiers are read every snapshot (ADS is fast enough that the slow-tier heartbeat is not required), and the excluded set (config manifest + on-demand drill-down + fieldbus) is never read cyclically — it is served by targeted readValues calls, identical to the OPC UA excluded tier.

ADS is Beckhoff-specific by design: it is the native fast path, while OPC UA stays the portable multi-brand path — a PLC with a licensed OPC UA server integrates by pointing the same HMI at opc.tcp://…. A Siemens CPU without that licence uses the gateway’s s7web:// transport (below); Allen-Bradley uses its CIP gateway. Reconnect-on-router-loss and first-snapshot handle batching are tracked as hardening in ADS_TRANSPORT_MIGRATION.md §11.

Siemens S7 Web API transport (Fraktal/TIA)

Section titled “Siemens S7 Web API transport (Fraktal/TIA)”

The gateway may connect to a Siemens S7-1500 / S7-1200 (≥ V4.5) CPU with an s7web://<host>[:port] endpoint. WebApiSessionClient (packages/fraktal_opcua_client) speaks the CPU’s own JSON-RPC 2.0 Web API over HTTPS and emits the same fraktal.opcua.snapshot.v1 document, so the mapper, manifest and mailbox contracts apply unchanged — no runtime licence is needed, unlike the CPU’s OPC UA server. Measured on a CPU 1214C V4.7.3 (Siemens/Evidence/TIA_S1W_WEBAPI_2026-10-08.md):

  • Trust is one pinned server certificate (--plc-certificate, PEM or DER), checked on every new connection; system roots are never consulted. The CPU user (UMAC on S7-1200 V4.7) holds only read/write-process-data rights, and members without “Writable from HMI/OPC UA/Web API” refuse writes in the CPU (205), so the mailbox remains the single write surface even past the gateway.
  • Discovery browses every DB whose top level has a Status structure, breadth-first in batched requests, and expands structures and arrays to scalar leaves (the Web API reads leaves only). Paths are spelled as on ADS: PLC1/<Root>/<Member>/Rows[3]/<Leaf>; Web API names quote every segment.
  • Cost is ≈ 57 ms per request + ≈ 15 ms per leaf; the CPU serves one request at a time across sessions, so requests carry at most --webapi-batch leaves (default 20). Slow and excluded tiers behave as on the native clients; a slow path is re-read every 10 s or on refreshSlowPaths.
  • Connection. An S7-1200 TLS handshake costs ≈ 2.75 s, the CPU closes an idle connection after 1–2 s, and dart:io HttpClient opened a new connection per request to it. The client therefore keeps ONE persistent TLS connection, serializes requests on it and sends Api.Ping before the idle close. A request on a connection the CPU dropped is resent once on a new one — safe, because reads are idempotent and the PLC acts only on a changed Sequence.
  • Session. One Api.Login; an expired token (2, after 2.5 min idle) is renewed once and the call resent (a refused call applied nothing); Api.Login is never sent with the old token (101).
  • Mailbox. writeBatch writes every argument in one request, then the Sequence commit alone — only if every argument was accepted.
  • Scalar encodings on the S7-1500 reference. time becomes Int32 milliseconds. ldt is a signed64-bit decimal string of Unix nanoseconds; the transport emits DateTime as an ISO UTC string with nine fractional digits, or zero for Core’s unset sentinel. Malformed or out-of-range LDT yields Bad status and no value. The generic HMI date parser retains microseconds. lint/ulint keep exact decimal strings labelled Int64/UInt64; wide wstring fields become String. These encodings passed the live client on simulated1516 V3.0/Advanced7; full Unit rendering and commands are separate gates (evidence).

The native library exports create/connect/disconnect, snapshot, typed write and error functions from native/opcua/fraktal_opcua_bridge.h. open62541 1.4.12 and Mbed TLS 3.6.6 are pinned and vendored with their licenses. All native calls run in the fraktal-opcua Dart isolate; the Flutter UI isolate never performs a blocking browse/read/write.

The ABI exposes frk_opcua_connect_secure with an explicit profile, policy URI, application URI, client certificate, private key, optional private-key password, server/CA trust list, and optional revocation list. Secure profiles force SignAndEncrypt; reconnect reuses the same material and may not downgrade. Private-key bytes are cleared after open62541/Mbed TLS configures the client. Credentials are process inputs, not endpoint/query data or HMI settings JSON.

Four deployment profiles are defined:

Profile Channel / identity Rule
production trusted certificate + SignAndEncrypt + named TF6100 user Default; required for a network-connected production cell
secure-anonymous trusted certificate + SignAndEncrypt + Anonymous token Transitional commissioning only; preserves channel and application authentication
commissioning-anonymous None + Anonymous Troubleshooting/initial bring-up; gateway warns and auto-stops after a bounded TTL
isolated-anonymous None + Anonymous Explicit exception for one physically isolated, unrouted PLC/HMI deployment

Missing production material is a startup failure. A failed secure connection shall never retry with a weaker profile. Anonymous namespace/write rights shall be least-privilege. A network-connected production target shall disable the Anonymous/None exception after commissioning. A permanent isolated exception requires documented physical/network controls and ownership.

The direct Windows opc.tcp wizard path intentionally remains Anonymous/None and logs a security warning; it is only for commissioning, troubleshooting, or the isolated exception. The cross-platform production path is wss through the gateway, so PLC credentials and OPC UA private keys remain under a dedicated gateway service identity.

A TwinCAT PLC online change reloads the TF6100 Data Access namespace and commonly tears the OPC UA session down. The native client is driven by explicit service calls (no open62541 event loop), so it recovers deliberately, not via auto-reconnect:

  • Session loss — every snapshot checks the live channel/session/connect status; if it degraded, the client reconnects with the cached endpoint and clears the cached NodeId map, then re-browses. This is transparent: no command is queued across the gap, and the HMI returns to LIVE as soon as the session is back (a STALE/DOWN blip only if the reconnect itself fails).
  • Structural change with a surviving session — reads against cached NodeIds that no longer resolve (BadNodeIdUnknown/BadNodeIdInvalid) are counted; a surge (≥20 % of cached variables gone) invalidates the discovery cache so the next snapshot re-browses the fresh tree (added/removed/renamed symbols).
  • Writes issued during the brief reconnect window are rejected, not queued (§14); the operator re-issues once the HMI is LIVE again.

Reconnect attempts are naturally throttled by the connect timeout and the shared in-flight refresh, so a PLC that is genuinely down cannot starve the isolate.

{
"protocol": "fraktal.opcua.snapshot.v1",
"nodeCount": 123,
"truncated": false,
"namespaces": [
"http://opcfoundation.org/UA/",
"urn:BeckhoffAutomation:Ua:PLC1"
],
"values": {
"PLC1/MAIN/PneumaticPress/Status/Name": "PneumaticPress",
"PLC1/MAIN/PneumaticPress/Status/ModuleType": 1
},
"dataValues": {
"PLC1/MAIN/PneumaticPress/OutImm/Pressure": {
"status": 0,
"type": "Double",
"value": 4.2,
"sourceTimestampUs": "1784613600123456",
"serverTimestampUs": "1784613600124000"
}
}
}

dataValues is an additive v1 field carrying the OPC UA DataValue quality, runtime scalar type, value when encodable, and optional timestamps. Timestamps are Unix microseconds encoded as decimal strings so JavaScript cannot lose 64-bit precision. values remains the compatibility/discovery surface and contains only Good-quality scalar values. A client may retain a Bad or Uncertain tag from dataValues so an imported binding survives a transient fault, but it shall render that tag unavailable and shall not chart or write from the stale payload. Good status codes are classified by their OPC UA severity bits, not by testing only for the literal zero status.

An adapter may add a deployment freshness envelope, version 1. Its optional top-level freshnessBudget contains integer millisecond fields pollPeriodMs, fastGoodMs, fastExpiryMs, slowPeriodMs, slowGoodMs, slowExpiryMs, and schemaVersion: 1. Each period is positive and less than its Good limit, which is less than its expiry limit. Values are bounded to 60,000 ms. These limits belong to the measured deployment; they are not defaults for an entire binding.

With this envelope, sampleAgeMs is the monotonic age of the accepted complete acquisition, measured conservatively from before I/O. Each DataValue also carries its own ageMs and tier (fast or slow); an excluded native group uses the slow limits when retained and refreshes only on targeted demand while excluded. A visible table promoted to slow refreshes on the declared heartbeat. A native group with any fast leaf remains fast after intersecting all viewers’ tier requests. Cached replies advance ages without replacing acquisition timestamps. No controller source UTC time is inferred from these ages.

At a Good limit a previously Good value becomes Uncertain (0x40000000, reason read-late); at expiry it becomes Bad (0x80000000, read-expired). Existing non-Good quality is never improved by aging. Invalid leaf metadata maps to Bad (read-metadata-invalid). A present malformed/unknown budget, invalid complete sample age, or disappearance of an established budget fails closed.

Budgeted complete polls renew on their declared start-to-start cadence with one acquisition in flight. When a read overruns its period, the next starts after completion instead of waiting for a later periodic-timer boundary; faster reads wait out the remaining period. Expiry still runs independently of pending work.

The repository uses a local monotonic clock and adds the snapshot RPC’s elapsed time as a conservative transit allowance. A gateway may additionally publish responseProcessingMs, bracketed from request handling to the exact monotonic boundary at which source ages were calculated. The client subtracts that server wait/read from the full RPC allowance and adds one millisecond for clock resolution. Cached source ages/timestamps do not change; malformed, nonfinite or negative brackets, or values larger than the RPC plus that millisecond, fail closed. Missing brackets preserve the legacy full RPC allowance. This avoids counting native acquisition twice without relaxing Good/expiry limits. Its expiry timer runs independently of a pending RPC. At the complete sample’s Good limit it withdraws the interactive shell and cached Good data (STALE); at expiry it reports DOWN. It also checks age synchronously before each write or queued request. Only a fresh complete snapshot restores LIVE; partial mailbox/Ack reads cannot renew it. Declared polling continues during initial manifest hydration and long interactive operations once a valid tree exists. The delivery timeout remains a separate limit. Older transports without this optional envelope retain their existing polling policy and do not inherit its evidence.

The mapper recognizes a module only through Status : ST_ModuleStatus and builds its HMI identity from published Status.Name values. Server-specific prefixes such as PLC1/MAIN do not enter the Fraktal identity. namespaces is diagnostic metadata read from the standard OPC UA Server/NamespaceArray: if the PLC namespace is present while Objects exposes only Server, the connected identity lacks browse rights; if it is absent, the TF6100 Data Access NodeManager/TMC configuration was not loaded.

Native discovery is breadth-first and cached once per OPC UA session. Breadth first ordering guarantees that shallow root contract/mailbox nodes are found before implementation detail when a server publishes a large tree. Value nodes are subsequently read in bounded service batches; the 500 ms repository refresh does not recursively browse the namespace again. truncated=true means the configured discovery cap was reached and is a commissioning defect: narrow the published namespace or revise the contract-aware projection after measuring it, instead of silently treating a partial tree as complete.

TF6100 may expose references held by recipe catalogs, I/O drivers, or control coordinators as additional navigable paths to the same FB. The snapshot may carry those values. Status.Name is a qualified dotted identity, so the mapper accepts a candidate when its final browse-name segment equals the final segment of Status.Name, deduplicates every module by the complete identity, and builds parentage from the dotted identity prefix. Among multiple same-identity candidates it selects the shallowest path; discarded aliases are logged as opcua-aliases-discarded. This implements Part II §3.10’s rule that a reference/owner alias is not another deployed module/root.

The direct native HMI and the gateway’s commissioning-anonymous / isolated-anonymous profiles use Anonymous with SecurityPolicy=None. The following Anonymous setup applies only to those explicit exception profiles. Production and secure-anonymous instead require a trusted client application certificate and a matching SignAndEncrypt endpoint; production additionally requires a named least-privilege TF6100 user.

TF6100 5.x (TwinCAT 4026) first requires a one-time Trust-On-First-Use initialization before it publishes any Data Access namespace; until then an Objects browse shows only Server and Initialization and the HMI reports zero root Units. Initialize once from the OPC UA Configurator over a secured endpoint (Basic256Sha256 / SignAndEncrypt) with a UserName admin identity — a credential token cannot be sent over a None channel. Initialization then disables the Anonymous token, so the anonymous commissioning access below must be re-added afterward. On a usermode/standalone runtime the server lacks rights to create its admin OS user during init; pre-create that account in Windows first. Full procedure and the local-PC quick path are in FIRST_PROJECT_AGENT_GUIDE.md §7.0 / §11.

In the OPC UA Configurator connected to the remote PLC, open Security and:

  1. Edit the existing Anonymous user and assign it to the built-in Users group. Configurator versions that offer only Guests, Users, and Administrator should use Users; do not create a second Anonymous user or grant Administrator for HMI data access.
  2. In the Users group’s namespace/default access, add urn:BeckhoffAutomation:Ua:PLC1 with Browse, ReadAttribute, and ReadValue. Namespace browse permission is required so PLC1 and MAIN are visible; granting access only at the root Unit cannot expose hidden ancestors.
  3. If node permissions are used, add the deployed root Unit with depth -1 for inherited Browse/Read. Add Write only for its HmiRequest subtree.
  4. Activate the changed server configuration and restart/reload TF6100 before retrying the HMI.

When the server trace accepts AnonymousIdentityToken, prints Roles assigned to session without any role entries, and returns only Server from an Objects browse, these rights have not reached the active server configuration.

For TwinCAT TMC-Filtered publication, every deployed root Unit declaration is explicitly marked with {attribute 'OPC.UA.DA' := '1'}. The marker is inherited by the root’s children and makes the intended forest explicit. Fraktal does not use TwinCAT’s definition-level enable marker because it also publishes undeployed instances and reference aliases. A separately published GVL value places the marker immediately before that variable, not before VAR_GLOBAL. After activating a changed PLC project, restart/reload TF6100 so it imports the updated Port_<ADS port>.tmc; an authorized identity browsing Objects shall then see the configured Data Access device and a direct MAIN/<Root> path.

The inherited root marker must not publish implementation-only pointer, interface-reference, or REFERENCE TO storage. Mark those fields with {attribute 'OPC.UA.DA' := '0'} (or keep their owner outside the published subtree). An Unsupported datatype ... UXINT importer entry means TF6100 skipped such a pointer-like leaf. Fix an application-owned path and reload the TMC; the Beckhoff system leaf TwinCAT_SystemInfoVarList._AppInfo.TComSrvPtr is outside the Fraktal contract and can be ignored when the application namespace and roots otherwise import correctly.

The native browser reads NodeCount and each active ChannelCount before it enqueues the fixed topology arrays. Unused Nodes[] and Channels[] elements therefore do not consume the browse/read budget. A snapshot carrying truncated=true is rejected by both the gateway and HMI; gateway /readyz remains degraded and no operator repository reaches LIVE. Raising the browse cap is not an acceptance fix.

The Web client sends:

{"protocol":"fraktal.opcua.gateway.v1","id":1,"method":"snapshot","params":{}}
{"protocol":"fraktal.opcua.gateway.v1","id":2,"method":"write","params":{"path":"...","valueType":"boolean","value":true}}
{"protocol":"fraktal.opcua.gateway.v1","id":3,"method":"writeBatch","params":{"writes":[{"path":".../HmiRequest/Kind","valueType":"int32","value":4},{"path":".../HmiRequest/Sequence","valueType":"uint32","value":19}]}}
{"protocol":"fraktal.opcua.gateway.v1","id":4,"method":"discoverPaths","params":{}}
{"protocol":"fraktal.opcua.gateway.v1","id":5,"method":"setReadTiers","params":{"revision":7,"slow":[41,42],"excluded":[90,91],"refreshSlow":false}}
{"protocol":"fraktal.opcua.gateway.v1","id":6,"method":"readValues","params":{"revision":7,"indices":[90,91]}}

The gateway replies:

{"id":1,"ok":true,"result":{"protocol":"fraktal.opcua.snapshot.v1","values":{},"dataValues":{}}}
{"id":2,"ok":true,"result":true}
{"id":4,"ok":true,"result":{"revision":7,"nodeCount":1234,"paths":["PLC1/MAIN/Unit/Status/State"]}}

The gateway shall enforce origin/TLS/authentication policy, preserve browse paths and values exactly, serialize writes in request order, and never replay a write after reconnecting.

The gateway relays dataValues without normalizing status codes, types, or timestamps. Native and Web HMIs therefore make the same quality decision from the same server result.

discoverPaths returns the complete stable path vector plus a revision. setReadTiers uses indices into that vector instead of repeating long browse strings; stale revisions, duplicates, overlap, and out-of-range indices fail closed. readValues accepts at most 512 unique indices per request. Clients split larger logical reads into bounded calls and merge the results. A tier profile accepts at most 20,000 indices and the whole request remains bounded to 256 KiB. The first snapshot on a connection includes the discovery vector; after tier setup, cyclic snapshots carry an empty paths list so static browse strings are not retransmitted. A rediscovery increments the revision and clears every connection’s profile before new tiers can be installed.

One gateway owns one native PLC session, so connection-local tier mutations cannot be applied independently at that layer. The server therefore applies the intersection of every connected browser’s slow and excluded sets: a path is slowed or omitted only when all clients agree. A new or not-yet-configured browser temporarily requests the full live surface. This costs bandwidth during bootstrap but cannot make an existing operator view stale or incomplete.

The reference service is FraktalCore/HMI/gateway. It builds as a headless Windows or Linux executable and shares the same native client package as the Windows HMI. Its OPC UA profile is explicit and production is the default. The process binds only to loopback. With --web-root, it also serves the matched compiled Web HMI from the same listener. Release Web builds derive ws:///wss://<page-origin>/fraktal, avoiding a second endpoint setting or a separate static server. Browser and native Windows/Linux/Android clients use the same protocol; the native client validates wss with the platform trust store and may present a deployment-provisioned mTLS certificate/key or protected bearer token. Such identity material is rejected for ws and is never stored in the HMI connection-settings JSON. A remote client shall reach the service through a same-host reverse proxy that terminates trusted TLS, authenticates ordinary HMI access and the WebSocket upgrade, preserves Origin, and proxies both HTTP and WebSocket traffic to loopback. The service checks exact configured remote browser origins as a second boundary; origin checking is not authentication. Installation and acceptance are specified in WEB_HMI_GATEWAY_DEPLOYMENT.md.

Every gateway write is type-checked, globally serialized, attempted once, and restricted to a published root HmiRequest subtree. Deployment may further restrict reads/discovery with repeatable --read-root subtrees and eligible Unit write roots with --write-root; the reference service is read-only until at least one root is configured (an all-root commissioning override is explicit). Invalid protocol versions, binary/oversize requests, non-mailbox paths, and unapproved origins are rejected before OPC UA. One HMI request uses writeBatch: all fields belong to one mailbox, paths are unique, and Sequence : uint32 is the final write. The entire batch holds the global write serializer, so another HMI cannot interleave fields. A standalone Sequence write is rejected. The gateway remembers the last observed/committed sequence per mailbox and rejects a duplicate or skipped commit, preventing two HMI clients from consuming one another’s acknowledgement.

The gateway sends WebSocket Ping frames every 2 s. Native clients also enable a 2 s Ping/Pong watchdog; browser clients rely on the server heartbeat because the browser WebSocket API does not expose control frames. A missing Pong closes the socket. Snapshot transport failures reconnect with jittered exponential backoff (250 ms to 5 s), but writes are never queued or replayed. The first failed snapshot makes the HMI STALE and removes the operator shell; 5 s without a good snapshot makes it DOWN. Cold-start connection failures retry automatically (500 ms to 5 s) while the connection editor remains available after the normal 30 s gate.

/livez reports process liveness. /readyz returns HTTP 200 only when the last OPC UA operation succeeded and HTTP 503 after an observed OPC UA failure. /healthz is the backward-compatible JSON summary. None returns PLC data.

All three replies include writeAccess: enabled reports whether the configured gateway policy enables mutations, roots is the sorted list of configured write roots, and allRootMailboxes reports an effective all-root scope. Explicit roots take precedence over an all-root flag. Scope fields describe configuration even when enabled is false. For the AB gateway, enabling mutations also requires a configured bearer token and a wired mailbox writer; the reference Dart gateway relies on the authenticated reverse proxy described above. These fields contain no credentials and do not attest to proxy authentication, native write permissions, PLC readiness, or a user’s PLC access level. plcReady and the PLC command acknowledgement remain separate. An inert read-only QUERY_CONFIG transaction does not make enabled true.

Config manifest — obscured static publication (Core §3.10.2)

Section titled “Config manifest — obscured static publication (Core §3.10.2)”

Activation-static configuration is deliberately excluded from the cyclic OPC UA tree with {attribute 'OPC.UA.DA' := '0'} and served on demand through the request mailbox instead. This keeps the published address space (and the server’s per-node ADS handle load) proportional to the live data:

Obscured (manifest- or never-served) Stays cyclically published
Catalog/CatalogCount (manual commands) Status/* (discovery identity)
AvailableModels/AvailableModelCount PLCopen outputs, counters, step, mode
ModePolicy, StallTime SupportedModes/RunStylesPublished
Nameplate, AlarmLog Meta/MetaCount ParCfg/StationCfg (editable fields)
ST_BusNode identity (Name/TypeId/Address/ParentIdx/ChannelCount…) ST_BusNode.State, LinkOk
ST_IoChannel identity/capability (Name/Address/Path/ModulePath/Dir/Kind/Unit/Forceable…) channel values/Forced/Quality/FaultActive/Diagnostic

Protocol. The root Unit publishes ConfigRev : UDINT (seeded from boot time, incremented on config writes, model changes, and re-activation) and answers E_HmiRequestKind.QUERY_CONFIG (IntValue = page index) by filling HmiResponse.ConfigPage — a bounded window whose read projection begins with {Scope, Item, ValueText}. Scope is the dotted module identity ('#Fieldbus' for the bus topology); Item reproduces the server’s array naming (Catalog/Catalog[2]/Label, Nodes/Nodes[3]/Channels/Channels[5]/Name) so a generic client rebuilds the exact browse path it would otherwise have read. The enumeration is produced by a deterministic walk (I_ConfigSource. M_AppendConfig: base facets once in FB_ModuleBase, children recursed by the composite base, Unit facets appended, projects may append — the press demo adds its fieldbus topology via F_AppendTopologyConfig). FB_ConfigPager counts the walk and stores only the requested window, so no full manifest buffer exists.

An entry is writable only when its append-only capability tail is complete: WriteKey, non-zero WriteRevision, ConfigKind, ValueType, Writable, RequiresReady, optional Minimum/Maximum, Unit, LabelKey, and optional pipe-separated exact EnumDomain. Missing or conflicting metadata fails closed. WRITE_CONFIG transports TargetPath=Scope, NameValue=WriteKey, IntValue=WriteRevision, and TextValue=candidate; direct writes to Item are not part of the contract. The PLC owning handler rechecks access, owner, revision, type, domain/range, state, and transactional recipe invariants.

Parameter sets (Core ?3.8b). Append-only request kinds are SAVE_CONFIG_SET = 28, LOAD_CONFIG_SET = 29, LIST_CONFIG_SETS = 30, EXPORT_CONFIG_SET = 32, IMPORT_CONFIG_SET = 33, and DELETE_CONFIG_SET = 35; CAPTURE_CONFIG = 27 is the separate teach-capture request. Named operations use TextValue; Save uses IntValue = ConfigKind. Each is CONFIG_SET gated. Loads are staged, validate every record, and apply all or nothing. Model loads use the recipe prepare/readiness/commit path; an adapter lacking that integration shall refuse. List/export are reads and do not require READY. The persistence outcome remains visible separately from the live configuration. The client serializes a complete import/export, including every line and piece, through the mailbox queue. Background config queries wait until that transfer ends; a disconnected transfer is abandoned, never continued on a later link.

Core 0.22.0.0 adds two optional kinds. CREATE_MODEL = 37 uses NameValue for the new code, IntValue for the source model index (0 running), or BoolValue = TRUE and TextValue for a saved Model set. Positive ModelCapacity is required before the HMI offers creation. Existing ordinals and active values remain unchanged. EXPORT_CURRENT_CONFIG = 38, offered only with Features/ExportCurrentConfig = TRUE, uses TextValue for an export name, IntValue for ConfigKind, and DurationMs for the model index (0 running). It returns the immutable document’s header as ConfigSetDocumentLine = 0; EXPORT_CONFIG_SET continues lines 1..ConfigSetDocumentLines by that name on the same connection. No saved-set slot is allocated. The PLC re-checks access for every line. Older bindings expose no capability and refuse these requests.

HMI behavior. The repository fetches all pages when a forest is live and the ConfigRev signature is new (startup, reconnect to a restarted PLC, config write, changeover), synthesizes flat browse-path values from the entries, and overlays them under the live snapshot before mapping. The snapshot mapper receives typed configuration capabilities beside that read-value overlay; facets and views remain transport-agnostic (the mailbox works identically over the gateway). A server that publishes no ConfigRev (older PLC library) is treated as fully published and never queried. Absent manifest data degrades to empty facets, never an error.

The direct native client reads the discovered contract at three rates, so the 2 Hz snapshot only pays for always-visible data. A single classifier (opcua_field_tier.dart) is the source of truth; the bridge stays generic (fast/slow read lists + an excluded set + targeted reads) and the mapper is unchanged. The bridge emits the full discovered path list once per discovery so the client can classify paths it never reads.

Tier Read rate Data (examples)
fast every snapshot (500 ms) tiles, PLCopen state, counters, current step, active alarms (AlarmLog/Active — the global banner), OEE snapshot, live cycle profile, Unit SystemHealth/TimeQuality, and semantic SignalTower state
slow once + ~2 s heartbeat always-visible but slow-changing facets published redundantly on every module: Safety, ControlPower (read-only §9 status mirrors — display lag is bounded by the heartbeat; the PLC safety authority is unaffected)
on-demand only while the owning view is visible drill-down rings/trends excluded while closed; budgeted tiered clients promote visible tables to slow snapshots, otherwise use targeted batches: per module — AlarmLog/Ring, Profiler/History/StepStats, OeeTrend, Part/Result/Records, command Timing; and the fieldbus I/O tree (GVL_<Project>Fieldbus.Topology state/values)
config manifest (above), never cyclic activation-static identity (OPC.UA.DA := '0') — container-matched subtrees are excluded from the cyclic read; leaf-matched names stay cyclic (see below)

Scoping the direct ADS read to the published contract

Section titled “Scoping the direct ADS read to the published contract”

A transport shall not read outside the address space the contract publishes. TF6100 enforces this for free: TMC-Filtered publication starts at the instances marked {attribute 'OPC.UA.DA' := '1'} and their inherited children, so a composition root’s private instances — part carrier, I/O driver, recipe catalogue, config store, access provider, HAL structs, simulation controls — are simply not there. ADS has no such filter: SYM_UPLOAD exposes the whole program, so a direct client that scopes discovery by program prefix reads all of it, at the cyclic rate, for data no view renders and no OPC UA client can see. Two rules restore parity, both applied before tier classification:

  • Outside the published roots. A path under a program container that owns a discovered root Unit, but outside every such root, is off-contract: excluded from the cyclic read and never given an activation scope. The containers are derived from the discovered roots rather than matched against the name MAIN, so this holds for any program name and for a peer forest (Core §3.1a). Before any root is discovered nothing is outside them — the first snapshot is how the roots become known.
  • Manifest-served containers. A subtree the PLC marks OPC.UA.DA := '0' and M_AppendConfig re-serves under the same browse path is excluded from the cyclic read; the manifest overlay supplies it before the mapper runs. This is the container half of the config tier. The leaf half stays cyclic: leaf names such as Name and ModuleType also occur on live structs, and a classifier cannot tell those apart from the path alone.

Discovery still enumerates excluded leaves, so they remain writable by path — which is what the §10.5.1 fieldbus demand gate needs. Over OPC UA and the gateway both rules are inert, because those paths are unpublished and never reach the classifier.

On-demand data is grouped by activation scope: a module’s drill-down data scopes to its owning root Unit’s browse base; the fieldbus tree shares a reserved scope. PlcRepository.setModuleDetailActive(rootPath, bool) and setFieldbusViewActive(bool) gate them — AppState activates the selected root’s scope while a module detail is shown, and the fieldbus page activates its scope on mount/dispose. Sim treats both as no-ops; direct and gateway clients apply the same classifier and view demand.

The optional containers set on setModuleDetailActive narrows the active root to the selected tab’s visible, access-permitted cards. Null preserves the whole scope for older callers; an empty set requests no detail. Sequence rows belong to Sequence, event rings to Events/history, and cycle tables to cycle analysis; parameter-set replies remain explicit post-request reads. Child command timing belongs to the owning root’s scope. Authored controls derive their demand from tag bindings, including visibility/rotation conditions. Closing a view or changing its demand discards pending replies for that demand. With a declared freshness envelope and a tiered client, demanded leaves move from excluded to slow. Complete snapshots renew the consumed native records on the declared heartbeat, avoiding repeated targeted leaf sweeps that can exceed the Good window under concurrent load. Closing a view excludes its leaves again. Tier updates are serialized with disjoint slow/excluded lists. Source ages and quality remain authoritative; expired detail still becomes unavailable. A non-tiered client keeps successful bounded detail sweeps on its own slow-period cadence, without an extra complete-poll gap. Each batch retains its own read-start age; no detail reply renews station health or another batch.

Targeted readValues requests may set includeDataValues: true. A supporting gateway returns protocol: fraktal.opcua.read-values.v1, values, and dataValues with each requested leaf’s original quality, timestamp and age. The AB gateway can reuse a Good native record while its age is within the slow period; otherwise it refreshes the requested group. Reuse changes no source timestamp or complete-station health. Clients add local RPC/processing time to the returned age. Scalar-only gateways retain their fresh targeted-read behavior and remain compatible; unknown envelope versions are refused. Partial control ACKs have their own acquisition quality/age and cannot renew station health.

Gateway parity status. The gateway preserves discovery, the config manifest, mailbox ordering/acknowledgement, root scoping, PLC-side access checks, and the same HMI-owned tier classifier as direct clients. Its bounded discoverPaths, setReadTiers, and readValues operations make Web cyclic traffic proportional to the consumed fast surface after the one-time bootstrap. Production acceptance shall still measure a representative large forest through the packaged gateway; source/protocol parity is not latency evidence for a particular IPC or TF6100 configuration.

Why this shape. The bounded history/trend arrays and the per-module safety/power facets otherwise dominate the cyclic read (thousands of nodes) and make TF6100 grow its ADS handle pool each poll (AdsIncreaseDynSymPool, a 0x00000710 handle burst), which stalls the single native worker isolate and delays interactive commands — measured mode-change latency dropped from ~1.1 s median to ~50 ms once the fast tier shrank from ~6.9k to ~2.7k nodes. Interactive mailbox commands also mark the repository busy so the periodic refresh yields the worker to the command’s small acknowledgement reads (Core §14). The manifest’s fieldbus topology base is resolved from the discovered path set (its live members are on-demand and absent from cyclic values).

OPC UA does not call IEC methods. Every root Unit publishes one HmiRequest : ST_HmiRequest input and one HmiResponse : ST_HmiResponse output. The client writes all request arguments first and writes Sequence last. The Unit consumes each new sequence once, invokes the same gated methods used by PLC callers, clears Secret, then publishes AckSequence last.

This commit marker prevents a scan from consuming a mixture of old and new arguments and gives native and gateway clients identical acknowledged writes. The HMI seeds its next sequence from the published request/ack values on every application start. It reserves the sequence before attempting the batch, so an ambiguous disconnect can never cause that command number to be reused.

E_HmiRequestKind is append-only across PLC and HMI. Core 0.3.0.0 appended LAMP_TEST := 26; it carries no arbitrary output path or duration. The Unit base rechecks MANUAL authorization and idle state, starts its configured bounded semantic tower test, and acknowledges the exact sequence. A client never writes individual lamp/horn members.

Core 0.4.0.0 also publishes each Unit’s HostEvents object as a bounded ring (Ring, RingHead, Count, Capacity, Wrapped). It is read-only, event-produced PLC data—not a command surface—and its ring belongs to the on-demand tier. Clients derive traversal from the published Capacity, whose current TC3 binding value is 32. E_HostEventKind is append-only and ordinal-identical in PLC and HMI. A north-bound client uses Sequence for ordering and must retain TimeSynchronized, Verdict, and ReasonCode rather than flattening quality or result semantics.


Built from Specification/OPCUA_TRANSPORT.md at revision a1163c7 of the Fraktal repository.