Fraktal Core — Modular Automation Architecture (Part I)

Unified PLC Programming Standard · Part I: platform-neutral normative core

Status: Draft · Part I of III (Part II: the TwinCAT 3 binding, Fraktal/TC3; Part III: the Allen-Bradley Logix binding, Fraktal/AB, draft/R0-complete/spike-ready) Platform: none — this Part is platform-neutral. Platform-specific clauses live in binding Parts (Part II: TwinCAT 3; Part III: Allen-Bradley Logix). Grounded in: ISA-88 / IEC 61512 (physical & procedural model), PLCopen (command-handshake vocabulary, motion & safety function blocks), ISA-TR88.00.02 PackML / OPC 30050 (optional overlay), ISA-95 / IEC 62264 (MES integration), ISA-18.2 / IEC 62682 (alarm management), IEC 62443 (cybersecurity), and OPC UA / IEC 62541 companion models — reconciled into a single recursive-module architecture.

Normative language: shall/must = requirement · should = recommendation · may = permitted · can = possible. This document is Part I (Core): Foreword and environment requirements (§1–2), the architecture and coding core (§3–8), and safety principles, I/O abstraction & motion model, connectivity mappings, worked-example index, change management, and cybersecurity (§9–14). Platform mechanics are cited as TC3 §x.y (Fraktal_TC3_Part_II.md) or AB §x.y (Fraktal_AB_Part_III.md); Core section numbering is preserved across bindings where applicable.


Description. This standard defines a single, unified way to write equipment software for the production line — defined platform-neutrally and delivered first as its TwinCAT 3 binding (O8). It synthesises established industry practice — the ISA-88 (IEC 61512) physical/procedural architecture with disciplined alarm (ISA-18.2), safety, and naming rules, and a proven object/handler framework of coding conventions — into one recursive three-tier module model (FB_Unit / FB_EquipmentModule / FB_ControlModule). Every module shares one data contract, one PLCopen command handshake, and one diagnostic model, and the whole station describes itself through the transport-neutral Fraktal Self-Description Service (§3.10/§11) so a single generic Flutter HMI can render and navigate it without per-station screen building.

Concept. The standard is organised around one intention: bring a machine into service with as little application programming as possible, so that what remains to be written is the part that is genuinely specific to that machine.

  • Equipment is composed, not written. A station is assembled from reusable module types, each of which ships with its own tests, its own reason-code band, and its own published contract. A type is declared and wired once (§3.11); it is then finished.
  • Everything common is reused, not repeated. The command handshake (§6.1), mode and state machines (§6.2), first-out diagnosis (§6.9), the alarm model (§8), recipe load and migration (§3.8), traceability (§3.16), and the published data contract (§3.12) are defined once at the level that owns them. A concrete type supplies its device logic and declared lifecycle extensions, and nothing else (§2.2, §3.14). A binding may enforce that reuse through inheritance or through generated composition, but a project never re-implements the lifecycle.
  • The operator interface is discovered, not engineered — and not generated. Because every module publishes the same self-describing contract (§3.10), a generic HMI walks the live forest at run time and renders the tree, its commands, its alarms and its flow charts (§3.13). Adding a module makes it appear. A binding may generate the controller-side manifest or exposure metadata from the same authoritative declaration, but there is no separately hand-maintained per-station HMI artifact to regenerate, redeploy, or keep synchronised when the machine changes.
  • What the application author writes is the step sequence — the process itself — in whichever of ST, SFC or Ladder suits the author and the site (§5.5, §6.8), all three implementing the same sequence contract through the binding’s proved execution form.

The effort model that follows from this is stated in O1 and made normative by the trimming rule below: standardisation is paid once per reusable module type, and once per framework mechanism — never once per step, per station, or per screen.

Technology baseline. The Core assumes a deterministic cyclic PLC environment capable of the bounded records and state machines defined here, a transport-neutral Fraktal Self-Description Service (§3.10, §11), a generic operator HMI that auto-discovers the module forest (§3.13), and pluggable recipe/type transports — local, OPC UA, socket (JSON/XML), REST, or a binding-defined equivalent (§3.8). It does not require IEC object-oriented extensions or a particular connectivity transport. Each binding declares its concrete technology baseline — toolchain, language mechanisms, fieldbus, safety system, self-description transport, and optional industry projections — in its own Part (TC3 §1, AB §1).

Deliverables. This standard (§1–13), the worked-example annex set A–I (§12) exercising every contract end-to-end, and a two-page quick-start (“your first module”: scaffold from the binding’s §2.2 lifecycle form, wire, test to the §5.7 checklist) with the Annex C chain also rendered in SFC (§6.8). The original core trio: three worked-example annexes that exercise every contract end-to-end and serve as reference implementations: a Control Module (Annex A — separator/stopper), an Equipment Module (Annex B — dual clamp with parent-child rollup), and a Unit (Annex C — station with a continuous mode chain, mode cascade, and the cross-tier stall diagnostic). Each binding supplies the framework artifacts those examples assume (§2.2).

Objectives (in priority order):

  1. Low development and maintenance effort. Application logic stays lean — issue a command, wait for Done — with no per-step boilerplate. Standardisation is paid once per reusable module type, not once per step (§6.9); and a change to a shared contract, diagnostic, or transport is made once at the owning level and reused everywhere through the binding’s enforced mechanism, so the cost of evolving a fleet stays bounded as it grows rather than scaling with the number of modules or stations.
  2. Easy to learn from any background. SFC is the default, but sequences, interlocks, and conditions may also be written in ST or Ladder (§5.5); names follow the widely-known PLCopen convention (§6.1) so the interface feels native to programmers from any platform.
  3. Diagnosable by construction. When a sequence stalls, the operator always gets a precise root cause — “Step N stalled → awaiting Module.Command → reason” — produced automatically from the module contract, with no hand-coded per-step conditions (§6.9, §8).
  4. Reusable, recursive, and scalable. One module model scales structurally from a single device to the whole station; recurring assemblies are packaged as types and dropped in anywhere with a fresh mapping (§3.11). Scalability is also a runtime and deployment property: a station’s published surface, discovery cost, and connectivity traffic should stay proportional to the data actually consumed, so a large forest does not degrade the HMI, MES, or server — data that is static, historical, or view-specific may be served on a lower cadence or on demand rather than continuously, without changing the module contract (§3.10, §11).
  5. Flexible data & connectivity. Recipe/type data may be local or fetched over OPC UA, socket (JSON/XML), REST, or another binding-defined provider behind one logical provider contract (§3.8); the HMI and MES consume the Fraktal Self-Description Service generically through the selected binding transport (§3.10, §11).
  6. Simulatable. Every module runs unchanged against simulated or real I/O through the HAL, enabling virtual commissioning before hardware exists (§2.6, §10).
  7. Safe. Safety lives in the certified safety system; application code consumes safety state read-only and never bypasses it (§9).
  8. Portable. The normative model — tiers, contracts, state machines, diagnostics, routing — is platform-neutral; each PLC platform is served by a binding that maps the model onto that platform’s language extensions and services. TwinCAT 3 is the first binding and Allen-Bradley Logix the draft second binding; platform clauses are tagged [TC3] or [AB]. The standard is named Fraktal — one contract, self-similar at every tier — with the platform-neutral core designated Fraktal Core and each binding Fraktal/⟨platform⟩ (Fraktal/TC3, Fraktal/AB; future: Fraktal/TIA). Conformance claims compose as “Fraktal Core + Fraktal/⟨binding⟩ (+ binding-qualified profiles)” (for example Fraktal Core + Fraktal/TC3 + Robot or Fraktal Core + Fraktal/AB). Fraktal is published as an open-source project in the MrFrakt/Fraktal monorepo.
  9. Good coding and engineering practice. The preceding objectives are upheld through disciplined coding and engineering practice, which the standard treats as a first-class goal rather than a matter of individual style. Every fact — a contract member, a reason code, a diagnostic, a piece of configuration — has one authoritative source and is derived, never duplicated (§4.8, §8.8, §3.8); behaviour is written once at the level that owns it and reused through a binding mechanism that prevents project duplication, so concrete types add device logic only (§2.2, §3.14). Public capability contracts expose the minimum surface needed and no more (§3.2, §3.13); changes to a released type are additive and versioned, never silently breaking a consumer or a stored recipe (§1.5, §3.8). Machine-verifiable rules — naming, contract usage, lifecycle ordering, step/condition records, per-type tests — are enforced by a CI/lint gate on every commit (§1.5, §5.5, §6.8) so conformance is continuous, not a review-time hope. New code should follow the idioms and structure of the code around it, keeping the codebase legible to any engineer from any binding. This objective is cross-cutting: it names explicitly the practices the other objectives assume, so that scalability and maintainability survive as the standard and its fleets grow.
  10. Industrial-grade robustness. The framework is built to the reliability expected of production equipment software, not of a demonstrator. Every command, recipe payload, and external input is validated before use, and every behaviour-selection path has a defined fail-safe fallback — never a silent default or a stall (§5.6); bounded, statically-sized structures (fixed rings, no run-time allocation on the scan) keep timing and memory deterministic (§8.3, §8.11); faults fail closed and are never masked, and a lost transport or connection queues nothing and resumes cleanly rather than replaying stale actions (§7.8, §11, §14). The reference implementations are held to the same bar — warning-clean builds, green per-type tests against the simulated HAL before release (§1.5, §5.7), and honest status reporting that distinguishes proven behaviour from deferred work. Robustness is a shall wherever safety, data integrity, or command acceptance is at stake, so a Fraktal station behaves predictably under load, fault, and recovery in a real plant.

O1 in practice — the trimming rule. O1 is not satisfied by documenting repeated project work; it is satisfied by removing it. Whenever the same wiring, latch, reset, or per-scan call has to be written in more than one project sequence, module, or Unit, that repetition shall be treated as a framework defect and absorbed into the binding’s owning framework/generator mechanism — even when absorbing it makes that mechanism materially more complex. The cost is paid once by the standard’s implementers; the saving recurs in every station, forever. Two consequences follow, and both are normative:

  • A project shall never be required to remember a call for correctness. If forgetting a call yields a wrong or intermittent result — a stale transition result, a latch that never re-arms, an unreset sub-chain — the call belongs in the framework, driven from a path the application already takes (attach, cyclic, step change). An obligation a project can forget is a defect the framework chose not to fix.
  • Repeated glue is measured, not judged. “More than once” is the threshold. The reference implementation absorbed the composite sub-chain pattern after it appeared four times at eight lines each, and the per-scan chain reset before it could appear even once in a project.

This rule is what keeps the effort model honest: standardisation is paid once per reusable module type (and once per framework mechanism), never once per station.

Non-goals. The standard deliberately does not mandate PackML (it is an optional overlay, §6.6), does not tightly standardise step bodies the way heavily templated step-body standards do (that verbosity, slow to write and error-prone, is precisely what this standard sets out to avoid), and does not lock sequence authoring to a single language.

Platform-tagging convention (O8). Binding-specific clauses carry their binding tag and live in that binding Part: [TC3] in Part II (Fraktal_TC3_Part_II.md), [AB] in Part III (Fraktal_AB_Part_III.md). Compiler pragmas/attributes, REF=/__QUERYINTERFACE, FB_init ordering, TF6100/TwinSAFE services, Logix AOI/UDT/L5X mechanics, CIP access, and gateway mechanics therefore do not become Core requirements. Where a binding fragment is inseparable from an otherwise-neutral Core example, it may remain here only with its tag and a pointer to the owning binding clause. Untagged normative text is platform-neutral Core; another platform implements its own binding Part without changing Core. All new platform-specific normative text shall land in its binding Part.

This Part defines, platform-neutrally, how PLC application software is structured, named, sequenced, interlocked, alarmed, and exposed for equipment delivered into the production line; the platform is fixed by the binding in use (Part II — TwinCAT 3, TC3 §1; Part III — Allen-Bradley Logix, AB §1). It applies to all equipment suppliers and to in-house controls work for the site. A project-specific specification may add to this standard and, only where explicitly agreed in writing, supersede a part of it.

Equipment suppliers’ PLC programmers, controls engineers, and commissioning and maintenance personnel. Readers are assumed competent in IEC 61131-3 and in the selected binding platform (for example TwinCAT 3 for Fraktal/TC3 or Studio 5000 Logix Designer for Fraktal/AB).

This standard is grounded in publicly available standards, not a proprietary lineage: the ISA-88 / IEC 61512 physical and procedural model gives the tier architecture (§3.1); PLCopen supplies the command-handshake vocabulary (§6.1) and the motion (§10.6) and safety (§9.7) function-block sets; ISA-TR88.00.02 (PackML) with its OPC UA companion OPC 30050 is supported as an optional overlay (§6.6, §11.7); ISA-95 / IEC 62264 shapes MES integration (§11.6); ISA-18.2 / IEC 62682 govern alarm rationalization (§8.9–§8.10); IEC 62443 frames cybersecurity (§14); and OPC UA (IEC 62541) with its companion models — Machinery (OPC 40001), PackML (OPC 30050), Energy (OPC 34100), AAS/MTP, FX — supplies one binding transport and several optional industry projections (§3.10, §11). Where common industry practices diverge, the resolution is recorded in the relevant section — variable prefixing (§4.4), flow control and the lean-vs-diagnosable trade-off (§6), PackML made optional (§6.6), and the language policy (§5.5).

  • A project conforms when every shall requirement is met. Should items are strongly recommended; departures should be justified in the project documentation.

  • Any deviation from a shall requirement shall be approved in writing by the site’s controls engineering before deployment, and logged (§13).

  • A CI/lint gate (§5.5, §6.8) shall check the machine-verifiable requirements — naming, step records, condition records, and contract usage — on every commit.

  • Each reusable module type shall ship an automated test suite (§5.7) that runs in CI against simulation and covers its handshake, first-out diagnostics, and interlocks; the suite shall be green before the type is released or changed.

  • Module-type versioning. Released types follow semantic versioning: major = any change to the contract surface (commands, handshake members, ParCfg schema, reason codes, SourcePath semantics — anything a consumer or a stored recipe can observe); minor = additive members/commands with defaults preserving old behaviour; patch = internal fixes with no observable change. A major bump shall ship the §3.8 recipe migration for its SchemaVersion step, and consumers pin versions per §2.2/§5.4 — so “reusable library” is a compatibility promise, not a hope.

  • Binding-qualified projections. Core behavior-profile conformance is transport-independent. A claim for a transport or companion-model projection (for example Fraktal/TC3 + PackML/OPC UA) is additionally qualified by the selected binding and may be made only when that binding maps and verifies the projection. Absence of an optional projection does not invalidate base Fraktal Core conformance.

  • Optional Line profile. Line config (§3.8e) and shifts (§8.5.2) form the Line behaviour profile, claimed per binding like Robot (§10.6): Fraktal Core + Fraktal/TC3 + Line. They describe a line of stations sharing one owner, which a single-station cell does not have, so base Fraktal Core conformance does not require them. A binding that claims the profile binds both clauses whole; one that does not claim it shall not publish partial line config or shift statistics, and clients shall treat their absence as “no line” rather than as a fault.

Term Meaning
Unit (FB_Unit) Recursive mode-owning module (the ModeHandler role, §3.1). A Unit with no parent is a root Unit (§3.1a); a program may have several, one per station/conveyor/sub-line, forming a forest.
Station The independently controlled operational scope represented by one root Unit.
PLC / cell scope One PLC program and Self-Description Service endpoint hosting the module forest: one or more peer stations/root Units plus shared system services.
Equipment Module / EM (FB_EquipmentModule) Discrete-command module (the CommandHandler role, §3.1).
Control Module / CM (FB_ControlModule) Hardware-bound leaf module (one HAL channel).
HAL Hardware-Abstraction Layer between CM logic and the I/O driver; enables simulation.
Hardware Driver Lowest layer that talks to physical I/O; carries the SIM toggle.
PermIntlk Standard permissive/interlock container with per-condition description + reason code.
Recipe / Type data Parameter set shaping module behaviour (ParCfg); source is pluggable (§3.8).
ExecState Derived command/module state: READY/BUSY/DONE/ERROR/ABORTED.
ParCfg/ParCmd/OutCmd/OutImm The four-structure object data contract (§3.12).
OEE / MES / HMI / SCADA Overall-Equipment-Effectiveness / Manufacturing-Execution-System / Human-Machine-Interface / Supervisory-Control-And-Data-Acquisition.
Fraktal Self-Description Service Transport-neutral live discovery, typed-value, quality/freshness, bounded-read, and acknowledged-mutation contract of §3.10/§11.
OPC UA OPC Unified Architecture — a permitted binding transport and optional companion-model projection. Fraktal/TC3 uses TF6100 (TC3 §3.10/§11.1); Fraktal/AB defaults to EtherNet/IP plus the Fraktal gateway (AB §1/§11).
Safety system The certified functional-safety platform of the binding (§9.1); Fraktal/TC3: TwinSAFE/FSoE (TC3 §1, TC3 §9).
SFC / LD / ST / FBD / CFC IEC 61131-3 languages: Sequential Function Chart / Ladder / Structured Text / Function Block Diagram / Continuous Function Chart.
Capability study (Cmk/Cpk) Repeated-cycle measurement run assessing machine/process capability; the CAPABILITY mode (§3.17).
Data carrier / RFID Part-bound data tag read/written via I_PartCarrier (§3.16).
Heartbeat / link supervision Periodic liveness check on an external device link, with a defined loss reaction (§3.15).
PackML / PackTags OMAC machine-state model (ISA-TR88.00.02; OPC UA companion OPC 30050) and its Command/Status/Administration tag groups (§11.7).
ISA-95 / ISA-88 IEC 62264 enterprise-control (MES) integration / IEC 61512 batch & procedural models (§11.6).
AAS / MTP Asset Administration Shell (IEC 63278) / Module Type Package (VDI/VDE/NAMUR 2658, IEC 63280) — vendor-neutral module descriptions (§11.8).
UNS / MQTT / Sparkplug Unified Namespace / lightweight broker protocol / its birth-death payload spec, for north-bound telemetry (§11.9).
PTP / NTP IEEE 1588 Precision Time Protocol / Network Time Protocol — station clock-sync sources (§2.7).
PLCopen Motion / Safety Standard MC_* motion and SF_* safety function-block sets (§10.6, §9.7).
IEC 62443 Industrial-automation cybersecurity standard: zones/conduits and security levels SL 0–4 (§14).
ISA-18.2 / IEC 62682 Alarm-management lifecycle & rationalization standards (§8.9–§8.10).

2. Development & Runtime Environment (platform-neutral requirements)

Section titled “2. Development & Runtime Environment (platform-neutral requirements)”

The toolchain-and-versions and project-and-solution-settings clauses are binding-level — see TC3 §2.1/§2.4 and AB §2.1/§2.4. The requirements below are platform-neutral and bind every implementation regardless of platform. One neutral toolchain rule is retained here:

  • The build shall be warning-clean before release; shall-level compiler/lint findings are treated as errors. Exact toolchain builds shall be pinned per project and recorded (mechanics per binding, TC3 §2.1 / AB §2.1).
  • System, framework, and vendor libraries shall be referenced by pinned version with their dependencies; local or relative library references are not permitted (§5.4). Reference/distribution mechanics are binding-owned (TC3 §2.2 / AB §2.2).

  • The framework distribution — module contracts, capability surfaces, the step-chain mechanism, permissive/interlock records, alarm/diagnostic handlers, and Self-Description Service exposure — is versioned centrally. Projects consume a pinned release, never a copy.

  • Single lifecycle authority (O1). The binding framework shall implement the §6.1 lifecycle once: Execute edge, state/output mapping, Execute-drop reset, ErrorID, abort routing, status publication, command timing, and recipe-transaction defaults. Its composite mechanism adds child registration, recursive recipe handling, and diagnostic rollup without assigning a tier; its tier forms add only Unit/EM/CM obligations, so a Unit never acquires Equipment-Module identity by implementation accident. A concrete type shall supply only its device/sequence dispatch and explicitly declared §3.14 extensions; it shall not re-implement lifecycle-owned behavior or write lifecycle-owned state directly.

    Every binding shall define one non-optional cyclic execution path with this order: reset a previously published command-terminal state when §6.1’s Execute-drop rule permits it, then sample/accept a new command edge; run one-shot initialization and accepted-command-start extensions; run cyclic management and child/rollup work; route abort/error-abort handling; run concrete device or sequence dispatch only while BUSY; resolve HELD, timing, terminal outputs, diagnostics, and the published status mirror; then release any framework-owned one-shot request for the next scan. The exact placement of a documented tier-specific derivation may vary only when the binding proves identical observable Core behavior. The mechanism may be inheritance (TC3 §2.2/§3.14) or generated composition (AB §3.14), but it shall make the required calls/order machine-checkable and shall not leave a project author to remember correctness wiring. Rows T1/T4 and the shared T2/T6 mechanisms are proven once at this owning lifecycle implementation (§5.7); generated-composition bindings additionally prove that every concrete type includes it. Expanded annex forms remain pedagogical only.

  • One primary cyclic PlcTask runs MAIN and the module tree (§4.2). Its cycle time and watchdog shall be sized for worst-case load with margin and recorded.
  • Additional tasks (fast I/O, comms) require controls-engineering approval and shall not share state with the primary task except through documented, lock-free exchange.
  • Blocking or long-running work — recipe fetch over OPC UA/REST/socket (§3.8), file or database access — shall run asynchronously and never stall the cyclic task.
  • The project shall be held in text-diffable form under version control; binary-only storage is not acceptable. Storage forms are binding-owned ([TC3]: TC3 §2.5; [AB]: AB §2.5).
  • One repository per solution/line as agreed; the pinned framework-library release is referenced rather than vendored where the tooling allows.
  • Commits are gated by the CI/lint checks of §1.5.
  • Every Control Module shall be runnable against a simulated Hardware Driver (DI/DO/Motor SIM, §3.6), selected by configuration, with no change to module logic.
  • Simulation supports both local PLC test and external virtual commissioning (e.g. Process Simulate). The same ParCfg, handshake, and diagnostic contracts apply in simulation and on real hardware, so a sequence validated in sim behaves identically on the line.

Every timestamp the standard produces — the ST_Diagnostic.Since first-out time (§8.8), alarm queue entries (§8.3), traceability records (§3.16), and host events (§11.6) — is only as trustworthy as the controller clock behind it. A station shall therefore derive its clock from a synchronized source, not the free-running IPC clock.

  • PTP (IEEE 1588) is the primary source. Where the network and devices support it, the station clock shall be disciplined by PTP — over the fieldbus’s distributed-clock mechanism and over network PTP for the controller ([TC3] mechanics: TC3 §2.7). NTP may be used as a fallback where PTP is unavailable; the chosen source shall be documented per station.
  • One clock feeds all timestamps. Diagnostic, alarm, traceability, and host-event timestamps shall read the synchronized clock so that PLC, HMI, historian, and MES share a single, comparable time base (this is the precondition that makes first-out ordering across tiers and across stations meaningful).
  • Loss of sync is a System alarm. If the clock loses its sync source beyond a configured tolerance, the station shall raise a System-category alarm with ReasonCode := E_Reason.TIME_SYNC_LOST (§8.6, §8.8) and shall flag subsequently generated timestamps as unsynchronized, rather than silently emitting drifting times.

Clock confidence is published once as ST_TimeQuality := {Available, Synchronized, Source, OffsetUs, LastSyncAt, ObservedAt}. Available=FALSE is not a healthy zero and shall never be interpreted as synchronized. Every timestamp-bearing framework record appends a quality Boolean owned by that timestamp: ST_Diagnostic.TimeSynchronized, the come/gone/reset/shelf flags on ST_AlarmEvent, ST_PartResult.TimeSynchronized, and StartedTimeSynchronized on cycle/step records. The time value remains present for forensic ordering when quality is false; clients shall mark it untrusted rather than discard or silently present it as synchronized.

Cross-references: §8.3/§8.8 (timestamps), §3.16 (traceability), §11.6 (host events), §10.1 / TC3 §2.7 (fieldbus distributed clocks).


The application is built from exactly three function-block archetypes arranged as recursive trees. Each tree’s root represents one independently controlled station; a PLC/cell scope may host several peer roots as a forest (§3.1a). The leaves bind to physical hardware. The tiers map onto ISA-88 (IEC 61512) names and onto two handler behaviours:

§3.1a Roots & the forest. The topmost Units — those with no parent — are root Units; a program may run one or more (§4.2). They are independent peers (own mode, cycle, model, rollup); the set of roots and their sub-trees is the module forest.

§3.1b Root model identity. A root Unit shall expose an active model identity — at minimum a ModelCode : STRING, and optionally Family, Variant, and a fixed-size list of client-defined named fields (ST_ModelId, §3.8a) — describing what it is currently set up to produce. Because roots are independent, two roots may carry different model identities at the same time (one station running model A while another runs model B on the same PLC). The identity is what a changeover (§3.8) sets: selecting a model resolves, through the recipe provider, the ParCfg of every module beneath that root — so ModelId is the key, and the per-module ParCfg values are the resolved data. The identity is published for the HMI and MES (§3.13, §11.6) and is part of every traceability record (§3.16) so a part is stamped with the model that produced it. A non-production or single-product cell may leave Family/Variant/fields empty and use a constant ModelCode.

Tier Type ISA-88 Behaviour (handler role)
Top (recursive) FB_Unit Unit ModeHandler — runs a continuous mode sequence from Start until Stop; owns mode and the station state machine.
Middle FB_EquipmentModule Equipment Module CommandHandler — exposes discrete commands, individually triggerable (incl. manually in Manual mode).
Leaf FB_ControlModule Control Module Hardware-bound device (cylinder, valve, sensor, drive). One HAL channel.

A FB_Unit may nest inside another FB_Unit; the recursion is what lets a single type scale from a fixture to the entire station. Strict ISA-88 would insert a non-recursive Process Cell above Unit — this standard collapses Process Cell into a recursive FB_Unit as a deliberate, documented extension. The top-most FB_Unit instance plays the station/Process-Cell role.

3.2 Type catalogue and capability surfaces

Section titled “3.2 Type catalogue and capability surfaces”

Every archetype provides the logical base capability I_Module, which carries everything a parent needs to discover, monitor, roll up, and re-recipe a child regardless of tier. The I_* names below are Core capability-contract names, not a requirement that a binding implement an IEC interface, method, property, pointer, or dynamic dispatch. A binding may realize them with language interfaces (TC3 §3.2) or with generated records, bounded registries, and typed operations (AB §3.2), provided the same behavior and minimum surface are available.

capability I_Module
Name, ModuleType // canonical identity and UNIT | EM | CM (§4.8)
State, FaultActive // derived state summary
GetFaultSummary() -> ST_Diagnostic // first-out of this node + descendants (§8.2/§8.8)
PrepareRecipe(Model) -> BOOL // validate/load staging only
CommitRecipe() // bounded, infallible active-data swap
AbortRecipe() // discard staging
Cyclic() -> BOOL // one required lifecycle invocation
capability I_Unit includes I_Module
ModeActive
SetMode(Mode) -> BOOL; Start() -> BOOL; Stop() -> BOOL
capability I_EquipmentModule includes I_Module
ExecuteCommand(Command : DINT) -> BOOL; AbortCommand() -> BOOL
capability I_ControlModule includes I_Module
ExecuteCommand(Command : DINT) -> BOOL; AbortCommand() -> BOOL

Two deliberate omissions keep this surface implementable and single-sourced: it carries no numeric ErrorID—the number lives only on the PLCopen output (§6.1)—and the fault summary is the ST_Diagnostic of §8.8. The recipe transaction is on the base capability because changeover must prepare, commit, or abort every descendant through one generic surface (O4).

Generic command ids are the enum’s numeric value (DINT), and the operations are named ExecuteCommand/AbortCommand. A per-type E_<Type>Command cannot appear in a shared capability surface. The typed enum remains the primary surface (the Command input every step chain and HMI catalogue use); the generic operations let one logical contract serve every type ever written (O4), and an implementation shall validate the received value against its command set, rejecting out-of-range values with a ReasonCode per §5.6.

Every module additionally publishes the PLCopen signal set (Execute, Busy, Done, Error, ErrorID, Abort, Aborted, §6.1) as data for hand-written step code and the Self-Description Service; State is the single derived summary of those signals.

A composite owns a bounded child collection through binding-defined validated handles and resolves tier capabilities for a common walk. Conceptually:

for each child in Children
if Supports(child, I_Unit)
SetMode(child, ModeActive)
end_if
end_for

The collection, capability lookup, and calls shall be bounded, fail closed for an invalid handle/capability, and preserve the same canonical child identity. TC3 binds this to an interface array and __QUERYINTERFACE (TC3 §3.2); AB binds it to generated registry indices and capability bits (AB §3.2). Neither representation changes the containment or rollup contract.

Container May contain Must not contain
FB_Unit FB_Unit, FB_EquipmentModule, FB_ControlModule —
FB_EquipmentModule FB_ControlModule, nested FB_EquipmentModule FB_Unit
FB_ControlModule — (leaf) anything

The single prohibition — no FB_Unit inside a FB_EquipmentModule — structurally enforces the rule that a continuous mode-runner can never be subordinate to a discrete command-handler. A reviewer or a CI check can verify this by walking the instance tree and asserting no I_Unit is reachable through an I_EquipmentModule.

A FB_Unit owns a mode and runs a continuous sequence for that mode. Standard modes:

Mode (E_Mode) Purpose
AUTO Normal production sequence; runs continuously between Start and Stop.
MANUAL Operator triggers individual EM/CM commands; no automatic sequence.
CHANGEOVER Type/recipe change, guided sequence.
CALIBRATION Calibration/reference runs.
HOME Move to defined home/output position.

The mode sequence is started by Start (operator or parent) and runs until Stop is requested internally or by the operator/parent — it does not “complete and exit” the way an EM command does. The sequence body is the continuous SFC step chain of §6.2, built from the command handshake of §6.1.

A Unit shall reject a SetMode for a mode it does not implement (returns FALSE); the caller — including a parent Unit cascading mode — must handle rejection gracefully (§3.7).

Sequence source layout. A concrete Unit implementing more than one sequenced mode shall keep _M_Dispatch as a thin mode router and place each sequence in an explicitly named implementation unit (_M_SequenceAuto, _M_SequenceHome, _M_SequenceChangeover, or the equivalent SFC/LD/FBD POU). AUTO, HOME, and CHANGEOVER shall not be hidden as unrelated step-number ranges inside one monolithic dispatcher. This is a source-organization requirement, not a second lifecycle: every sequence still runs through the owning Unit lifecycle, the binding’s step token/record service, and PLCopen child handshakes.

Application ownership. A deployed Unit’s concrete mode chains are application engineering and shall be visible in that Unit’s project branch (§4.2). A reusable library may provide abstract helpers, reusable sub-sequences, or an opt-in generic default, but the application shall explicitly select it and retain an extension/replacement seam. A library implementation shall not silently make AUTO, HOME, CHANGEOVER, or other project modes opaque or final. The concrete project Unit may derive from a reusable base, compose reusable sequence helpers, or own the complete implementation directly.

3.4.1 Mode-switch policy while a sequence runs

Section titled “3.4.1 Mode-switch policy while a sequence runs”

Whether an operator may leave the current mode while its sequence is running is per-mode policy, held as station config (§3.8a) — not hardcoded — so a deployment tunes each mode’s protection. Two orthogonal axes describe every case:

  • Shield (E_ModeSwitchShield): INTERRUPTIBLE (switch proceeds), CONFIRM (the HMI shall prompt before switching), or BLOCKED_WHILE_RUNNING (SetMode returns FALSE while BUSY; the operator must Stop first).
  • Style (E_ModeSwitchStyle): GRACEFUL (request Stop, let the cycle finish at its stop point, then switch — reuses _stopReq/§8.11.1 and OnModeExit §3.14.4) or IMMEDIATE (cancel now via OnAbort, then switch).

The policy of the mode being left governs (that is the sequence at risk). MANUAL has no sequence, so leaving it is always free; entering any mode still requires _M_Supports (§3.7). Defaults: AUTO = CONFIRM+GRACEFUL; CHANGEOVER/CALIBRATION = BLOCKED_WHILE_RUNNING; HOME = INTERRUPTIBLE+IMMEDIATE. A SetMode refused by shield is not a fault — it returns FALSE and is surfaced (§3.13), like any graceful rejection.

A running mode advances under one of three run styles (E_RunStyle), an optional per-mode capability (a Unit advertises support like a mode): CONTINUOUS (default — free-running), SINGLE_STEP (the sequence pauses at each step boundary and advances one step per step request), and HOLD_TO_RUN (advances only while a run input is held). The sequence consults these at its §6.2 step boundaries via the base helper _M_StepGate(Steppable) — the sequence author marks step points; the base decides go/hold. Modes that don’t opt in run only CONTINUOUS.

Per-step stop points. _M_StepGate takes a Steppable flag, defaulting TRUE, so each step declares whether it is a valid stop point: a step with Steppable := FALSE runs straight through even in SINGLE_STEP or HOLD_TO_RUN (group several motions into one operator step, or protect a step that is unsafe to pause mid-way). Both stepping styles honour the flag identically. The default (TRUE) means every step is a stop point unless the author opts out — stepping “just works” without annotating every step.

Safety — HMI hold-to-run is not a dead-man. An HMI HOLD_TO_RUN button travels over the network (latency, no safety rating) and shall not be presented or relied upon as a safety enabling device. A real dead-man/enabling function is a monitored, safety-rated hardware device on the safety system (§9). HMI single-step/hold-to-run is a non-safety convenience for low-risk step-through only; interlocks (§7.2) still apply at every step regardless of run style.

A FB_EquipmentModule exposes a finite, named set of discrete commands (its per-type E_<Type>Command enum, §3.2) that orchestrate the primitive commands its Control Modules already provide. Each command:

  • shall be individually executable via Execute(Command), including manual triggering when the owning Unit is in MANUAL;
  • shall run as a bounded action (it completes, faults, or is aborted) — it is not a continuous mode loop;
  • shall not add device-level logic that belongs in a Control Module; an EM only sequences CM commands.

If an operation legitimately needs several CM actions in parallel, that is a signal to split the CMs across separate EMs for parallel orchestration, rather than overloading sequence branches.

A FB_ControlModule is the only tier bound to I/O, and it binds through the HAL, never to raw %I/%Q directly. The HAL is a data structure that sits between CM business logic and a hardware driver, so the CM can be exercised against either real I/O or a simulated driver (DI SIM / DO SIM / Motor SIM) without code change. Simulation is enabled at the driver, leaving the CM logic untouched — this is what allows virtual commissioning (e.g. Process Simulate) before hardware is available.

When a parent FB_Unit is Started, Stopped, or changes mode, each child FB_Unit shall follow only if the mode is available for that child:

for each child in Children
if Supports(child, I_Unit)
if not SetMode(child, RequestedMode)
Stop(child) // defined safe state; do not force an unsupported mode
SetEvent(EVENT_CHILD_MODE_UNSUPPORTED, Name(child))
end_if
end_if
end_for

A parent in CALIBRATION therefore never drags a child that has no calibration mode into an undefined state — the child is brought to a defined safe state and the condition is reported. EMs and CMs do not have modes; they respond to the commands the active mode sequence issues.

A FB_Unit (and, where useful, an FB_EquipmentModule) may expose a typed recipe/type structure. Recipe data:

  • shall land in the module’s ParCfg structure (§3.12) regardless of where it came from, so all downstream code is source-agnostic;
  • shall be versioned: every ParCfg (and serialized recipe record) carries SchemaVersion : UINT as its first member. During PrepareRecipe, the provider compares versions and either migrates into staging or rejects with RECIPE_INVALID; active data is never partially overwritten or guessed by field position. Adding a member is a schema change; external payloads carry the same version;
  • shall carry, for any measured value, its limit/target and a fixed engineering unit (units are not made variable at runtime);
  • shall load top-down through the module tree during CHANGEOVER.

Two kinds of persistent data, one placement rule (§3.8a). The standard distinguishes model/recipe data (varies per model — servo target positions, speeds, tolerances; resolved by ModelId at changeover) from station config (varies per deployment, not per model — the MES IP/port, a scanner’s baud, a scale’s calibration, a fixed endpoint). Both are persistent editable data, and both follow the same rule: each value lives in the module that needs it. A servo’s positions belong to the axis Control Module — or, at the programmer’s discretion, to the EM of an XYZ gantry that owns the three axes; the MES endpoint belongs to the host-interface module; a scanner’s config to the scanner CM. There is no central config blob. Concretely, a module holds its persistent values in its own ParCfg (model config, versioned per §3.8) and/or its own StationCfg (deployment data), both PERSISTENT. Read publication and write authority are distinct: an editable value shall be registered as an explicit typed write capability in the §3.10.2 manifest and changed only through the acknowledged root mailbox. Browsability or DATA_WRITE access alone never makes a value writable. Station config is not keyed by ModelId (it does not change at changeover) and shall not be bundled into a model recipe; a module that needs both simply declares both structures.

Source is pluggable. Recipe/type data shall not be assumed to be local. The source is selected per deployment via E_RecipeSource and supplied through one logical provider capability, so the same module works whether data is held in the PLC or fetched at runtime:

E_RecipeSource Transport Payload
LOCAL in-PLC PERSISTENT/ParCfg native struct
OPCUA OPC UA read/method from MES/SCADA structured nodes
SOCKET_JSON / SOCKET_XML TCP/UDP socket JSON / XML (or other)
REST HTTP client JSON over REST
capability I_RecipeProvider
Load(ModelCode, RecipeKey, staged target, declared size/schema) -> BOOL
Source : E_RecipeSource
Ready : BOOL

ModelCode is the product/model selected at the root; RecipeKey identifies the consuming module role/type. They are distinct parts of the lookup key. An empty ModelCode may be registered explicitly as a deployment default. The provider implementation is injected at configuration time; a conforming framework ships a working local provider by default. External payloads load only into staging and shall be complete, size-checked, and schema-valid.

Discoverable model catalog. A Unit may publish AvailableModelCount plus a bounded AvailableModels[] : ST_ModelId catalog. A finite local/project catalog should publish it so the generic HMI renders a validated selection rather than requiring free text. An external or effectively unbounded provider may leave the catalog empty; in that case the HMI may accept a model identity only if the PLC/provider validates it transactionally. The catalog is selection metadata—not a duplicate recipe store—and the active ParCfg remains the authoritative resolved recipe.

Every offered model is editable. A root’s own model config may be read and edited for any model its catalog lists, without a changeover. The root registers the record it resolves at changeover as its model region (address, size, RecipeKey, provider); every PAR_CFG capability stored inside that region is published with ModelScoped = TRUE. A configuration query or write then names a model by catalog index (0 = the active model, n = AvailableModels[n]): for another model the root loads that model’s record into a staging buffer through the ordinary Load, serves or edits the value there, and writes the record back through the provider’s optional I_RecipeStore.Save(ModelCode, RecipeKey, data, size) — the exact existing record, same size, same SchemaVersion, or refused. The active ParCfg is never touched by another model’s edit, and RequiresReady does not apply to a record that is not running. An edit of the active model is also saved back to its record, so a changeover away and back keeps it. A provider without I_RecipeStore (an external or read-only source) leaves every model but the active one read-only and active edits unsaved, as before. A child module’s ParCfg follows the active model only. An unknown index is refused with std.error.modelNotAvailable; a client shall send an index only with a value marked ModelScoped, because a controller that marks none reads every request as the active model. A query for any index but 0 answers with that model’s model-scoped values only: the rest of the manifest belongs to the running station and is served by index 0, and a client reading one model’s recipe shall not have to walk it.

Atomic changeover. SetModel first calls PrepareRecipe(Model) recursively. Validation, migration, provider I/O, and every fallible operation occur only in this phase. Any rejection calls AbortRecipe() and leaves every active ParCfg and the root identity unchanged. After every participant accepts, CommitRecipe() is an infallible, bounded in-memory publication at the scan boundary; it performs no validation or I/O. The root publishes the new ModelId only after commit. Station config is outside this transaction.

3.8b Persistence lifecycle and parameter sets

Section titled “3.8b Persistence lifecycle and parameter sets”

§3.8a says where an editable value lives; this section says what happens to it across a restart, and how a whole machine’s parametrization is saved, moved, and restored as one named thing. Both concern the same data: persistence is a lifecycle over the values §3.10.2 already publishes, never a second copy of them.

Storage stays distributed; the root is the authority, not the store. A parameter set is a projection produced by the same deterministic walk that builds the §3.10.2 manifest, keyed per value by (Scope, WriteKey). It is not a central blob and confers no ownership: a set is applied by replaying each record through the owning module’s typed handler, exactly as a single WRITE_CONFIG would be. A byte image of a station’s configuration — one aggregate structure memory-copied in and out — shall not be used. It reinterprets retained bytes silently when a type changes, carries no per-value identity for a file, database, ORM or MES to bind to, and cannot reject one bad value without rejecting all of them.

StationCfg is versioned exactly like ParCfg. Every StationCfg structure shall carry SchemaVersion : UINT as its first member. A retained image whose version is unrecognized shall initialize the module’s declared defaults exactly once and shall not be interpreted by field position. Version zero means never written: a first boot has lost nothing and initializes silently. Any other unrecognized version means a real image was rejected, and that shall be annunciated — the difference between an empty machine and one that has just lost its commissioning is exactly what an operator needs told. Adding a member is a schema change (§13).

Durability is a stated property, not a hope. An accepted configuration write shall reach non-volatile storage without further operator action, within a declared bounded window, and the root shall publish whether it has: PersistPending while any accepted write is not yet durable, PersistFailed when the store rejected or could not complete it. Transport acknowledgement and Accepted (§3.10(a″)) mean a value is live, not that it is durable. A station that cannot persist is a station that will silently revert at its next restart, and that shall be visible before the restart rather than discovered after it.

Restore is fail-closed and never silent. At startup a module runs on its restored values, or — if the restore is absent, unreadable, or schema-rejected — on its declared defaults with an event carrying the §8.8 reason code and the owning module’s canonical path. The deployment declares the consequence through E_ConfigRestorePolicy: DEFAULTS_AND_ANNUNCIATE (shipped default — the station runs and the annunciation stands until acknowledged) or BLOCK_UNTIL_ACKNOWLEDGED (no START_STOP release until an operator of at least ENGINEER level acknowledges the loss). Running on defaults while presenting itself as a commissioned machine is the failure this rule exists to prevent.

Named parameter sets. A root Unit may expose bounded set operations — save, load, and list — over named sets. A set carries the root’s canonical identity, the ConfigRev it was taken at, a set schema version, the creation timestamp on the synchronized clock (§2.7), and one record per registered write capability (Scope, WriteKey, ValueType, serialized value). Load is staged and all-or-nothing: every record is validated through its owning typed handler before any value changes, and one rejection aborts the whole load naming the offending (Scope, WriteKey). A half-applied machine parametrization is never a valid outcome. Records whose capability no longer exists in the target are reported, never silently dropped. Credentials (§7.7) are never included in a set.

Optional runtime model creation. A root may expose a bounded, PLC-owned catalog with ModelCapacity > 0. CREATE_MODEL appends a unique model code by cloning an existing model or a complete Model parameter set. The PLC shall validate source schema, every field’s type/range/read/write permissions and capacity before publishing the new entry. Creation requires CONFIG_SET, shall leave all existing indices and the running recipe unchanged, and may therefore run while the root is BUSY. The new model is activated only through the ordinary prepare/readiness/commit changeover path. Catalog/recipe retention follows the provider’s declared retention policy; download is a separate boundary. A missing or zero capacity means runtime creation is unavailable.

A root may also expose Features/ExportCurrentConfig. It takes an immutable, permission-checked snapshot of current configuration (or a selected inactive model) for export without consuming a saved-set slot. The document remains connection-scoped and is never replayed after an interrupted request. An export shall include every value in its scope or refuse the complete document.

One mechanism, two kinds of set. A set is scoped by ConfigKind (§3.10.2). A station set carries the STATION_CFG records of a root’s subtree and restores deployment data in place. A model set carries the PAR_CFG records for one ModelCode — the same content §3.8 calls a recipe — and shall be applied through the §3.8 changeover transaction (PrepareRecipe → recursive readiness → infallible CommitRecipe), never as a sequence of per-field writes, so a model load keeps its atomicity and its migrate-or-fault behaviour. Loading a model set is therefore a changeover and is gated by CHANGEOVER as well as CONFIG_SET. This is also what makes a local recipe catalog editable and durable instead of a compiled-in constant: the §3.8 provider reads its records from the same I_ConfigStore, so where recipes come from and how recipes survive a restart stop being two unrelated answers.

The store is pluggable and untrusted. Set persistence is supplied through one logical I_ConfigStore capability selected per deployment, mirroring §3.8’s provider pattern:

E_ConfigStore Medium Payload
LOCAL_RETAIN in-PLC retentive memory native structures
FILE_JSON / FILE_XML controller or host file system serialized set document
EXTERNAL database, asset system or MES, reached through a connector (§3.15) store-defined

The store moves bytes and nothing else. It does not validate, does not know what a value means, and is never an authorization authority; everything it returns is untrusted input, validated on the way in (§5.6, §14). LOCAL_RETAIN is the shipped default, so a conforming station persists its parametrization with no file system, no network, and no configuration.

Access. Editing one value remains DATA_WRITE. Saving, loading or importing a set is the separate gated action CONFIG_SET (§7.7), because replacing a machine’s entire parametrization is not the same decision as changing one number. Set operations require the owning root to be READY, and both acceptance and refusal are audited per §8.3 with the set name and record count.

Scope. This mechanism covers registered editable configuration only. Retained operational data — counters, alarm history, OEE accumulators — persists under its own rules and is never part of a parameter set. The digital nameplate (§3.10.1) is identity rather than configuration and is likewise excluded.

Cross-references: §3.8/§3.8a (the two kinds of persistent data and their placement), §3.10.2 (capability registration — what a set contains), §7.7 (DATA_WRITE, CONFIG_SET), §8.3 (audit), §8.8 (reason codes), §13 (schema change), §14 (untrusted input).

3.8c Teach capture — acquiring a value from the machine

Section titled “3.8c Teach capture — acquiring a value from the machine”

§3.8a says where an editable value lives and §3.8b what happens to it across a restart. Neither says how the value is first obtained. For most parameters that is a non-question: an engineer knows the number and types it. But a class of values is knowable only by demonstration — a gripper’s closed width with a real part between the jaws, a camera’s exposure under the real lighting, a force or torque threshold, a tare, a mechanical offset. These cannot be calculated, so without a mechanism they are commissioned by reading a live display and transcribing the number by hand: a two-person job, repeated per variant, and one transcription error away from a wrong recipe.

A module may therefore register a capture beside an editable value: an action that writes the module’s own live value into its own ParCfg or StationCfg field. A capture is a write whose value comes from the machine instead of from the client. It is not a new authority and it adds no new gated action.

(a) A capture reaches only an already-editable field. It shall be registered in the §3.10.2 manifest against the same (Scope, WriteKey) as the value it writes, and shall be routed through the same acknowledged root mailbox. A capture able to reach a field that is not independently an editable capability would be a back door around §3.8a, so it is not permitted: capture changes how the number arrives, never which numbers may change.

(b) The source shall be published. The captured quantity shall be a value the module already publishes (§3.10) — never a private internal. The operator can then see the number that is about to be stored, on the same screen, before storing it; a capture whose input is invisible is unreviewable.

(c) Validation is not bypassed. The captured value shall be validated against the same range, band and schema as a typed write, and a failure refused with the same reason (RECIPE_INVALID, §8.8). A machine-supplied number is not more trustworthy than a human-supplied one (§14).

(d) Same authority, same audit. A capture shall be gated DATA_WRITE (§7.7) and audited per §8.3, recording the stored value, the field, and that the source was a capture rather than a client entry — so a later reader can tell how a recipe value came to hold what it holds.

(e) Deliberate setup only. Capture should be offered only in modes where the machine is knowingly being set up rather than producing — ADJUSTMENT is the mode §3.4 defines for exactly this — and shall respect the same release and permissive rules as a manual movement (§7.6), because reaching the pose or state worth capturing is usually itself a manual movement.

(f) One value, not a set. Capture writes a single registered value. Saving, loading or importing a whole parametrization remains the separate CONFIG_SET action of §3.8b, unchanged.

Capture is optional and advertised through the ordinary Features flag set (§3.9), so a module with nothing worth demonstrating publishes nothing and pays no cost. Where it is offered it is paid once in the owning module type — a gripper CM, a camera CM, a force-monitor CM — and never re-invented per station, per device family, or per annex.

Cross-references: §3.8a (placement), §3.8b (persistence and sets), §3.4 (ADJUSTMENT), §3.9 (feature flags), §3.10.2 (capability registration), §7.6 (manual release), §7.7 (DATA_WRITE), §8.3 (audit), §8.8 (RECIPE_INVALID), §14 (untrusted input).

§7.7 gates editable data with two actions for the whole station: DATA_READ to see a value and DATA_WRITE to change one. That is one threshold for everything a station stores, so a deployment that wants its commissioning values guarded by an ENGINEER cannot also let an OPERATOR adjust a counter preset or a label without either lowering the guard on everything or raising it on the preset. Real stations need both at once.

(a) Data class — the access axis. A root Unit may declare data classes: named, project-owned groups of editable values, each with its own required read level and write level (E_AccessLevel). ConfigKind (§3.10.2) remains the lifecycle axis — what the value is (model config, station config, line config) and which parameter set carries it; the data class is the access axis — who may see and change it. The two are orthogonal: a “public station data” class holds STATION_CFG values, travels in station sets exactly like the rest of the station config, and differs only in who may edit it.

A class is declared at the root with a stable ClassId, a label key and default read and write levels. Every root carries three built-in classes, one per ConfigKind, whose levels are the DATA_READ/DATA_WRITE thresholds of the policy — so a value registered without a class behaves exactly as it did before this section existed. Declaring a class is additive; the policy keeps the gated actions of §7.7 unchanged.

(b) Class levels are policy. A class’s read and write levels are held in the root’s access policy (§7.7(b)) beside the gated-action thresholds — persistent station config, editable through the same audited, ACCESS_POLICY-gated path, and subject to the same self-lockout rule. The declared levels are defaults, not constants: a deployment may raise or lower a class without a download, as it may any other threshold.

(c) A value may only raise its class’s requirement. A registered value may declare its own minimum read and/or write level. The effective level of a value is the higher of its class’s level and its own minimum — never lower. A single value can therefore be made harder to change than the class it sits in (a calibration constant inside otherwise-public data), but no value can be made easier to change than its class says. That is what keeps a class auditable: its level is a bound on everything in it, and a reviewer reads one number instead of every registration. A value’s own minimum is declared at registration and is not editable at runtime; it states a property of the value, not a deployment preference.

(d) The PLC computes and enforces the effective level. Each manifest entry (§3.10.2) publishes its ClassId and its effective ReadLevel and WriteLevel, so a generic HMI greys and hides editors from data rather than recomputing policy. Enforcement stays in the PLC: WRITE_CONFIG, a capture (§3.8c) and a collection operation (§3.10.2a) are accepted only when the session level meets the value’s effective write level, and a refusal names the value and the level it required. A value whose effective read level the session does not meet is served in the manifest with its metadata and without its value (Readable := FALSE), so an editor can say that something exists and why it is hidden instead of silently omitting it. This is presentation control and defense in depth, not confidentiality: where the same data is also published in the cyclic namespace, protecting it from another client is the transport’s job (§7.7(d), §14).

(e) Sets respect the levels of what they carry. A parameter set (§3.8b) is not a way around a class. Loading a set shall be refused, before any value changes, when the session does not meet the effective write level of every record the set would apply — naming the first such record — so CONFIG_SET access alone cannot replace values the same user could not edit one at a time. Exporting a set likewise requires the effective read level of every record it would reveal. Saving and deleting reveal nothing outside the PLC and remain governed by CONFIG_SET alone.

Cross-references: §3.8a (placement), §3.8b (parameter sets), §3.8c (capture), §3.10.2 (manifest entry), §3.10.2a (collections), §7.7 (levels, policy, ACCESS_POLICY), §8.3 (audit), §14 (defense in depth).

Optional behaviour profile Line (§1.5): §3.8e and §8.5.2 together.

Station config describes one station and model config one product. A third kind describes the line the station belongs to and is shared by every station on it: the shift calendar (§8.5.2), a line-wide takt, the line’s identity for a host system. Held per station, such data drifts the first time one station is edited and its neighbour is not; held nowhere, it is re-entered on every HMI. Line config is therefore its own ConfigKind, LINE_CFG, with exactly one authoritative copy.

(a) A line is orthogonal to the Unit forest. Like the control domain (§9.8), a line is not a Unit and has no parent: it is a named arrangement (LineId) that zero or more root Units reference, on one controller or across several. A root Unit references at most one line. No super-root is created to hold it, and the line is never registered as any Unit’s child: it is declared beside the roots, as a control domain is. Each referencing root presents the line’s values as its own line config — in its §3.10.2 manifest, under its own scope — and routes their writes, captures, set records and access checks to the line through its own mailbox, so a line value is edited, audited and access-classed like any other without the line entering the module tree. To keep the two key spaces apart, a LINE_CFG value’s WriteKey shall begin line. and no other value’s may.

(b) One owner; every other copy is a mirror. Exactly one controller hosts the line’s owner. Line values are registered as write capabilities (§3.10.2, ConfigKind := LINE_CFG) only on the owner and are edited only there, under the ordinary WRITE_CONFIG path, data classes (§3.8d) and audit. Every other controller that references the line hosts a mirror: a read-only local copy whose manifest entries carry Writable := FALSE, and which a client cannot change. Two editable copies of one fact are exactly the drift this section exists to remove, so there is no multi-master mode.

(c) Revisioned, whole-revision replication. The owner increments LineRevision on every accepted change. A mirror obtains the line’s records through one pluggable I_LineSource capability — mirroring the provider pattern of §3.8 and the store of §3.8b — and applies a new revision whole or not at all, staged and validated like a parameter-set load, so a mirror never runs on a half-replicated line. Several root Units on the owner’s own controller share the owner directly and need no source. The transport behind I_LineSource is a binding and deployment choice; the source, like a store, is untrusted input (§14).

(d) A mirror keeps running, and says how current it is. A mirror persists its last applied revision (§3.8b rules apply unchanged), so a controller restarted while the owner is unreachable runs on the line config it last had rather than on defaults. It publishes LineRole (OWNER/MIRROR), LineRevision, the owner’s identity, the time of the last successful update, and Stale once no update has succeeded within the declared window. Stale line config is annunciated as a LOW/SYSTEM AUTO_RESET event and never blocks production on its own: a shift boundary computed from a calendar one revision old is a reporting error, not a hazard. A deployment for which line config is safety- or quality-relevant declares that through its own release conditions (§7.2.1), visibly and per condition.

(e) Line config is not a set operation on a mirror. Station and model sets (§3.8b) never carry LINE_CFG records. A line set may be saved, loaded and deleted on the owner only; a mirror refuses every line-set operation with a reason naming the owner.

Cross-references: §3.8a/§3.8b (kinds, persistence, sets), §3.8d (classes), §3.10.2 (manifest), §8.5.2 (shifts — the first line config), §9.8 (control domain — the same orthogonal pattern), §14 (untrusted sources).

Each module advertises a Features flag set — e.g. RecipeEnabled, CalibrationEnabled, CaptureEnabled (§3.8c), ManualFunctionsEnabled, plus per-command enables. Disabled features:

  • shall be omitted from the Self-Description Service catalogues/data surface (§3.10), so the Flutter HMI renders only what exists and pays no read cost for it;
  • should be checkable by clients through declared capability metadata and by PLC code through the binding’s capability lookup (TC3 §3.2; AB §3.2).

This is what makes the same reusable type behave as a “stripped” or “full” instance purely by configuration.

3.10 Fraktal Self-Description Service and Flutter auto-discovery

Section titled “3.10 Fraktal Self-Description Service and Flutter auto-discovery”

The operator app discovers and renders the module forest generically through the Fraktal Self-Description Service. The service is a logical runtime contract, not a prescribed wire protocol or server product. Fraktal/TC3 binds it to TF6100 OPC UA (TC3 §3.10/§11); Fraktal/AB binds it by default to EtherNet/IP explicit messaging plus the Fraktal gateway and permits OPC UA as an alternative projection (AB §3.10/§11).

A conforming service shall provide all of the following from one live source of truth:

  • live runtime discovery of every deployed root and its hierarchy, with stable canonical identities, declared tier/type/capabilities, and a monotonic configuration/discovery revision;
  • typed values with declared logical type/dimensions, explicit freshness and quality, and source timestamps plus synchronization quality where the PLC owns a timestamp;
  • bounded fast/slow/on-demand reads (or equivalent bounded change detection) so discovery and traffic stay proportional to actual demand;
  • one narrow, typed, acknowledged mutation vocabulary routed back through PLC access/release/validation, with no arbitrary symbol/tag write and no reconnect replay;
  • explicit protocol and schema versions with fail-closed incompatibility handling; and
  • authenticated principals, least privilege, and integrity/confidentiality controls appropriate to the binding’s declared IEC 62443 conduit (§11.2, §14), plus optional industry projections generated from this same live model rather than maintained in parallel.

The following layers make that contract HMI-complete without station code:

(a) Exposure by deployed root. Exposure starts only at an explicitly deployed root instance (and at a separately defined published data product such as fieldbus topology). The binding carries that selection through the root’s real child hierarchy or generated manifest, so a new module type still needs no station-specific exposure code. Reusable type definitions shall not publish every possible instance globally: doing so turns implementation storage and infrastructure aliases into additional roots and violates least privilege. Pointer/reference storage, private registry/provider state, scratch data, and aliases beneath a published root shall be excluded. Bindings define and gate the exact mechanism (TC3 §3.10; AB §3.10/G-EXTACCESS).

(a′) The HMI contract is data, not accessors. A client shall not require PLC-language properties, methods, pointers, or type introspection. Everything it renders is published data in the module mirror: Status : ST_ModuleStatus (Name, ModuleType, State, FaultActive, the live Diagnostic per §6.9(a), TileEnable per §3.13), refreshed each scan by the owning lifecycle — so a type is HMI-complete with zero exposure code (O1), and a port re-binds the same structures (O8). On a Unit, a live stall (Pending, §6.9) surfaces on the mirror whenever no fault is active, so the tile message is always the most useful sentence available (O3).

(a″) Remote commands are acknowledged data transactions. Every root Unit shall publish one typed request mailbox and response mailbox through the service. The client writes all arguments before changing the commit sequence. The Unit samples each new complete sequence once, copies it to private storage, routes it through the same access/release-gated operations used by local PLC code, clears transported secrets immediately, and publishes the matching acknowledgement sequence only after processing. Transport write success is not PLC acceptance; Accepted plus the matching acknowledgement is. A reconnect shall never replay an unacknowledged request automatically. Bindings may name the records and fields (ST_HmiRequest/ST_HmiResponse, Sequence/AckSequence in TC3; AB §7.7’s physical names are frozen after S9), but these commit/acknowledgement/no-replay semantics are normative.

(b) Type-aware discovery. Every module record explicitly declares ModuleType, concrete type identity, capability flags, canonical path, and parent/root identity. The Flutter app walks this hierarchy and selects standard UI templates from the declared semantics—never from a guessed tag name, optional-field absence, PLC-language inheritance relation, or transport metadata. A binding may project richer native type metadata, but clients do not depend on it.

(c) Standard semantics. The state model is the native command model by default: expose each module’s ExecState and, for Units, Mode directly (§6.1, §3.4). No companion specification is required for base conformance. OPC UA for Machinery (OPC 40001-1), PackML/OPC UA (OPC 30050), AAS/MTP, and the other §11.7–§11.11 mappings are optional, binding-qualified projections from the same service model.

Each module shall present the same logical sub-structure mirroring §3.12: Identity, Status (plus Mode for Units), ParCfg, ParCmd, OutCmd, OutImm, Features, and Children; clients read the execution summary from Status.State. These are canonical repository path segments. A binding may obtain them from native namespace nodes or reconstruct them from a validated manifest, but it shall not expose a competing hierarchy or identity.

The runtime self-description (§3.10) answers what the module is doing; maintenance also needs what the module is: who made it, which serial, which versions, where the manual lives. Every module therefore carries a digital nameplate, published through the same Self-Description Service:

  • Fields (aligned with the IDTA Digital Nameplate for Industrial Equipment submodel template, IDTA 02006, so the projection to AAS in Annex K is direct): product URI (globally unique asset identifier), manufacturer name, product designation, serial number, year of construction, hardware/firmware/software versions, order code, and a documentation link (manual/handover docs, cf. IDTA 02004). All fields are plain published data — static identity, set at Setup, never runtime-mutated.
  • Cardinality. A root Unit shall publish a nameplate (it is the sellable asset); any module may (a purchased CM — a robot, a camera — has its own identity worth keeping). Empty nameplate = none published; the HMI simply omits the card.
  • HMI (§3.13). The nameplate renders as a facet card on the module detail view — identity, versions, and a tappable documentation link. No per-type HMI code (O1).
  • Not configuration. The nameplate is identity, not behaviour: it is deliberately outside §3.8 (no recipe/model dependence, no §7.7 write gating question — it is not writable from the HMI at all).

Cross-references: §3.10 (self-description), §3.13 (HMI rendering), §8.3/§10.5.1 (the diagnostic surfaces this complements), Annex K (AAS/IEC 63278 projection).

3.10.2 Bounded configuration manifest and typed write capabilities

Section titled “3.10.2 Bounded configuration manifest and typed write capabilities”

Activation-static identity and catalog data should be excluded from the cyclic namespace when the binding can serve it on demand. Each root Unit therefore exposes a revisioned, bounded configuration-manifest page through its acknowledged mailbox. A deterministic walk emits entries containing Scope (qualified module identity), Item (canonical repository-path fragment), and ValueText; paging shall not require a full manifest buffer in the PLC. ConfigRev changes after activation, model/configuration changes, or restart so a client cannot retain stale metadata silently.

Read publication does not confer write authority. An editable entry appends all of the following capability data:

  • stable WriteKey scoped to the owning module and a non-zero WriteRevision;
  • ConfigKind (PAR_CFG, STATION_CFG, or LINE_CFG — §3.8e) and ValueType (NUMBER, TEXT, BOOLEAN, or TIME), with append-only ordinals;
  • the value’s data class (ClassId) and its effective ReadLevel and WriteLevel (§3.8d), computed by the PLC, and Readable := FALSE with no value when the session does not meet the read level;
  • Writable, optional numeric bounds, optional exact enum domain, engineering unit and label key; and
  • whether the owning root must be READY for the write.

An absent key/revision, Writable=FALSE, invalid metadata, or a duplicate (Scope, WriteKey) registration shall fail closed and produce no editor control. Item remains a path/display identity; WriteKey is the mutation identity and shall not be inferred from Item or from transport-level writability. For WRITE_CONFIG, the client sends TargetPath=Scope, NameValue=WriteKey, IntValue=WriteRevision, and the serialized candidate in TextValue, committing Sequence last.

The root rechecks the value’s effective write level (§3.8d; DATA_WRITE for a value in a built-in class) and subtree ownership, then routes only a registered key to the owning typed handler. That handler shall recheck revision, value type, range/domain, current machine state, and all module-specific invariants before changing data. Unknown keys, stale revisions and malformed or out-of-domain values are rejected without mutation. Recipe-backed changes remain migrate-or-fault and transactional per §3.8; this mailbox is not a partial recipe-write escape hatch. Accepted and denied requests follow the §8.3 audit rules. A generic HMI may render editors from these capabilities, but is never an authorization or validation authority.

3.10.2a Bounded collection capabilities (repeating editable data)

Section titled “3.10.2a Bounded collection capabilities (repeating editable data)”

The capability of §3.10.2 describes one value. A class of real configuration is instead a bounded, repeating structure: a list of taught positions in path order, the corner set that generates a pallet, a table of tools, a set of planning zones, a table of reject codes. Published as scalars these explode — a forty-position list is over three hundred write keys, and six of them are two thousand, which violates O4’s rule that published surface stay proportional to what is actually consumed. Published not at all, they migrate into a vendor engineering tool and leave the standard’s recipe, parameter-set, access and audit machinery entirely (§3.8, §3.8b, §7.7, §8.3) — which is the larger failure, because it is what makes routine post-commissioning work (a new model, a new gripper, a re-taught tray) require a laptop, a licence and a specialist instead of an HMI.

A module may therefore register a collection capability: one manifest entry describing a bounded collection of records and the schema of a record, rather than one entry per cell.

(a) The manifest carries the schema; the data is paged on demand. A collection entry adds ConfigShape := COLLECTION (append-only beside SCALAR), a compile-time MaxRecords, the current RecordCount, an Ordered flag, and a bounded list of field descriptors — each carrying exactly the scalar metadata of §3.10.2 (ValueType, bounds, enum domain, unit, label key). Record contents are not manifest entries; they are fetched by page through the same mailbox when an editor opens. Discovery cost therefore stays proportional to the number of collections, not to the number of cells (O4), while the whole collection remains editable.

(b) One capability, addressed per cell. Mutation extends WRITE_CONFIG with a record index; the field is named by its ordinal in the schema. (Scope, WriteKey) uniqueness is unchanged — a collection is one registered capability, not a family of them. Because each field descriptor is an ordinary scalar descriptor, a generic HMI renders each cell with the editor it already has, and needs no per-type knowledge to present the collection as a grid or a form.

(c) Record operations are enumerated and bounded. Beyond setting a field, a collection may permit AppendRecord, DeleteRecord and — only where Ordered is TRUE — MoveRecord. Ordering is declared rather than assumed: a path’s record order is its execution order and must be editable, a tool table’s is meaningless and the HMI should not offer it. MaxRecords is fixed at compile time and an append beyond it is refused, never allocated (O10).

(d) Same authority, same validation, same audit. Every record operation is a DATA_WRITE (§7.7), audited per §8.3, and routed to the owning typed handler, which rechecks revision, type, range/domain and collection invariants before mutating — a path with fewer than two points, a pallet with a degenerate corner set, a duplicate identifier. Collection-valued configuration is recipe- or station-class like any other (§3.8a) and takes part in parameter sets (§3.8b), where it replays as its records in order under the same deterministic walk.

(e) Capture applies per cell. A field whose value can only be demonstrated rather than calculated uses the teach capture of §3.8c — the operator brings the machine to the state, and the module writes its own published live value into that cell. This is what makes a taught-position collection editable from the generic HMI without re-hosting a vendor teach tool: the pose comes from the machine, the structure is ordinary configuration.

(f) It stays optional and bounded in ambition. A collection is for configuration a person edits. Operational data — counters, histories, traceability records, measurement series — is not configuration and shall not be published this way (§3.8b scope rule).

Cross-references: §3.10.2 (scalar capabilities this extends), §3.8a (placement), §3.8b (parameter sets), §3.8c (capture), §3.13 (generic rendering), §7.7 (DATA_WRITE), §8.3 (audit), §1.1 O4 (proportional surface), O10 (bounded structures).

3.11 Reusable sub-trees (low-effort duplication)

Section titled “3.11 Reusable sub-trees (low-effort duplication)”

Reuse is achieved with a binding-native reusable type form, not copy-paste:

  • Any archetype is a type. To duplicate, declare another instance with a fresh canonical identity and HAL/configuration mapping. The binding shall provide a deterministic, exactly-once initialization mechanism and shall fail closed before cyclic execution when wiring is invalid (TC3: constructor/Setup, TC3 §3.11; AB: generated first-scan setup, AB §3.11).
  • A recurring assembly (e.g. a clamp = 1 cylinder + 2 sensors) is packaged as one conforming Equipment-Module type that owns its children internally. That whole sub-tree then drops in anywhere as one named type with a fresh mapping.
  • Nested wiring is explicit and order-safe. A parent shall not rely on an unspecified member-construction or import order to forward identity, HAL, recipe, provider, or child registration. Each binding provides an order-safe one-shot setup form usable at any nesting depth and machine-checks exactly-once setup before first cyclic use (Annex B; TC3 §3.11; AB §3.11/G-SETUP).

Every module — FB_Unit, FB_EquipmentModule, FB_ControlModule — exposes the same four-structure data contract, which is also exactly what the Self-Description Service publishes (§3.10):

Structure Suffix Role Distribution
Configuration ParCfg parameters/recipe set from the parent; behaviour-shaping applied on Start, or on disabled → operational
Command params ParCmd per-command transfer parameters latched on the positive Execute edge
Command results OutCmd values valid after a command completes written once on ExecState → DONE
Cyclic status OutImm live status (inputs, outputs, flags) + first-out Diagnostic refreshed every scan

Command result vs. derived state — the distinction that decides which one. Ask what makes the value change. If a command produced it and it stays true until another command replaces it, it is OutCmd. If it is simply true right now, recomputed from what the modules underneath actually report, it is OutImm.

Homed is the case that gets this wrong most often. Written as OutCmd.Homed := TRUE at the end of a HOME sequence it goes on claiming “homed” after an operator jogs an axis off the reference position in MANUAL — because no sequence runs to clear a latch that only a sequence can clear. It is not a command result. It is a fact about where the axes are, and it shall be derived.

A module publishes derived state through _M_State, which returns the value so the assignment reads as it otherwise would:

OutImm.Homed := _M_State(Idx := 1, Key := 'project.state.atLoadPosition',
Ok := Ram.OutImm.Retracted AND Door.OutImm.Retracted AND Slide.OutImm.Retracted);

What the call adds over a bare assignment is what nobody wants to write per flag (§1.1 O1):

  • The flag carries its own name, so the HMI renders it without knowing the module type (§3.13) — the same generic-rendering bargain as the rest of the contract.
  • Since — the moment the value last changed, on the synchronized clock (§2.7). “Door closed” is rarely the question; “closed for how long” is.
  • Fail-safe on abandonment. A flag shall be published unconditionally every scan. One that stops being published is marked Stale and forced FALSE on the next scan: state nobody is computing is not a claim (§5.6). A latch left standing is precisely the failure this mechanism exists to prevent, so the mechanism must not be able to leave one.
  • Bounded at MAX_STATE_FLAGS per module, statically sized like every other Fraktal table (§1.1 O10).

It is deliberately the same shape as the §6.9(b) named condition wait (_M_Await(Idx, Label, Ok)) — one idiom for “a named boolean the framework publishes”, not two (§1.1 O9).

This contract makes every module uniform and self-describing: the handshake of §6.1 reads/writes ParCmd/OutCmd, the recipe of §3.8 lives in ParCfg, and the Flutter HMI binds to OutImm for live state. Module-specific structure types shall be named ST_<Module>ParCfg / ST_<Module>ParCmd / ST_<Module>OutCmd / ST_<Module>OutImm (e.g. ST_SeparatorParCfg).

StationCfg (§3.8a, §3.8b) is deliberately not a fifth member of this contract. A module that needs deployment data declares its own persistent ST_<Module>StationCfg, and its editable values reach clients as §3.10.2 write capabilities. A binding may also mirror the structure cyclically for reading, but the capability — never the mirror — is what makes a value writable.

3.13 HMI navigation contract (drill-down model)

Section titled “3.13 HMI navigation contract (drill-down model)”

The module hierarchy maps directly onto an HMI navigation tree (FB_Unit = ModeHandler view, FB_EquipmentModule = CommandHandler view, FB_ControlModule = device view). The operator app shall navigate by drill-down through the module tree, and the PLC shall expose the metadata that makes this automatic:

The module tree with Station A and ClampStation tinted red under an event banner naming StationA.ClampStation.CylB, and Conveyor B tinted blue.

Drill-down by event path: a module’s events tint its path in the tree, by severity.
  1. The event’s source, StationA.ClampStation.CylB.
  2. Its path in the tree, tinted red: Station A, then ClampStation.
  3. An information message tints Conveyor B blue.
Browser HMI simulation at revision a1163c7 · try it
  • Two views per module. Each module type provides a Tile (compact: name, state LED, key status, quick manual buttons) and a Detail/Overview (manual functions, status LEDs with descriptions, parameters).
  • Parent shows children as tiles. A module flags whether it appears as a tile on its parent’s child view (and whether it serves as a header control). The operator app renders a parent by laying out its children’s tiles, and drills into a child on tap — the same parent→child path as the module tree.
  • Status LEDs carry descriptions. Every status LED binds to a condition with an adaptable, multilingual text description (sourced from the channel/PermIntlk descriptions of §7), so the operator reads why, not just red/green.
  • Generic rendering. Because the tree is self-describing through the Fraktal Self-Description Service (§3.10), every module carries the four-structure contract (§3.12) and Features flags (§3.9), the Flutter app builds tiles and detail views generically — no per-station screen building. New or duplicated modules (§3.11) appear in the HMI automatically.
  • Tabbed details and category facets. Every module detail provides Overview and Description; typed/category data may add reusable Motion, Vision, Code Reader, or RFID tabs. An HMI-local Administrator may set each tab’s minimum view level and add localized custom controls, but this layout cannot widen the §7.7/§14 PLC write surface or recover symbols excluded from publication. A one-visible-tab detail omits the tab strip.
  • Guided Unit work. A Unit guidance tab may match CurrentStep.StepNo/StepName (or all WAIT_OPERATOR steps) and opens a full-screen localized work instruction with the live wait conditions and typed Decision. The PLC sequence remains the sole owner of progress and acceptance; dismissing HMI guidance never advances a step.
  • The stuck-step reason surfaces on the owning Unit’s view, exactly where the operator expects sequence state (see §6.9).
  • Discovery & binding contract. The client discovers the tree by walking the service’s canonical hierarchy (§3.10) for module records carrying Status : ST_ModuleStatus — that record is the module marker, tile caption, state LED, and message line (§3.10(a′)); child tiles are the child records with Status.TileEnable. A binding may expose that hierarchy as a native namespace or reconstruct it from a manifest and bounded value services. Units additionally publish Pending, CurrentStep, History (the §6.9(a) ring), GoodCount/NokCount (§8.11), Decision, and the §8.11.4 profiler structures. The write surface is deliberately narrow and is committed through the acknowledged Unit mailbox of §3.10(a″): command execution/abort, decision answer, mode/start/stop, manual commands and the other explicitly gated actions of §7.7.
  • Event path highlighting (tree). The navigation tree shall tint the full ancestor path — from the root Unit down to the event’s source module — with the colour of the highest-severity active event in each node’s subtree (ERROR > WARNING > MESSAGE, §8.3); the source module renders strongest, ancestors as tint. An operator therefore sees where to drill from any depth with zero station code — the highlight derives from the same Status.Diagnostic/AlarmLog data every node already publishes (§8.2 rollup made visible).
  • Cycle-profile view (§8.11.4). Every Unit’s detail view renders, generically from the fixed profiler structures, the last cycle as a step waterfall (start/duration per step, ExpectedTime overlaid) and a Pareto of per-step Avg/Max; tapping a step drills to the awaited module, whose detail shows its per-command timing table. Steps are coloured by time class and the view header splits Total vs Work (the real cycle time) vs the waits (WAIT_UPSTREAM/WAIT_DOWNSTREAM/WAIT_OPERATOR/WAIT_EXTERNAL, §8.11.4(f)) — so “the station is slow” and “the station is starved” are visibly different statements. No station adds screens or code for this — the chart exists because the step records and the framework lifecycle exist.

Localized presentation and module content. Every operator-facing string follows LOCALIZATION_AND_MODULE_CONTENT.md. PLC display fields shall carry stable localization keys rather than prose; the HMI composes standard/project catalogs and keeps identity, protocol data, and structured diagnostic context separate. First-run language selection, administrative CSV exchange, module descriptions/PDFs, and per-module section view policy are part of the generic HMI contract and add no station-specific screen code.

3.14 Module lifecycle extensions (framework callbacks)

Section titled “3.14 Module lifecycle extensions (framework callbacks)”

Every module has the same small set of lifecycle extension points. They are framework-internal callbacks at defined points in the authoritative cyclic lifecycle (§2.2), not public parent-facing capabilities. The binding shall state how each extension is represented and invoked. A binding with inheritance may use protected virtual methods; a binding without inheritance may use generated composition and explicit callouts. Either mechanism shall preserve the same ordering, one-shot semantics and default behaviour without project-authored correctness wiring.

These extension points replace ad-hoc callback sets and hand-written one-shot guards with one fixed contract. A module declares only the application reaction it needs; the framework or generator supplies the lifecycle behavior and the default for every omitted reaction. The On<Event> logical names are stable across bindings even when their native object names differ.

Standard extension Owner Invoked by framework when Return
OnInit any module First operational scan only (one-shot, after recipe/type data is available) DINT
OnCommandStart any module Once for each accepted Execute rising edge, after OnInit and before cyclic/dispatch work DINT
OnCyclic any module Every scan, background management after data load DINT
OnModeChanged Unit only After a SetMode is accepted and the new mode is committed DINT
OnModeExit Unit only During a mode change, before leaving the old mode — lets a Unit stop gracefully instead of being cancelled outright DINT
OnAbort any module On cancel/abort, not during ERROR or NOT_READY DINT
OnAbortInError any module On cancel/abort while the module is in ERROR DINT
OnManRelease any module exposing manual functions To (re)evaluate manual-function release conditions (see §7.6) —
OnChainAbort step chain A chain is leaving via cancel —
OnChainError step chain A chain is leaving via error —

OnChainStart / OnChainDone logical points may exist in a binding but shall not be used by applications; put initialization in start step N000 and teardown in finish step N999 instead (they always run, optional callbacks may not). See §6.5 step-chain conventions.

3.14.2 Extension-order contract (mandatory)

Section titled “3.14.2 Extension-order contract (mandatory)”
  1. Framework behavior first. Except for OnModeExit, the framework-owned behavior associated with an extension shall execute before the application reaction and its return shall be propagated unless deliberately changed. [TC3] realizes this with a base-method call first; [AB] realizes it in generated lifecycle routines before the application callout. A project shall never have to remember this ordering.
  2. Declare only what is needed. An omitted extension uses the framework default; do not create empty reactions.
  3. Keep extensions side-effect-bounded. A cyclic extension (OnCyclic) shall be idempotent per scan and shall not drive outputs directly — it manages state and raises events; movement stays in the step chains (§6.2–6.4).
  4. One-shot initialization belongs in OnInit. Do not reproduce it with a first-scan flag in OnCyclic.
  5. Command-local reset belongs in OnCommandStart. Reset or latch command-local wiring there when it must run once for every accepted command, including a repeated finite command in the same mode. Keep process initialization in sequence step N000 and process completion in N999; the extension shall not become a second sequence body.
  6. The binding shall prove the assembly. Generation and linting shall reject a module whose extension can bypass, reorder or duplicate the framework-owned portion of the lifecycle.

3.14.3 Worked example — OnModeChanged on a Unit

Section titled “3.14.3 Worked example — OnModeChanged on a Unit”

A Unit limits actuator speed in MANUAL and restores it in AUTO. The binding-owned lifecycle first performs the common mode bookkeeping, then invokes this application reaction:

OnModeChanged application reaction(NewMode, OldMode):
when NewMode = MANUAL: OutImm.MaxOverride := 30
when NewMode = AUTO: OutImm.MaxOverride := 100

The reaction contains no duplicate bookkeeping and is identical in intent whether the binding emits an override or a composed callout.

3.14.4 Mode change aborts immediately by default — OnModeExit provides graceful completion

Section titled “3.14.4 Mode change aborts immediately by default — OnModeExit provides graceful completion”

By framework default, a mode change performs an immediate software abort: all standard-control chains and commands are cancelled so the operator lands in a defined state. This is not an emergency stop and not a safety function (§9). Where a Unit must instead finish its cycle or move to a waiting position before yielding the mode, it shall declare an OnModeExit reaction that triggers a stop-after-cycle and holds the mode until the Unit is stopped (bounded by a timeout), rather than immediately propagating abort to children. Return semantics are fixed: the framework invokes the reaction every scan while a mode request is pending; returning 0 consents to the default immediate abort, returning >0 holds the transition while the Unit stops gracefully; the new mode commits only when the Unit leaves BUSY, after which OnModeChanged fires.

OnModeExit is the deliberate exception to framework-first ordering: the application reaction runs before the framework cancel while it returns >0; when it returns 0, the binding invokes the framework cancellation/commit portion exactly once. [TC3] stages the base call to the end; [AB] stages the generated cancel phase after the callout. Every binding shall document and test this exception.

Per §6.7, lifecycle extensions shall be filed with the module’s private/protected implementation (for example, a Lifecycle or Transition States group alongside Steps, Commands, Sequences). They are not step actions and shall not live in the Steps group.

Cross-references: §2.2 (authoritative lifecycle), §3.2 (public capabilities), §6.5/§6.7 (step chains and source organisation), §7.6 (OnManRelease is the manual-release member of this family), §8 (extensions raise events via the §8.7 constants, never ad-hoc strings).

Section titled “3.15 External device connector & link supervision”

The HAL (§3.6, §10.2) abstracts bit/word I/O. It does not cover networked smart devices — robots, programmable power supplies, chillers, testers, vision systems, scanners — which hold a session and speak a protocol (TCP/socket, S7, REST, vendor SDK) with their own connect/handshake/heartbeat. Wrapping such a device as if it were I/O hides the one failure mode that matters most for it: the link itself going away. The standard therefore defines a dedicated archetype and a uniform link-supervision contract.

A smart device is represented by the logical I_DeviceConnector capability, which composes the I_Module capability (§3.2) with session and link concerns. It owns the transport; it is then composed inside a Control Module so the rest of the tree still commands it through the standard handshake (§6.1) and never sees the protocol. The capability surface is:

I_DeviceConnector capability
operations: Connect, Disconnect
state: Linked, LastSeen, LinkReason

Linked means session up and heartbeat healthy; LastSeen uses the synchronized timestamp contract (§2.7); LinkReason carries the first-out link/protocol diagnostic. Bindings may realize this with an interface, a typed record plus routines, or a generated registry entry (§3.2).

The protocol boundary (serialization, socket lifecycle, vendor SDK) lives entirely inside the connector — the FC_PlcToTst_* / _00FB_Eth_*-style bridge functions in the reference programs are exactly this layer and shall not leak into Control Modules or sequences.

3.15.1a Byte-transport abstraction (TCP/serial devices)

Section titled “3.15.1a Byte-transport abstraction (TCP/serial devices)”

Many peripheral devices — vision sensors, code readers, gauges, printers — speak a simple byte protocol over TCP/IP or serial (typically ASCII request/response). The framework therefore defines one platform-neutral transport seam, so device modules are written once and ported by swapping only the transport:

  • I_ByteChannel. This logical capability has non-blocking, cyclic-poll semantics (PLC-friendly, no blocking calls): Open(Host, Port), Close(), Send(bytes), Poll() (drains received bytes into the caller’s buffer), and a published E_ByteChannelState (CLOSED → OPENING → OPEN, plus FAULT). All operations return immediately; progress is observed over scans.
  • The porting seam (O4/O8). Platform bindings realize the capability — [TC3]: Tc2_TcpIp/TF6310 (TC3 §3.15); CODESYS: SysSocket/NBS; Siemens: TSEND_C/TRCV_C wrappers. No device module names a socket API: its protocol logic consumes I_ByteChannel semantics and moves between PLC brands with only its binding adapter regenerated or substituted.
  • FB_AsciiDeviceCM. This reusable CM category (§3.3) owns ASCII request/response behavior: configurable terminator framing, one-outstanding-request state machine (SendRequest → await → response-reaction extension), response timeout ⇒ fault with a §8.8 band code, bounded reconnect via the channel, and link state published for the HMI (Annex D facet — no new HMI code). Device profiles (a specific sensor or reader) compose it: publish their manual commands (§7.6.1, e.g. Trigger), supply a response parser reaction, and keep protocol strings as Setup parameters verified against the vendor manual — never hard-coded folklore.
  • Device-category CMs — configure first, specialize second. Consistent with the CM philosophy (modules are named for their function, never their vendor — a cylinder CM is not a Festo CM), the reusable categories above FB_AsciiDeviceCM are FB_TcpVisionCM (triggered inspection: configurable trigger command and OK/NG prefixes, publishes judgement + result payload) and FB_TcpCodeReaderCM (triggered read: configurable trigger and no-read token, optional match-code verification, publishes the decoded symbol). Most devices are covered by configuration alone (§3.8-able protocol strings, verified against the vendor manual). A model-specific type (e.g. an IV3 preset) is a thin specialization: preconfigured strings plus reactions only where the device has genuinely special features. Category CMs cover ASCII request/response devices; binary or unsolicited-streaming protocols need a different category (deferred until demanded).
  • Testability. A scripted FB_SimByteChannel realizes the same capability, so device CMs are binding-xUnit-tested end-to-end (request → scripted reply → parse; silence → timeout fault) without any socket or vendor hardware.
  • The connector archetype (§3.15.1) and its link supervision (§3.15.2) sit above this seam unchanged: a TCP connector realizes its open/close/heartbeat operations over an I_ByteChannel capability. The ASCII framing and one-outstanding-request rule are one reusable piece (TC3: FB_AsciiLink) that both the device CM category and an ASCII connector compose; each owner keeps only what is its own — the CM its faults and reconnect, the connector the heartbeat and loss reaction its base provides. A connector is never built on a Control Module base: it is composed inside one (§3.15.1), so exchanging connectors does not change the module tree.

Reason band: TCP/ASCII device CM base 10401–10406 (§8.8 registry). Cross-references: §3.3, §7.6.1, §8.8, Annex D, TC3 §3.15.

Section titled “3.15.2 Link supervision (mandatory for every connector)”

Every connector shall implement a heartbeat and a defined loss reaction:

  • Heartbeat. The connector exchanges a periodic liveness signal (counter echo, keep-alive, or cyclic read) and considers the link healthy only while heartbeats arrive within LinkTimeout (a ParCfg value, §3.8). Linked is FALSE the moment either the session drops or the heartbeat lapses.
  • Loss reaction. On loss, the connector shall drive a configured, defined reaction — HOLD (freeze and wait), ABORT (safe-stop the dependent command), or MODE_STOP (request the owning Unit to stop after cycle) — never an undefined hang. The reaction is a ParCfg choice so the same connector behaves correctly whether it drives a critical motion or a passive scanner.
  • Reason. Loss raises a first-out reason on LinkReason / the module diagnostic: LINK_TIMEOUT (heartbeat lapsed), DEVICE_NOT_READY (session up but device not operable), or DEVICE_PROTOCOL_ERROR (malformed/refused exchange) — Framework band, §8.8 — with the device’s SourcePath. The owning CM adopts it via the normal rollup (§8.2), so a dead robot surfaces as “Loc130.Robot: link timeout (see Annex I)” on the Unit’s view through the same stall walk as any other fault (§6.9), with no per-device diagnostic code.
  • Reconnect. The connector shall attempt reconnection on a bounded backoff while holding the safe reaction, and shall not auto-resume a dependent command on reconnect — resumption is a deliberate sequence/operator step, mirroring the safety re-energize rule (§9.3).

A connector is assembled once via Setup (§3.11) like any reusable sub-tree, injecting its endpoint/credentials from configuration (never embedded — §11.4, §14). Because it presents I_Module semantics, the parent CM’s generated/native cyclic assembly services it every scan so Linked/status stay live, exactly as it services the HAL. The parent adopts a false Linked state through the common diagnostic rollup; a project does not hand-write recurring connector wiring.

A connector renders a link LED (Linked), a last-seen time (LastSeen, §2.7), the live LinkReason line, and a reconnect action (release-gated, §7.6) — the same generic tile/detail pattern, so no per-device screen is built.

Cross-references: §3.6/§10 (HAL is for I/O; connectors are for networked devices), §3.11 (Setup wiring), §8.2/§8.6 (rollup, System alarms), §9.3 (no self-resume), §14 (endpoints/credentials).

The standard moves recipes down (§3.8). It must equally move part identity and results up. Production cells commonly do this — data-tag/carrier access raising per-workpiece part events, or RFID reads bound to test results — but rarely as a contract. This section defines one: a typed part context, a source-agnostic carrier, and a fixed set of part-lifecycle events.

A workpiece is represented by a typed record carried by the Unit (and, for multi-station lines, handed between Units):

TYPE ST_PartContext : STRUCT
Uid : STRING(64); // serial / VIN-like unique id ("" if no part)
Present : BOOL; // a part is in the station
CarrierKind : E_CarrierKind; // RFID | DATAMATRIX | BY_POSITION | HOST
Result : ST_PartResult; // accumulates this station's outcome
Parents : ARRAY[1..MAX_GENEALOGY] OF STRING(64); // genealogy: consumed components
END_STRUCT END_TYPE
TYPE ST_PartResult : STRUCT
Verdict : E_Verdict; // NONE | OK | NOK | REWORK
ReasonCode : E_Reason; // first NOK reason (reuses §8.8 vocabulary)
Records : ARRAY[1..MAX_RESULTS] OF ST_MeasRecord; // measured values (test cells)
StationPath : STRING(255); // canonical path of the producing station (§4.8)
Stamp : DT; // synchronized timestamp (§2.7)
END_STRUCT END_TYPE

ST_PartResult reuses E_Reason (§8.8) so a NOK verdict carries the same reason vocabulary as a fault — the thing that stopped the part is named identically whether it halted the machine or just failed the part.

3.16.2 The carrier is source-agnostic (like the recipe provider)

Section titled “3.16.2 The carrier is source-agnostic (like the recipe provider)”

A module reads/writes part data through an injected logical I_PartCarrier capability, mirroring I_RecipeProvider (§3.8) so the transport — RFID/data-tag, Data Matrix scan, position-tracked host lookup, or MES query — is configuration, not code. The capability has two operations: ReadContext(Ctx) : BOOL and WriteResult(Ctx) : BOOL; FALSE reports read/write failure. A binding may realize those operations with an interface or with a generated provider handle and typed routines (§3.2).

A failed read shall fault the consuming module with CARRIER_READ_FAILED, a failed write with CARRIER_WRITE_FAILED, and a Uid that does not match the expected part with PART_ID_MISMATCH (Framework band, §8.8) — never a silent continue on a missing or wrong identity.

3.16.3 The four canonical part-lifecycle events

Section titled “3.16.3 The four canonical part-lifecycle events”

A Unit’s mode chain (§6.2) shall raise exactly these events at defined points, so every station reports a part’s progress identically:

Event Raised when
EVENT_PART_RECEIVED part identity confirmed at station entry (after ReadContext)
EVENT_PART_PROCESSING_STARTED the processing/test sequence begins
EVENT_PART_PROCESSED processing completes — carries Verdict (OK/NOK/REWORK)
EVENT_PART_PROCESSING_ABORTED the part leaves without a valid result (fault/abort/manual removal)

These are the in-PLC events; their mapping to MES/ISA-95 is §11.6. Result write-back (WriteResult) shall occur before EVENT_PART_PROCESSED so the carrier and the host agree.

The Unit tile shows the live part Uid, Present, and current Verdict; the detail view exposes the result record and genealogy. As everywhere, this renders from the self-describing model with no per-station wiring.

Cross-references: §3.8 (recipe provider — the symmetric pattern), §2.7 (timestamps), §8.8 (shared reason vocabulary), §11.6 (host mapping), §14 (carrier/host data is third-party input — validate per secure-coding).

3.17 Additional modes and extension control

Section titled “3.17 Additional modes and extension control”

§3.4 defines five baseline modes. Real cells run more — the reference station adds Capability and Adjustment — so the Core transport contract appends these two optional modes explicitly.

  • CAPABILITY — a capability/Cmk–Cpk study: the Unit runs a defined, repeated cycle collecting measurements for machine- or process-capability assessment, outside normal production routing. Used at commissioning and re-qualification.
  • ADJUSTMENT — a guided setup/teach mode for tuning positions, offsets, and forces between changeovers, without running production.

Both are added to E_Mode (framework band) and behave like any other mode: a Unit advertises support through _M_Supports (§3.4, §3.7), so the mode cascade and graceful rejection of an unsupported mode (§3.7) apply unchanged, and OnModeChanged/OnModeExit (§3.14) handle entry/exit.

Extension control. E_Mode ordinals are an append-only PLC↔HMI transport contract. A new mode therefore requires a coordinated Core contract revision: append the enum value, increase the declared mode count, add the HMI label/icon and policy entry, define its PackML mapping, and perform the compatibility/version review of §1.5. A project or downstream library shall not silently add a private ordinal and claim generic-client compatibility. The Unit still implements the mode’s continuous chain _M_<Mode>Chain (§6.2), advertises it in _M_Supports, and reacts in OnModeChanged (§3.14); it reuses the normal handshake and diagnostics.

Cross-references: §3.4 (baseline modes & _M_Supports), §3.7 (cascade & rejection), §3.14 (OnModeChanged/OnModeExit), §6.2 (mode chains), §11.7 (PackML Unit-Mode mapping).


  • A deployed application PLC project name shall be SolutionName_PLC, matching the controller name in the electrical schematic. Framework libraries, reusable-module libraries, and test projects use their published library/gate identities instead.
  • Toolchain version and all libraries (system, standard, vendor) shall be pinned; local library references are not permitted (§2.2).
  • Documentation format: reStructuredText; project Company/Title/Version/Author/Description fields populated.
  • Platform project/solution settings (symbol download for §3.10, boot behaviour, runtime ports) are binding-level — TC3 §4.1.

An application folder tree shall answer “which deployed module owns this?” before “what kind of artifact is this?”. It follows the physical/instance tree, not global POUs, DUTs, Sequences, or fixed-tier buckets. Every project object has exactly one structural owner: 00_System, one root Unit branch, or a descendant module inside that branch.

00_System // MAIN, raw I/O, safety aliases, tasks, shared infrastructure
01_<RootUnitName> // one deployed root Unit and its project engineering data
├─ Release // cross-module/mode-entry permissives and release reports
├─ Recipes // owner-local model/recipe catalog, when present
├─ Io // approved I/O catalog and fieldbus publication, when present
├─ Sequences // only when the tool stores chains as separate objects
│ ├─ Mode // this Unit's continuous mode chains
│ └─ Sub // this owner’s private sub-sequences
├─ <ChildUnitName> // recursion: same ownership layout
├─ <EquipmentModuleName> // owner-local command chains and children
└─ <ControlModuleName> // project-owned leaf/HAL adaptation, if any
02_<NextRootUnitName> // peer root; never a synthetic super-root

Role folders are permitted inside an owner branch; an application-wide Modes or Commands folder is not. If a platform stores methods under their owning FB, those methods stay there—do not create forwarding POUs merely to manufacture folders. Reusable library types are not deployed instances and therefore do not pretend to be an application tree: a library may group a small public surface by stable artifact kind, or a larger family by type with type-local Data, Simulation, and sequence objects. In both cases the owner/type relationship shall remain unambiguous, and the executable aggregate test runner remains outside the runtime library (§5.7).

Project-specific composition, concrete mode sequences, cross-module/mode-entry release policy, recipe catalogs, I/O identity, and deployment adapters belong to the owning application branch. A genuinely reusable module type and its simulation belong in a reusable library (§3.11); copying its implementation into every instance folder defeats O1/O4. A generic Unit implementation may be offered by a library only as an explicit, documented, extendable/replaceable choice—not as hidden final project behavior (§3.4).

MAIN(PRG) is linked to the PlcTask and is only the composition/call root: it initializes shared infrastructure and calls each root Unit’s Cyclic() in the defined scan order (§10.2.1). It does not own child sequence logic or channel assignments.

Deliberate non-adoptions. Location-owned folders and distinct Mode/Command/Sub chain roles are common to several equipment-software conventions and are adopted here on their own merits. Fraktal does not adopt the patterns that usually accompany them: per-step command/error wrappers repeated in every step, a paired <X>Unit + <X>Extension object per module, an add-on object per optional concern, or PLC code deciding HMI visibility. The lifecycle is single-sourced (§2.2), optional concerns use §3.14 hooks or a narrow injected interface, and the HMI derives presentation from published capability/release data (§3.13).

One or more root Units per program (§3.1a). A PLC program shall host one or more root FB_Unit instances — one per independently-controlled entity (a station, a conveyor system, a sub-line). Roots are peers: each owns its own mode, cycle, recipe/model identity (§3.1b), and diagnostic rollup, and there is no shared super-root in PLC code. MAIN holds them in a fixed root collection and ticks each every scan; the folder tree gains one 0N_<UnitName> branch per root. This is the same recursion as any nested Unit — a root is just a Unit with no parent — so nothing in the contract changes; what changes is that “the tree” is formally a forest, and the HMI (§3.13) may render the whole forest (all roots) or be scoped to one root. 00_System remains single (one clock, one safety project, one alarm spine serving all roots).

Object Prefix Object Prefix
Function F_ Structure ST_
Function Block FB_ Enumeration E_
Method (application-specific public implementation) M_ Alias type T_
Method (non-public) _M_ Union U_
Property (implementation) P_ Interface I_
Action A_ GVL GVL_
Program PRG_ (except MAIN) Parameter list PL_

The M_/P_ prefixes apply to application-specific implementation members where the binding has methods/properties. Standard-defined logical operations/data retain their canonical contract names (Start, Stop, Setup, SetMode, Name, State, Diagnostic), and lifecycle extensions retain the §3.14 OnX names. This keeps the logical API identical across bindings while still making local extensions recognizable.

  • Ordinary variables and object instances shall not carry type prefixes (no Hungarian). Use Clamp1 : FB_ControlModule, not fbClamp1. The type is visible in IntelliSense/mouseover.
  • Interface tags (VAR_INPUT etc.) shall not be prefixed to denote declaration type or usage; group related signals into a named structure instead (Commands.Open, Status.Closed).
  • Three access-semantic markers are retained in bindings that provide these constructs because they describe access, not data type:
    • p prefix for pointers, r for references, i for interface instances (pData, rHal, iChild);
    • leading _ for symbols mapped to %I/%Q/%M, marking the HAL/hardware boundary.
  • A leading _ on internal VAR-block members is permitted (so migrated legacy code stays conformant) but not required.
  • Local names shall not shadow globals.
  • Status variable: adjective(opt) · noun · number(opt) · past-tense verb → ClampClosed, UpperValve1Opened.
  • Command variable: present-tense verb · adjective(opt) · noun · number(opt) → CloseClamp, OpenUpperValve1.
  • Constants: UPPER_SNAKE_CASE, ≤12 consecutive capitals (BUFFER_SIZE, EVENT_PARTS_MISSING).
  • Structure names use the ST_ prefix and enumeration names the E_ prefix; redundant Struct/Enum suffixes are not used. Enums carry {attribute 'qualified_only'}.
  • Message/event constants use the EVENT_ prefix; specific ERR/WARN/INF prefixes only where the message class must be fixed.

Where a device is named in the electrical schematic, the software shall use that exact name above every other rule in this section (VLV01, not Valve01).

4.8 Local segment and canonical qualified-identity rule

Section titled “4.8 Local segment and canonical qualified-identity rule”

A module record’s local service-hierarchy segment shall equal its local PLC instance/schematic name. Its published Status.Name shall be the stable qualified Fraktal identity: the root’s local name, followed for each nested module by . and that child’s local name (for example PneumaticPress.PressRam). The root’s declared name is therefore both its local segment and qualified identity; a nested child’s setup assembles the qualified identity while its containing PLC member supplies the local segment. The final segment of Status.Name shall equal the record’s local segment. A local module name shall not contain .; the dot is reserved as the identity-path separator. This keeps diagnostics, HMI paths, schematics and every transport projection identical without mistaking a binding reference/handle alias for another module instance.


  • VAR_EXTERNAL is not permitted (it breaks modularity/reuse).
  • VAR_TEMP only for single-scan temporaries in programs/function blocks; TwinCAT does not permit it in methods. Method-local temporaries use VAR; VAR_INST is for method variables that must persist across scans; VAR_STAT requires justification.
  • Declaration order shall be: VAR CONSTANT → VAR_INPUT → VAR_IN_OUT → VAR_OUTPUT → VAR → VAR_TEMP → VAR_INST → VAR_STAT.
  • Permitted attribute keywords: RETAIN, PERSISTENT, CONSTANT (order preserved as above).
  • Identifiers shall not equal a binding keyword, case-insensitively. In the TwinCAT binding this includes function/operator names such as ACTION, LOG, MIN, MAX, R, S, and data-type aliases such as DT/TIME; use semantic names such as Gate, AuditSlot, Minimum, Maximum, and DeltaMs.
  • Declarations shall be laid out in tab-aligned columns: name · allocation (AT %…) · type · init · comment.
  • Thematically related variables shall be grouped in a block with a header comment and a trailing blank line.
  • Keywords shall be UPPERCASE (IF, THEN, END_IF); enable editor auto-correction.
  • Prefer a bounded FOR over WHILE/REPEAT; avoid unbounded loops in cyclic code.
  • Conditions shall be explicitly parenthesised. A guard that protects a handle/reference dereference shall use the binding’s proved short-circuit operator where available ([TC3]: AND_THEN/OR_ELSE) or nested guards; the protected access shall never be evaluated after an invalidity check fails.
  • // comments are permitted in declaration sections.
  • No local library references; system and vendor libraries pinned with their dependencies.
  • Each implementation unit should be independently testable; cross-module communication goes through declared logical capabilities/structures, not globals.

To stay approachable from any background, the standard separates framework from application logic, and that split decides which IEC 61131-3 language may be used.

  • Framework language is binding-defined. A binding shall implement the authoritative lifecycle, capability registry, step-chain engine, permission/interlock container, diagnostic/alarm handling, and Self-Description Service in the language/mechanism that its platform can generate, lint and test most reliably. [TC3] uses ST and OOP (FB_init, interfaces, methods and inheritance; TC3 §3.11). [AB] uses generated AOI/routine/UDT composition and Ladder/ST where appropriate (AB §3.14). Core conformance depends on observable behavior and machine-checkable single ownership, not IEC OOP availability.
  • Application logic is the author’s choice:
Application logic Languages allowed Most natural
Sequences / step actions (§6) SFC, ST, LD SFC
Permissive / interlock conditions (§7.2) LD, ST, FBD/CFC LD
Manual-function release (§7.6) LD, ST, FBD/CFC LD
Alarm trigger conditions (§8) LD, ST, FBD/CFC LD
Control Module device logic (debounce, invert, simple on/off) ST, LD either

Regardless of language, application logic shall plug into the fixed contracts — the §6.1 handshake, the §6.5 step record, and the §7.2/§8.8 condition record (index + description + ReasonCode) — so diagnostics work identically (§6.9). A CI/lint check shall enforce this. FBD/CFC are blessed only for boolean condition networks and continuous control; teams should keep to the smallest language set that fits, since each added language adds review and tooling burden.

When SFC is selected, it shall be a genuine SFC implementation: the operational logic belonging to Nxxx (command issue, awaited Done, decision/condition evaluation, result handling, and that step’s transition result) shall be visible in that step’s action/transition. A chart whose actions only publish an ActiveStep number while an external ST CASE ActiveStep OF contains the complete sequence is an ST state machine with an SFC visualization, not the default SFC form, and shall not be presented as the SFC reference.

5.6 Defensive coding (input & bounds validation)

Section titled “5.6 Defensive coding (input & bounds validation)”

A module shall validate inputs before acting on them. This is both a reliability rule (bad data faults cleanly at its source instead of crashing a downstream movement) and a security control (§14.2).

  • Command & enum inputs. A received command shall be checked against the module’s supported set; an out-of-range or unsupported value is rejected with a ReasonCode (§8.8), not silently ignored or run through a default action.
  • Array indices & bounds. Indices into arrays, step tables, and task lists shall be bounds-checked before use — the reference CheckBounds / F_CheckTaskIndexBounds pattern is the canonical form. Per the drafting rules (§5, E031), the loop index is never written inside a FOR loop.
  • Motion & physical targets. A motion target, force, or speed shall be validated against the axis/device limits (held in the CM/driver, §10.3, §10.6) before the command is issued — the F_CheckMoveValid pattern — so an unreachable or unsafe target is refused, not attempted.
  • External payloads. Recipe/host (§3.8, §11.4) and carrier/part data (§3.16) are already validate-before-load; this rule generalizes the same discipline to every input boundary.
  • Fail-safe defaults. Every CASE/IF that selects behaviour shall define a safe, explicit fallback (fault, hold, or refusal), never an implicit no-op that silently stalls a chain — this keeps the stall walk (§6.9) able to explain why nothing advanced. A guard clause is already an explicit fallback when the result is initialized fail-closed and the branch terminates with RETURN; an IF that only conditionally appends a diagnostic or performs an optional bounded update likewise needs no meaningless empty ELSE. CASE dispatchers still require an ELSE, because an unknown selector is an input boundary. The lint gate shall check these semantic forms rather than require syntactic ELSE noise on every conditional (O1/O9).

Cross-references: §3.8/§3.16/§11.4 (payload validation), §8.8 (reason on rejection), §10.3/§10.6 (limits live in CM/driver), §6.9 (defined defaults keep diagnostics valid), §14.2 (secure-coding).

5.7 Automated testing (unit & integration)

Section titled “5.7 Automated testing (unit & integration)”

The CI gate of §5.5/§6.8 checks static conformance (naming, step/condition records, contract usage); it does not prove a module works. Because the standard’s effort model is “standardise once per reusable module type” (§1.1 O1, §6.9), verification belongs at the same level: each reusable type carries an automated test suite, run against simulation, so the type can be reused or refactored (§3.11) behind a regression net instead of being re-proven by hand.

  • Framework & tooling. Tests shall be written with the binding’s xUnit framework and executed in CI by its headless runner, which emits JUnit-format results the merge gate consumes alongside the lint checks (§6.8) — [TC3]: TcUnit / TcUnit-Runner, TC3 §5.7. Reusable suites may ship beside their library sources, but the aggregate test runner is an executable test application and shall not be packaged as a runtime library or deployed with the machine application.

  • Run against the HAL, not hardware. Suites shall exercise the module through its HAL in simulation (§2.6, §10), so they run on any build agent with no rig. This is the second reason simulation is mandatory (§1.1 O6): it is what makes the code testable. Each type should ship a small sim plant model (e.g. FB_CylinderSim with travel time) alongside its suite, shared by the unit-test framework and virtual commissioning, so tests exercise realistic dynamics instead of hand-toggled bits.

  • Sim-only force hooks. Interlock/force test hooks (e.g. SimForceInterlock) shall exist only under the SIM build configuration and be compiled out of release builds — every §7/§9 reaction is testable, and the bypass can never ship.

  • What every module type’s suite shall cover:

    • the handshake (§6.1): Execute → Busy → Done on success; Error/Aborted on the relevant faults; idle after Execute drops;
    • the first-out diagnostic (§6.9, §8.8): a forced fault (e.g. a sim feedback withheld) yields the expected ReasonCode and SourcePath — the diagnosability the standard promises is itself under test;
    • the interlocks/permissives (§7): a dropped permissive produces the defined safe reaction and the right reason.
  • Integration tests assemble a small sub-tree in simulation and assert the rollup: e.g. the Annex B clamp EM with a sim cylinder withheld must surface CYL_NOT_EXTENDED @ ClampStation.CylB through GetFaultSummary (§8.2), proving the cross-tier walk (§6.9) end-to-end.

  • Scope discipline (NG2). Tests live in the type’s test suite, against sim — never as assertions sprinkled through application step bodies. Testing therefore protects the low-effort objective (§1.1 O1): correctness is proven once per type, not re-checked per step or per instance.

  • Conformance test checklist (normative). “Suite is green” is meaningful only against a defined bar. A module type may claim conformance only when its suite covers every applicable row below; rows are cumulative by tier. Each ✔ is at least one test case asserting the exact expected outcome (reason codes by value, paths by string):

# Required case All types Composite (EM/Unit) Connector-fronted (§3.15) Unit
T1 Handshake completes: Execute→Busy→Done; idle after Execute drops (§6.1) ✔ ✔ ✔ ✔
T2 First-out on forced fault: expected ReasonCode and SourcePath (§6.9, §8.8) ✔ ✔ ✔ ✔
T3 Interlock/permissive reaction: output withheld + right reason (§7) ✔ ✔ ✔ ✔
T4 Abort path: Aborted reported, safe state reached, no auto-resume (§6.1, §9.3) ✔ ✔ ✔ ✔
T5 Recipe failure: invalid/partial ParCfg faults with RECIPE_INVALID, never mis-runs (§3.8) ✔ ✔ ✔ ✔
T6 Cross-tier rollup: child first-out adopted verbatim via GetFaultSummary (§8.2) — ✔ — ✔
T7 Link loss mid-command: adopted as module fault; bounded reconnect; no self-resume (§3.15) — — ✔ —
T8 Mode lifecycle: unsupported mode rejected gracefully; child cascade + Stop() on rejection (§3.7) — — — ✔
T9 Stall walk: a stalled step names the awaited module or the first FALSE condition record (§6.9(b)) — — — ✔
T10 Gate/report equivalence: each Unit action accepts iff its release report is Released; custom mode-entry conditions are enforced and listed (§7.8) — — — ✔

A reusable module type is “done” when every applicable row is green in CI; anything less is not a conformance claim. Rows T1/T4 — and the T2/T6/T7/T10 mechanisms (lifecycle, first-out stamping, verbatim rollup, link supervision/backoff, and the Unit lifecycle consuming its own release result) — are satisfied by the binding’s authoritative framework/generator (§2.2) and proven once in the fraktal-core base suite. A generated-composition binding also proves that every concrete type contains exactly one generated lifecycle assembly. A type’s suite re-proves T2/T3/T5 and its tier rows with the type’s own reasons and source paths; a Unit that adds mode-entry records shall exercise at least one such record through T10. Types otherwise shall not re-test framework-owned rows—verification, like standardization, is paid once at the level that owns the behaviour (§1.1 O1). (Worked coverage: Annex H = T1–T3, T6 for the cylinder/clamp; Annex I §I.14 = T1–T5, T7 plus the planner/resolver cases.)

Cross-references: §1.1 (O1 per-type effort, O6 simulatable), §2.2/§2.6 (framework library, simulation), §3.11 (per-type reuse), §6.1/§6.9/§8.2 (handshake, first-out, rollup under test), §6.8 (CI gate this extends), §1.5 (conformance).


6. Command Execution & Sequencing (flow control)

Section titled “6. Command Execution & Sequencing (flow control)”

Flow control uses a PLCopen-style command/handshake model as the baseline. A PackML (ISA-TR88.00.02) state machine is an optional overlay (§6.6), not a requirement. The Unit’s continuous run is itself a §6.1 command: Start issues it, Stop completes it after the current cycle, and abort/fault land in the same terminal states — one lifecycle at every tier including the top, so command timing (§8.11.4) and the reset rule need no Unit-special case (O2, O4; FB_UnitBase).

Naming follows PLCopen so the interface feels native to programmers from any platform (Siemens, Rockwell, Beckhoff, CODESYS): commands use Execute, Busy, Done, Error, ErrorID, Abort, Aborted. A legacy return-code transition (_retVal = OK) is expressed as Done; a legacy numeric error code is carried by the PLCopen ErrorID output (§8.8).

6.1 Command execution model (PLCopen handshake)

Section titled “6.1 Command execution model (PLCopen handshake)”

Every command — a CM device command or an EM command — runs through one PLCopen-style handshake. The interface signals are:

Signal Dir Meaning
Execute in rising edge starts the command; ParCmd latched on this edge
Abort in requests a controlled abort
Busy out command in progress
Done out completed successfully (OutCmd valid)
Error out command failed
ErrorID out numeric reason (value of E_Reason, §8.8)
Aborted out command was aborted
ExecState out single derived state for HMI/Self-Description Service: E_ExecState = READY/BUSY/DONE/ERROR/ABORTED

Lifecycle: the caller checks Done = FALSE AND Busy = FALSE (target READY), writes ParCmd, selects Command, and sets Execute := TRUE. The module goes Busy, latches ParCmd on the rising edge, then on success publishes OutCmd and raises Done; a fault raises Error + ErrorID; an abort raises Aborted. The caller treats Done as the step transition, clears Execute, and the module returns to READY.

// Step action issuing a command to a child (PLCopen handshake):
IF NOT Clamp.Busy AND NOT Clamp.Done THEN
Clamp.ParCmd.Force := Recipe.ClampForce;
Clamp.Command := E_ClampCommand.CLOSE; // the type's own command enum (§3.2)
Clamp.Execute := TRUE;
END_IF
IF Clamp.Done THEN
Clamp.Execute := FALSE; // Done advances the step (§6.5)
END_IF
IF Clamp.Error THEN
// divert to the chain's error handling; reason is in Clamp.ErrorID / Diagnostic
END_IF

Timeout and first-out reason. Every command shall carry a timeout (from ParCfg). While Busy, the module shall publish Status.Diagnostic (§6.9) — the first condition preventing completion: the first FALSE interlock/permissive (with its §7 description), or the awaited sub-result. On timeout the module raises Error and promotes that diagnostic to ErrorID. This is the Single-High / first-out rule of §8 applied per command, and it is what lets a stalled step always answer “why” (§6.9).

Held — a suspended command is not a failed one. An interlock is by definition a condition that must hold during motion (§7.2), and losing one is frequently expected operator behaviour rather than a defect: releasing a hold-to-run or two-hand control is the designed way to stop a movement. A module shall distinguish these from failures. It shall publish a Held flag, orthogonal to the terminal states, that is TRUE while the module is BUSY, has withdrawn the outputs of the affected function, and is deliberately not progressing because a named condition is unsatisfied — the ISA-88/PackML HELD notion. While held, the module shall publish that condition as its Diagnostic at LOW severity, shall not raise Error, and shall not open a MANUAL_RESET event (§8.3(b)): there is nothing to reset, because progress resumes on its own when the condition returns. A parent shall roll a held child up the same way it rolls up a fault (§8.2) — adopting the child’s reason and SourcePath, as information rather than as an error — so a suspended chain explains which module waits on which condition instead of expiring into a generic stall (§6.9). Held is deliberately not an E_ExecState ordinal: that enumeration is transport contract (§3.10(a′)) and its ordinals shall not be renumbered. A condition whose loss genuinely indicates a defect (a lost feedback, an exhausted travel timeout, a process value out of range) remains a fault; HELD is for conditions the operator or the process is expected to restore.

6.2 Unit mode sequence (ModeHandler) — continuous step chain

Section titled “6.2 Unit mode sequence (ModeHandler) — continuous step chain”

A FB_Unit runs the active mode’s sequence as a step chain that runs continuously from Start to Stop. SFC is the default and recommended implementation; ST or Ladder are permitted (§6.8) and behave identically because they share the same contract:

  • the chain uses the standard step-chain contract and binding engine, whatever language implements it;
  • steps are numbered in increments — N000 init, N100, N110, …, N999 finish — leaving gaps for insertion;
  • each step’s action issues commands (§6.1) to child modules; the transition to the next step is the awaited command’s Done;
  • the finish step loops back to N000, so the mode sequence cycles until Stop is requested — matching the ModeHandler “runs until Stop” lifecycle of §3.4.
N000 (init) ──Done──▶ N100 (start child unit)
N100 (start child) ──Done──▶ N110 (wait child done)
N110 (wait done) ──Done──▶ N999 (finish)
N999 (finish) ──Done──▶ N000 (loop)

6.3 Equipment Module commands (CommandHandler)

Section titled “6.3 Equipment Module commands (CommandHandler)”

An FB_EquipmentModule exposes discrete commands; each command is itself a short step chain that completes (it does not loop):

  • individually triggerable, including manually in MANUAL mode, subject to release (§7.6);
  • runs the matching action to Done, Error, or accepts Abort;
  • adds no device logic — it only sequences CM commands through the §6.1 handshake.

A FB_ControlModule executes a primitive command bound to the HAL using the same handshake, and publishes cyclic status (OutImm) every scan. Example: a separator/stopper CM exposes SEPARATE and OPEN_CLOSE, sets OutCmd.SeparateOk when Done, and carries live input/output states in OutImm. It never sequences other modules.

  • Init step N000, finish step N999; user steps in increments of 10 or 100.
  • Each step shall carry a step record — StepNo, StepName, Awaiting (references to the child command(s) it issued), and ExpectedTime — feeding the diagnostic contract of §6.9 and the cycle-time profile of §8.11.4 — one record, two payoffs: diagnosis and measurement (the record also carries the step’s E_TimeClass, §8.11.4(f)). ExpectedTime is optional and defaults to the awaited command’s timeout (the longest, for multiple), so stall detection needs no per-step tuning; set it explicitly only when a step legitimately runs longer.
  • The standard transition is the awaited command’s Done; an Error diverts to the chain’s error handling. Step advancement uses PLCopen status, not ad-hoc conditions.
  • Chains are reusable and shall be side-effect-free except through the child commands they issue.
  • Parallelism uses chain branches; persistent parallelism is a signal to split CMs across EMs (§3.5) rather than over-branching.
  • Decisions, jumps (skip/retry), and parallel fork/join are covered in §6.10; all route through the step record so the stall walk stays valid.

PackML (OPC 30050) is optional and binding-qualified. A site that needs OMAC line coordination may additionally expose a PackML FiniteStateMachineType mapped from the Unit’s mode + ExecState (for example BUSY → Execute, DONE → Complete, ERROR → Aborted). Conformance to this standard does not require it; the native ExecState/mode model of §6.1 and §3.4 is the default exposed through the Self-Description Service (§3.10).

6.7 Sequence ownership, roles, and organisation

Section titled “6.7 Sequence ownership, roles, and organisation”

Every chain shall have one module owner and one writer of its step state. Its role is one of:

  1. Mode sequence — owned by a Unit, selected by that Unit’s active mode, and continuous until Stop (§6.2). Each supported mode has a separately named chain behind a thin dispatch router.
  2. Command sequence — owned by an EM (or the primitive device logic of a CM), finite, and externally addressable only through that module’s §6.1 command handshake (§6.3–§6.4).
  3. Private sub-sequence — a finite owner-local chain reused by one or more mode/command chains. It has private step state but no module identity, public Execute, independent mode, or self-description node; it aborts/resets with its owner and publishes progress through the caller’s §6.5 step record.

A private sub-sequence shall be promoted to an EM when it needs independent commandability, concurrency, lifecycle, recipe ownership, reuse by unrelated owners, or its own diagnostic identity. Conversely, a forwarding sequence that contributes no parameters, release, branching, result, or cleanup shall be collapsed; hierarchy without ownership adds effort without capability (O1/O2).

Extract a private sub-sequence when a coherent chain is used by more than one caller, owns a non-trivial branch/cleanup path, or materially improves reviewability. Do not extract every step. The caller remains the lifecycle owner and allocates a stable step-number window so the active private chain remains visible in CurrentStep, stall diagnostics, and timing. The chain-call graph shall be acyclic; a parent never writes a child’s private step and two chains never command the same child in the same scan.

Folders follow §4.2: Mode/Command/Sub role folders live inside the owning module branch when the tool represents chains as objects. When they are methods, use distinct names and keep them under the owner implementation unit. Lifecycle extensions (OnInit, OnCommandStart, OnCyclic, OnModeChanged, OnModeExit, OnAbort, …) remain separate from step bodies (§3.14); their native access form is binding-defined.

A sequence may be written in SFC (default), Ladder, or Structured Text — whichever a team knows best — per the language policy of §5.5. The language is free because the contract is fixed, not the syntax. Any sequence, in any of the three languages, shall:

  • drive children only through the §6.1 command handshake;
  • advance only on the standard transition (the awaited command’s Done);
  • populate the step record of §6.9 (StepNo, StepName, Awaiting, ExpectedTime).

Guidance: SFC is preferred for multi-step machine sequences (the step/transition structure is visible and self-documents the chain). ST suits data-heavy or highly conditional logic. Ladder suits simple interlock-style or maintenance-facing sequences. A CASE StepNo OF skeleton in ST and a step-coil pattern in LD both satisfy the same contract as native SFC steps, so diagnostics (§6.9) are identical regardless of language.

For an SFC+ST split, the SFC chart shall be the only progression/token owner and each non-stored ST step action shall contain that step’s application behavior: populate the step/condition records, issue or complete the child handshake, evaluate decisions/timers, and set the transition result. An owner adapter may run the chart and bridge framework services that the separate SFC POU cannot legally access; the OnCommandStart lifecycle extension may own the reset edge. The adapter shall not select application behavior through CASE ActiveStep OF, reproduce the chain, or hide commands and waits behind one action-specific forwarding method. A token-only SFC plus an external active-step selector is therefore non-conforming as a claimed SFC implementation, even if the chart is the only writer of the numeric token.

A reused finite sub-sequence may retain one private step state when the owning chain invokes it as a single, explicitly named composite step (§6.7), provided its detailed private progress is projected through the owning Unit’s normal §6.5 step record. This is reuse, not a license to hide the mode chain. The Fraktal/TC3 pneumatic-press HOME, CHANGEOVER, and AUTO chains are the reference implementation, written as the ST CASE StepNo OF skeleton on FB_SequenceBase (Part II TC3 §3.5); their per-step actions issue the child handshake, evaluate waits/decisions/timers, and set the shared transition result, so the diagnostics are identical to a native SFC per §6.8.

To keep all three languages cheap and consistent, each binding provides: (a) one shared step-chain engine that handles step records, the Done/Error transition, and the §6.9 diagnostic walk, so no author re-implements flow control; and (b) a template per supported language — an SFC chart, an ST CASE StepNo OF skeleton, and an LD step-coil rung pattern — so authors only fill in step actions. A CI/lint check shall verify that any sequence, whatever its language, populates the step record and advances only on the standard transition, so no language can quietly bypass the contract the diagnostics depend on.

The reference implementation of (a) is FB_SequenceBase [TC3]: a sequence POU extends it and receives the active step token (_step), the step record (M_Step), condition waits (M_Await), run-style pacing with a one-shot issue latch (M_TryIssue), declared process delays (M_Delay), the part/decision/completion forwards, and the shared transition result _retVal : E_StepResult. Each step action is _retVal’s only writer; at the end of the step it calls M_Advance(OnAdvance := <next>) (with optional OnJump<n> targets for §6.10 branches), which commits the transition — advancing to the mapped step and clearing the step-scoped latches so the next step re-arms, or holding on NONE. The owning module implements I_SequenceHost (written once in FB_UnitBase) and injects itself at the sequence’s Setup; the host bridge carries framework plumbing only — the application’s command, wait, decision, and transition logic stays visible in each CASE _step OF branch (§6.8). A native graphical SFC would place the same action bodies on its steps and read _retVal on its transitions; the ST skeleton is the shipped form because it is plain reviewable text and needs no editor-generated chart XML.

Lifetime of the shared result. _retVal shall be a one-scan signal: the active step’s action writes it, the chart’s transition reads it in the same PLC cycle, and it shall be cleared before the next cycle’s step actions run. Otherwise a result produced by one step re-fires the transition of the step it just entered. Who performs that clear depends on who owns the transition:

  • ST chart — M_Advance is the transition. It commits and clears in one call, so the requirement is met with no extra step.

  • Chart language (SFC / LD / FBD) — the runtime evaluates transitions, so nothing inside the chart is positioned to clear afterwards. The framework performs the reset: a chain announces itself to its owner when it receives the host bridge, and the Unit base clears every attached chain’s result at the top of each cycle, before it dispatches any step action. Clearing at the top of a scan is equivalent to clearing after the previous scan’s transitions, and it additionally forces every step action to re-assert its own result each scan, making a stale ADVANCE impossible rather than merely unlikely.

    This is deliberately not a project obligation (§1.1 O1). An application that had to remember one call per chart would eventually forget it, and the failure — a transition firing on a result its step never produced — is intermittent and expensive to diagnose. The reference implementation registers the chain in FB_SequenceBase.M_Attach and drives I_Sequence.M_BeginScan from FB_UnitBase, so a project adding a chart in any language writes no wiring at all.

The per-scan clear shall reset the result only. The step-scoped helpers — the M_TryIssue one-shot latch and the M_Delay timer — are cleared on step change (M_ClearTransition), never per scan: re-arming them every cycle would re-issue a child command each scan and prevent any delay from elapsing.

6.9 Step diagnostic contract (resolving the lean-vs-diagnosable dilemma)

Section titled “6.9 Step diagnostic contract (resolving the lean-vs-diagnosable dilemma)”

Lean step bodies and rich per-step diagnostics are reconciled by moving the standardization off the steps and onto the module types — the cost is paid once per reusable module, not once per step.

The current-step card: Step 40 Clamp the part, awaiting ClampStation.CLAMP, awaiting ‘Cylinder B extended’ = FALSE and ‘Working area safe’ = FALSE, expected at most 2.5 s.

The step diagnostic on the HMI: the active step, the command it waits for, the conditions still missing, and how long the step is expected to take.Browser HMI simulation at revision a1163c7 · try it

(a) Self-diagnosing modules. Every module shall, each scan, compute a single first-out reason it is not Done and publish it as Status.Diagnostic — once, in the structure every module shares, so a generic client and the walk of (c) read it without knowing the type; a type shall not copy it into its own OutImm, which holds only the type’s derived facts (§3.12) (fields per §8.8: ReasonCode, SourcePath, Description, Severity, Since) — the first FALSE interlock/permissive (with its §7 description) while Busy, or its timeout/fault (§6.1). Written once per module type, reused everywhere. Each module additionally should retain a small ring buffer of its last N first-out diagnostics (stamped per §2.7, exposed through the Self-Description Service; [TC3]: OPC UA) — shift-change post-mortem without a historian.

(b) Self-describing steps. Each step shall carry the thin record of §6.5 — StepNo, StepName, Awaiting, ExpectedTime. This is the command reference the step already sets, plus a name: near-zero extra effort, and language-agnostic (§6.8). A step that waits on a plain condition rather than a module shall additionally register each such wait as a named condition record — _M_Await(n, 'Vacuum OK', VacuumOk), refreshed every scan — so the walk of (c) can name the first FALSE condition (“Step N stalled → awaiting ‘Vacuum OK’ = FALSE”) instead of reporting a blind STEP_STALLED. One line per condition closes the last non-module diagnostic gap (Annex C §C.6).

(c) Automatic diagnostic walk. When a chain has not advanced past a step beyond its ExpectedTime, one generic runtime function composes the reason with no per-step code:

Step {StepNo} {StepName} stalled → awaiting {Module}.{Command} → {Module.Status.Diagnostic.Description}

The owning Unit exposes this as its current stall reason; the HMI (§3.13) shows it on the Unit’s view, where the operator expects sequence state.

A stall is a pending reason (Low severity, published live on the Unit), not a fault: the Unit keeps waiting while naming exactly what it waits for. The fault path is the awaited module’s Error, which the Unit base adopts immediately through the §8.2 rollup — without waiting for the stall timer — so a real failure is never delayed behind a stall guard (FB_UnitBase). Outcome. Steps stay lean; the operator gets a precise root cause; and because the answer comes from the standardized module contract (§3.12, §7, §8) rather than hand-coded step conditions, it is identical in SFC, Ladder, or ST. Standardization effort scales with the number of module types, not the number of steps — which is the whole point.

(d) Raising an error the framework cannot see. Awaits carries the automatic rollup of (c), but only for a step that hands its child to the framework. A step that decides for itself — a command inside an IF or CASE, a rule that lives in the application — is invisible to it, and would hang until the stall guard with nothing naming the cause. Two calls on the §6.8 base close that gap, and both are available in every language (ST, SFC, LD):

// a child commanded behind a guard: adopt ITS first-out, verbatim
IF M_RaiseFromChild(Source := _gauge) THEN
_gauge.Execute := FALSE; // §6.1 drop-reset frees the child to recover
RETURN;
END_IF
// a rule only the application knows: the step defines the whole message
IF _measured > _parCfg.MaxDrift THEN
IF M_RaiseCustom(Reason := PL_ProjectReasons.GAUGE_DRIFT,
DescriptionKey := 'project.error.gaugeDrift',
Severity := E_Severity.HIGH, Category := E_Category.PROCESS,
LinkPath := _gauge.Name) THEN
RETURN;
END_IF
END_IF

Both return TRUE only when a fault was actually raised, so calling them every scan is safe and the IF ... THEN RETURN shape reads the same everywhere. Severity and Category are a proposal: adoption runs the §8.8 rationalization, so a registered reason takes the registry’s priority and category, and the caller’s values survive only for a project band code (10000+) the registry does not know — which is where a message of a deliberately different level belongs.

The reaction is fixed and shall not be varied per step:

  1. Stop. The Unit adopts the diagnostic and enters ERROR, so _M_Dispatch is no longer called and the chain freezes on the raising step — it never advances past a step whose command failed.
  2. Link. The Unit stamps the §3.13 flow-chart row of the active step with ErrorActive and ErrorSourcePath, so the chart marks that step and drills into the module that actually failed — even for a step that passed Awaits := 0.
  3. Re-evaluate, never resume blind. When the ERROR state ends, the Unit clears the row marks and re-arms every attached chain (M_ResumeAfterError → M_ClearTransition). The step-scoped latches — M_TryIssue’s one-shot, M_Delay’s timer, M_RunSub’s latch — go back to their unissued state, so the step re-issues and re-tests its command instead of resuming mid-handshake on a spent one-shot. Whether the chain then continues from that step or restarts from the top is the project’s choice, made in OnCommandStart (§3.14); the framework only guarantees it will not skip.

A project writes none of the plumbing (§1.1 O1): registration, the row stamp, the clear and the re-arm all live in the base. Worked example: FB_ProbeRaiseChain / FB_SequenceRaise_Tests.

(e) Reporting without stopping. Not every message is a fault. A two-hand control released mid-motion, a ram that did not reach when the step already routes to an operator confirmation and a scrap — these are handled conditions with a consequence worth recording. Adopting them would replace a designed recovery with a hard stop; saying nothing leaves the operator with a machine that abandoned a cycle for no visible reason. Three calls, none of which touch the exec state:

// a rule the step states itself
_warned := M_RaiseWarning(Reason := PL_PressReasons.PRESS_TWO_HAND_RELEASED,
DescriptionKey := 'project.warning.twoHandReleasedDuringDoorClose',
Severity := E_Severity.LOW, Category := E_Category.PROCESS);
// a child's own first-out, published verbatim but NOT adopted
_reported := M_ReportFromChild(Source := _pressRam);

Guarantees:

  • Nothing stops. _exec is untouched, _M_Dispatch keeps running, and the step keeps whatever branch it was going to take. This is the whole difference from (d) and shall not be blurred: a condition that must stop the machine belongs in (d).
  • It can never block a restart. The ring entry is an AUTO_RESET come+gone event (§8.3(c)), so AlarmLog.Blocking is unaffected and the next Start is not gated on an operator reset.
  • Once per visit, not once per scan. The base latches the message for the duration of the step visit and re-arms it on commit, so a step body may call it unconditionally every scan (§1.1 O1 — a project shall never have to remember an edge latch for correctness).
  • It stays visible where the operator is looking. The active §3.13 row is marked with WarningActive/WarningKey, and with WarningSourcePath when the message is about a child — so a step that reports a child’s failure is click-through to that child even though it passed Awaits := 0. The mark is cleared when the step is entered again: the chart says what happened on the last pass, not forever.

The HMI resolves a row’s target most-specific-first — raised error, then reported message, then the declared Awaits — and renders a message as a steady mark, never as the error blink.

6.10 Branching, decisions, jumps & actions

Section titled “6.10 Branching, decisions, jumps & actions”

The step model already expresses decisions and jumps directly — a transition may target any declared step, not only the next one — but to keep the stall walk (§6.9) reliable, every branch and jump shall route through the step record (_M_SetStep, or the SFC step itself), so StepNo/StepName/Awaiting always follow the active path.

Decisions (alternative / selection branch). A step evaluates a condition and routes to one of several successors — an IF choosing the next step number in ST, an alternative divergence with mutually-exclusive transitions in SFC:

30: _M_SetStep(300, 'Measure', 'Gauge.MEASURE', T#4S, Gauge);
IF Gauge.Error THEN _M_AdoptChild(Gauge); RETURN; END_IF
IF Gauge.Done THEN
Gauge.Execute := FALSE;
IF Gauge.OutCmd.InTolerance THEN _step := 50; // pass → skip rework
ELSE _step := 40; // fail → rework
END_IF
END_IF

Jumps. A jump is simply a step target that is not the next step — a forward skip (above) or a backward retry. Both are permitted; the target shall be a declared step in the same chain, and a jump shall not leave a child command running — clear Execute and bring affected children to a defined state before jumping.

Bounded retry. A backward jump used to retry shall be bounded by a retry counter; on exhaustion the step shall fault with RETRY_EXHAUSTED carrying the underlying child reason, so a retry never silently masks a real fault:

40: _M_SetStep(400, 'Rework', 'Press.CYCLE', T#6S, Press);
IF Press.Done THEN
Press.Execute := FALSE;
_retry := _retry + 1;
IF _retry <= ParCfg.MaxRetry THEN _step := 30; // re-measure
ELSE _M_Fault(E_Reason.RETRY_EXHAUSTED, 'Rework retries exhausted'); END_IF
END_IF

Parallel branches (fork / join). To run actions concurrently, a step issues several child commands and advances only when all report Done — the dual-clamp step of Annex B §B.3 is exactly a parallel fork/join. Persistent parallelism is a signal to split children across separate EMs for parallel orchestration (§3.5), not to grow long parallel chains.

Actions & action qualifiers. Each step has one action body with two phases: a one-shot entry action (fire the child command on first scan of the step) and a cyclic body (evaluate the handshake/transition). Output behaviour shall be non-stored — the IEC N qualifier — so an output is driven only while its owning step/command is active and released when the step ends. Stored actions (IEC S/R set/reset) shall be avoided: they decouple an output from the step that set it and make “why is this output on?” untraceable, defeating the first-out diagnostic (§6.9). Where a state genuinely must persist across steps, it belongs in a Control Module’s device logic (held through that CM’s own command/state), not in a stored sequencer action.

The result is an expressive chain — decisions, skips, bounded retries, parallel joins — where every position stays visible to the stall walk and every output stays traceable to an active step.

M_Advance is the declaration of a step’s exits, not a convenience. An ST branch shall end with it. Assigning _step by hand reaches the same next step, but the out-edges then live inside whatever conditional produced them, and the property “every non-terminal branch has an exit” stops being checkable — the CI gate proves it today by finding one M_Advance per non-terminal branch (§1.5, §5.7). Keeping the graph in one greppable call per step is what makes a chain readable by scanning the last line of each branch (§1.1 O2) and enforceable without dataflow analysis (§1.1 O9). Unused jump targets are defaulted, so a step with no jump reads M_Advance(OnAdvance := 100); and a step with one reads M_Advance(OnAdvance := 200, OnJump1 := 185); — a jump is then visible at a glance instead of buried among three -1s.

A chart language is different and shall not be forced into it. SFC’s runtime owns the transition, and a Ladder integer state machine moves by writing _step from a rung, which is that language’s native form; neither has a commit point to hang M_Advance on. §6.5 is satisfied for both because M_Step — not M_Advance — is what records the step, so the §6.9 walk and the §3.13 chart are fed identically in every language.

Some sequence decisions need an operator, not a sensor — “remove the NOK part manually or auto-continue?”, “confirm tool change”. The standard defines one typed decision contract so operator interaction is uniform and never hand-built per station.

Station A waiting for an operator decision: The tool is worn. Replace it now or finish the batch? with the buttons Replace now and Finish batch.

An operator decision: the sequence waits until someone chooses.
  1. What the station is waiting for.
  2. The question and its choices, published by the station.
Browser HMI simulation at revision a1163c7 · try it
  • Typed decision request. A step may raise an ST_DecisionRequest — prompt text, an option set, a default option, and a timeout — and wait on it. The HMI (§3.13) renders it generically from that record; the operator’s choice (or, on timeout, the default) is consumed by the chain as the transition, advancing it exactly like a Done (§6.5).
TYPE ST_DecisionRequest : STRUCT
Prompt : STRING(255);
Options : ARRAY[1..MAX_OPTIONS] OF STRING(64);
Default : INT; // option index applied on timeout
Timeout : TIME; // 0 = wait indefinitely
SourcePath : STRING(255); // raising module (§4.8)
END_STRUCT END_TYPE
  • One active decision per root. A root Unit has one mode-chain/step-state writer (§6.7), so its base publishes one active decision slot rather than a second scheduling system. Re-presenting the same request while its step waits is idempotent; a different request arriving before the active one is consumed shall be rejected and logged, never overwrite it. A profile that genuinely permits independent concurrent decision producers may add a bounded FIFO in front of this slot, but the FIFO is an adapter and does not change the HMI contract. Each request carries its SourcePath so the operator sees who is asking.
  • No safety/release bypass. A decision shall not override safety (§9) or manual-release (§7.6); a timeout shall resolve to the safe default, and “continue” options remain gated by the normal releases.
  • Logged. Each decision (the request, the choice, and whether it was operator- or timeout-resolved) shall be logged as an event (§8.7) for audit (§14.3).

Cross-references: §6.5/§6.10 (transitions & branches), §3.13 (generic HMI rendering), §7.6/§9 (release & safety not bypassed), §8.7/§14.3 (event logging & audit).


6.12 Concurrent branches (parallel divergence)

Section titled “6.12 Concurrent branches (parallel divergence)”

A machine with two work positions that run simultaneously and independently — load one while the other presses, weld two joints at once — needs more than one active step at a time. IEC 61131-3 draws this as a simultaneous divergence in SFC; this clause says what it means for the rest of the contract, and gives the form that works in every language.

Sub-chain fork (M_RunPar) Native divergence (M_Step(Branch := n))
Available in ST, SFC, LD — all SFC / LD only (the chart draws it)
A leg is its own FB_SequenceBase instance a set of steps in the same POU
Per-leg step pointer, _retVal, latches inherent — separate instances provided by the base, keyed by branch
Leg written by anyone who can write a chain same, plus Branch := n on each step
Nests yes, without limit one level (a fork sits on a main line)
Reusable leg yes — it is a type no — it is drawing

A project should prefer the sub-chain fork. It is the same answer §1.1 O4 gives everywhere else: a work position is a thing, so make it a type and instantiate it, rather than duplicating its steps in a picture. The native divergence stays supported because a chart is often the clearest way to show two short legs, and because existing charts use it.

500: // both work positions run at once
M_Step(StepNo := 500, StepName := 'project.step.bothPositions', Awaits := 0,
AwaitingLabel := '', TimeClass := E_TimeClass.WORK, ExpectedTime := T#0S);
M_RunPar(Chain := _positionA, BaseStepNo := 600, Branch := 1);
M_RunPar(Chain := _positionB, BaseStepNo := 700, Branch := 2);
_retVal := M_ParJoin();
M_Advance(OnAdvance := 999);

M_ParJoin returns ADVANCE on the scan every leg run this scan reports Done. A composite step (M_RunSub) inherits the leg of the step that runs it, so a sub-chain inside a leg publishes its steps under that leg with nothing to declare — the framework already knows which leg it is in, and a second place to say so is a second place to get it wrong. The leg list is the calls themselves, so there is nothing to register and nothing to keep in step when a leg is added or removed (§1.1 O1). The entry latch is step-scoped: re-entering the fork step later restarts every leg. BaseStepNo offsets a leg’s step records exactly as it does for a composite step (§6.5, §6.7), so the §6.9 walk and the §3.13 chart still read one continuous chain.

Legs drawn inside one POU share the function block, so the framework cannot tell them apart. A leg step declares itself on its own step record:

M_Step(StepNo := 300, StepName := 'project.step.positionBWork', Awaits := 0,
AwaitingLabel := '', TimeClass := E_TimeClass.WORK, ExpectedTime := T#0S,
Branch := 1);
IF M_TryIssue(Steppable := TRUE) THEN ... END_IF
_conRetVal[1] := E_StepResult.ADVANCE; // this leg's transition result

and each leg’s transitions read _conRetVal[n] where the single-threaded line reads _retVal.

Number every leg; none of them is the main line. A simultaneous divergence has N equal legs, so a two-leg fork shall use legs 1 and 2 — not “the main line plus leg 1”. Leaving one leg on branch 0 costs twice: the §3.13 chart draws it as an unindented main-line row and the other as subordinate, when they are peers; and _retVal comes to mean two different things depending on whether you are reading inside the fork or outside it. _retVal is the line before and after the fork; between them there are only legs. The join then reads every leg:

_conRetVal[1] = E_StepResult.ADVANCE AND _conRetVal[2] = E_StepResult.ADVANCE

Branch is an input of M_Step rather than a call before it, so a leg cannot be declared without recording a step, and a step cannot land on the wrong leg because a separate declaration was forgotten (§1.1 O1). It defaults to this chain’s own leg: 0 for a top-level chain, which is the main line, and the index the fork assigned for a chain running as a leg — so neither a main-line step nor a leg written as its own chain ever mentions a branch. An index outside 0..MAX_PARALLEL_BRANCHES faults the chain rather than silently falling back (§5.6).

[TC3] Branch is a defaulted method input, which requires TwinCAT ≥ 3.1.4026. Under the legacy FRAKTAL_TC3_4024 profile the declaration has no default, so a 4024 build passes Branch := 0 at every M_Step call, exactly as it already does for M_ResetBase and M_Advance (see Params/PL_FraktalCompat.TcGVL).

Every step-scoped latch is per branch: the M_TryIssue one-shot, the M_Delay timer, the M_RunSub entry latch, and the §6.9(e) message latch. M_Step selects the leg before any of them, so everything a step action does after its step record is scoped to that leg. This is not an optimisation — sharing them let one leg’s issue consume another leg’s, and let one leg committing a step wipe another leg’s transition result mid-motion.

The re-arm itself moved to M_Step, which is the one call every step of every language makes. A chart language has no commit point to hang M_ClearTransition on, so before this a chart’s M_TryIssue fired once per chart run instead of once per step.

(f) The chart is scoped to the running mode

Section titled “(f) The chart is scoped to the running mode”

Step rows are discovered by visit (§6.5), which is what makes the chart free to author — but discovery has no end of its own. A Unit shall therefore drop its published rows when a mode commits, so the chart shows the chain that is running rather than the union of every chain run since power-up. Within one mode a re-run keeps its rows, so Visited and LastDuration stay meaningful across cycles.

This is also what keeps the bound honest. A row is therefore split by how often each part changes, because 98% of the original 1.16 kB row was strings that almost never did: the live scalars stay in SequenceSteps (25 B), the step’s text is discovered once and served through the §3.10.2 config manifest under the same browse paths, and the error/message text — sparse, since at most a few rows carry one — moves to a small SequenceAnnotations table rather than reserving 633 B on every row for the empty case.

Liveness is published per concurrent leg, not per row: a leg runs exactly one step at a time, so an ActiveSteps cursor indexed by branch is ~10 entries however long the chain is, and cheap enough to stay cyclic. What remains per row is only what a client could not reconstruct by watching — Visited, LastDuration, and the error and message marks. That boundary is deliberate: an HMI polls at a few Hz against a task at kHz, so anything it had to accumulate from observation would drop steps shorter than its own poll interval and lose transient faults. The chart shows what the chain did, not what a client happened to catch (§1.1 O3).

MAX_SEQUENCE_STEPS = 128 then costs ~46 kB per Unit instead of ~145 kB, of which only ~1 kB is read per poll while the chart is open. That is affordable only because the rows are read on demand rather than cyclically (§3.10); raising it further costs linearly in both, and shortening the string fields is the lever if it ever matters. Scoping the chart to the running mode is what keeps a Unit’s actual usage near its longest single chain instead of the sum of all of them.

CurrentStep, the §6.9 stall walk and the §8.11.4 profiler are main-line only. A first-out has to name one step; letting whichever leg ran last overwrite it would make the walk report at random. A leg is therefore timed and guarded on its own §3.13 row — Active, Elapsed, TimedOut per row — which is also what lets the HMI draw several live steps at once and blink only the leg that overran. A leg that must raise a fault still does so through §6.9(d), which stops the whole chain, as it should: one leg failing is a failure of the step.

  • Permissive — a condition that must be met to initiate an action.
  • Interlock — a condition that must be met to initiate and maintained throughout. If it drops mid-action, the affected output/action shall stop immediately. The owning module then applies the explicit classification from §6.1: an expected, operator/process-restorable condition enters HELD and resumes only when that same interlock returns; a defect or non-restorable loss faults. Neither classification permits motion while the interlock is false.

Permissives and interlocks use one identical container type, FB_PermIntlk (ST, framework — written once per §5.5). Each:

  • holds a set of conditions, each a Boolean where TRUE = OK; the object is OK only when all conditions are TRUE;
  • carries, per condition, a condition record — Index, Description, ReasonCode (§8.8), and a Bypassable flag — so the first FALSE condition is exactly the module’s first-out reason (§6.9);
  • exposes: an “all OK” output, a “first failed” output (index + ReasonCode + description), an “at least one bypassed” output, per-condition bypass, and a clear-all.

The condition evaluation is the author’s choice of language (§5.5). The container is fixed; how each condition Boolean is computed may be written in Ladder (the idiomatic form for interlocks — a rung of contacts), ST, or FBD/CFC. The author only has to drive the condition input; the container handles AllOk, bypass, and first-out.

// ST: feed conditions into the container (each with index/description/reason set once at init)
HeatPerms.Cond[1] := TempSensorOk; // idx 1: "Temperature sensor OK"
HeatPerms.Cond[2] := GuardClosed; // idx 2: "Guard closed"
HeatPerms.Cond[3] := NOT EStopActive; // idx 3: "E-stop clear"
( Ladder: the same three conditions as rungs driving the condition coils )
TempSensorOk───────────────────────────( HeatPerms.Cond[1] )
GuardClosed────────────────────────────( HeatPerms.Cond[2] )
EStopActive/(NC)───────────────────────( HeatPerms.Cond[3] )

Either way the gate reads the same:

// Permissive gate at command start:
IF Start AND NOT Cm.Busy THEN
IF HeatPerms.AllOk THEN
// begin Heating
ELSE
// -> Error; HeatPerms.Diagnostic carries the first failed reason + description
END_IF
END_IF
// Interlock maintained while Heating:
IF Heating AND NOT HeatIntlks.AllOk THEN
// halt Heating immediately -> Error, reason = HeatIntlks.Diagnostic
END_IF

Because every condition carries a Description and ReasonCode, a blocked or dropped condition feeds straight into the first-out diagnostic (§6.9) and the message catalog (§8.8) — regardless of the language the condition was drawn in.

Canonical permission/interlock container. The logical container has a fixed public surface so every module uses it the same way. ST_IntlkCond carries Defined, stable description key, Reason, and Bypassable; the bounded condition vector carries the live Boolean values. The derived outputs are AllOk, AnyBypassed, FirstFailed (lowest FALSE, non-bypassed index; 0 means none), and Diagnostic (the first-out record, or ReasonCode = NONE when all pass). Its operations are Define(Index, Description, Reason, Bypassable), gated SetBypass(Index, On) : BOOL, and ClearBypass().

Conditions are declared once during binding-native setup (§3.11); the author’s ST/LD logic drives Cond[i]; the framework evaluates the container cyclically; and the owner reads AllOk to gate and stamps its own SourcePath on Diagnostic. MAX_PERMINTLK_COND is a framework constant (default 16). [TC3] realizes the surface as FB_PermIntlk with methods; [AB] realizes it as bounded UDT/AOI composition. The representation shall not change the index, first-failed, bypass, or diagnostic semantics.

Each condition is owned at the lowest module that has enough semantic context to name and act on it. A reusable type derives its conditions from its HAL, parameters, child contracts, and explicitly injected semantic status—not by reaching into application globals or raw schematic I/O. The application composition root may combine system/domain status, but it does not restate a child’s device condition. Parents aggregate the child’s condition/report; they do not copy its Boolean expression under a second description.

Cross-module collision rules, active-mode entry permissives, and other project policy belong to the owning Unit’s application branch (§4.2), preferably in a visible Release/Permissives object or language worksheet. That project object shall expose named live condition state and append those same records to the Unit’s authoritative release report. Reusable libraries retain only device-intrinsic conditions or explicitly injected generic policy; they shall not hide station-specific release logic.

An aggregate Boolean such as CommonManRelease or AllStartConditionsOk may exist as a convenience, but it shall not be the only diagnostic source. Its constituent ST_IntlkCond records remain available so the gate, first-out diagnostic, and full release report all preserve provenance. A release expression duplicated once for execution and again for explanation is non-conformant even if the two versions initially look identical (O1/O3).

Bypass shall be per-condition and only for conditions explicitly marked bypassable. Any active bypass shall raise the object’s “bypassed” output so the HMI and alarm system can indicate a reduced-safety/diagnostic state.

Summing several discrete conditions into one permissive/interlock shall be avoided where reasonable: each discrete condition keeps its own description so the HMI can name the exact failed condition. Coarse summation destroys troubleshooting visibility.

During commissioning, manual functions and release conditions may be gated behind a commissioning constant (COMM_FLAG) so untested logic cannot drive outputs, and observe the common manual-release condition. These gates shall be removed (or the constant set to production) before FAT/SAT.

7.5.1 Engineering gates are build constants, and they are declared

Section titled “7.5.1 Engineering gates are build constants, and they are declared”

A commissioning/engineering gate is any deliberate, temporary departure from the production configuration: a simulation driver in place of the real one, an unverified electrical mapping held off, untested logic fenced out — and the output-force surface of §10.5.1. Three requirements make such a departure safe to carry in the source tree rather than in a private branch:

  • A gate is a build constant, not a runtime variable. Each gate shall be a compile-time constant of the deployed program, so defeating it requires a source change plus a download — a reviewable, auditable act — and never an online write from an HMI, an engineering client, or any other data path. A gate shall not be exposed as a writable value, and a published mirror of a gate (for observability) shall have no consumer in control logic. A binding may additionally require a compiler define so the gated code is absent from a production build rather than merely disabled (TC3 §7.5).
  • A gate is registered, not implicit. A station shall publish a bounded engineering-gate register: for every gate that is active, a stable name and a localizable description. A gate that is inactive publishes nothing, so a production station’s register is empty and the surfaces the gates control are not merely disabled but invisible to a client (§3.9 — a disabled feature is omitted from the discovery surface, and the client pays no read cost for it).
  • A gate is annunciated for as long as it is active (§7.5.2).

Gates shall be off for FAT/SAT and for production release; §14’s commissioning checklist shall include confirming the register is empty. A deviation that outlives commissioning is a §1.5 deviation and follows §13.

7.5.2 The standing engineering-gate annunciation

Section titled “7.5.2 The standing engineering-gate annunciation”

While any gate in the register is active, the station shall annunciate it. The requirement is deliberately shaped so the indication is impossible to lose and equally impossible to mistake for a machine fault:

  • One event per active gate, raised through the ordinary §8.3 log with ReasonCode := COMMISSIONING_GATE_ACTIVE (§8.8) and the gate’s own description, so each departure is named rather than summarised.
  • Lowest priority, lowest risk class. Severity := LOW and Category := SYSTEM (§8.1). The station is not faulted and production is not impeded: a gate is a statement about how this software was built, not about the process or about safety, and a higher priority would displace real process alarms during precisely the phase that generates the most of them (§8.9 priority distribution).
  • AUTO_RESET, and therefore never blocking. It shall not be a MANUAL_RESET event: a blocking event refuses Start (§8.3(b)), which would make commissioning gates prevent the commissioning they exist to serve.
  • Not clearable, and not shelvable. No operator action closes it. An operator reset closes only MANUAL_RESET events (§8.3(b)), so it does not reach this one; and its rationalization record (§8.9) shall mark it not suppressible, so §8.10 shelving cannot silence it either. It closes when — and only when — its gate goes inactive, which by §7.5.1 means a new download. This is the point: the annunciation cannot be dismissed by the person most motivated to dismiss it.
  • Persistently visible, not only in the alarm list. Because it is the lowest priority, a severity-ordered banner would bury it behind ordinary process alarms. The HMI shall therefore show a separate, permanent, non-dismissible indication for as long as the register is non-empty, naming the active gates (§3.13).

Cross-references: §3.9 (a disabled feature is not published), §7.6/§7.7 (the release and access gates a commissioning gate is ANDed with, never a substitute for), §8.1/§8.3 (severity, reset classes, log), §8.9/§8.10 (rationalization and the no-shelve rule), §10.5.1 (the output-force surface this governs), §13/§14 (change control and the commissioning checklist).

7.6 Manual-function release (OnManRelease)

Section titled “7.6 Manual-function release (OnManRelease)”

Manual mode does not bypass safety. OnManRelease is the manual-release member of the lifecycle-extension family (§3.14), subject to the same framework-first ordering and generated/native assembly contract as the other extensions. Each module that exposes manual functions shall define their release conditions in one place — its OnManRelease reaction — following one fixed pattern: each manual function’s release is the common release ANDed with that function’s specific permissives:

// Release conditions for this module's manual functions:
ReleaseClose := CommonManRelease AND PartPresent AND NOT AreaOccupied;
ReleaseOpen := CommonManRelease AND SafeToOpen;
  • CommonManRelease is derived by the owning Unit (ModeHandler) and is TRUE only when the module is in a mode that permits manual action and station-level conditions allow it. It is a convenience summary, not an opaque source: its common condition records shall be appended to every function’s release report before that function’s own directional/specific records (§7.2.1, §7.8).
  • A manual command (§6.3) shall be inhibited unless its Release<Function> is TRUE; the same PermIntlk descriptions (§7.2–7.4) surface why a manual function is blocked.
  • Being boolean release networks, these conditions may be authored in Ladder or ST (or FBD/CFC) per §5.5 — Ladder is the natural form, the same as interlocks.

7.6.0 Show-why-blocked (release transparency)

Section titled “7.6.0 Show-why-blocked (release transparency)”

An operator who presses a control that does not act shall be shown why. The framework therefore requires every gated action to publish, on demand, the full set of reasons it is currently withheld — not just the first — so the HMI can display a live “not released” panel (§3.13) rather than leave the operator guessing.

  • Rollup, not first-out. Unlike a fault’s single first-out (§6.9), a release rollup lists every unmet condition applicable to that action: mode/state, access (§7.7), blocking manual-reset alarms (§8.3(b)), common release records, and every FALSE function/mode-entry condition (§7.2). For Unit Start this includes the active mode’s immediate command frontier, not unrelated children or future-step waits (§7.8). Each entry carries its ReasonCode (§8.8), human Description, qualified owning SourcePath, and Bypassable flag (§7.4), so two children with the same condition text remain distinguishable.
  • Per action. The rollup is answered per gated action (Start, a specific manual command, changeover, …), because the blocking set differs. ReleaseReport(action) returns the report; Released = TRUE (empty reason list) means the action is released.
  • Live. The panel updates continuously while shown, so an operator watching sees conditions clear one by one (air pressure rises → that line goes green) until the action releases — the standard’s diagnosability objective (O3) applied to pre-action, not just post-fault.
  • No new authority. Showing why never bypasses anything: it is read-only diagnostic data. Bypassing a bypassable permissive remains its own gated action (§7.4/§7.7).

Cross-references: §6.9 (first-out, the fault analogue), §7.2/§7.4 (permissives & bypass), §7.7 (access), §8.3(b) (alarm blocks restart), §8.8 (reason vocabulary), §3.13 (HMI panel).

7.6.1 Manual command surface (discovery + gated entry)

Section titled “7.6.1 Manual command surface (discovery + gated entry)”

A maintenance user needs to command an individual device by hand — extend a cylinder, jog an axis — without hand-written per-device HMI screens. The framework therefore gives every command-bearing module a self-describing command catalog and one gated manual-command entry point, so the HMI renders manual controls generically (§3.13).

  • Discovery. Each Control/Equipment Module shall publish a command catalog: for every command it accepts, a {Value : DINT, Label : STRING} pair (the same values its ExecuteCommand accepts, §3.2; the same labels its timing rows already use, §8.11.4(a)). The catalog is published data (§3.10(a′)), so the HMI discovers the buttons — no per-type HMI code (O1). A module with no manual commands publishes an empty catalog and shows no manual panel.
  • Single manual path — MANUAL mode only. A manual command issued from the HMI shall be accepted only when all hold: (1) the owning Unit is in MANUAL mode (§3.4) — the command routes through the module, so the module still runs and its interlocks still defend it (§7.2); (2) the function’s §7.6 Release<Function> is TRUE; (3) the user holds the MANUAL access level (§7.7). There is deliberately no mode-bypass override: to move a device by hand, put its Unit in MANUAL first, which places the whole Unit in a known-safe state — a device must never be commanded while the rest of its Unit believes it is running automatically.
  • Routing, not bypassing. The manual command is delivered to the module’s existing command surface (§3.2) — the same entry the automatic sequence uses — never to the I/O directly. This is the opposite of a fieldbus channel force (§10.5.1): a manual command is defended by the module (interlocks, first-out, timing all apply); a channel force goes around it. The two shall be visually and functionally distinct in the HMI so the two risk levels are never confused.
  • Audit. Every accepted manual command, and every rejected one, shall be logged as a §8.3 event (manual actions are always traceable).

Some manual actions only act while the operator keeps asking — jogging an axis is the archetype. These do not fit the Execute/Done handshake, and PLCopen does not force them to: MC_Jog takes level inputs for exactly this reason. A module that offers one shall publish it in the same catalog with Style = HELD and accept it through a level entry point rather than ExecuteCommand:

// Called EVERY SCAN while the control is held; silence is a stop.
METHOD RequestHeldCommand : BOOL
VAR_INPUT
Value : DINT; // the catalog Value being held
Enable : ST_ManualEnableStatus; // §9 manual-enable fact, for actions that need one
END_VAR
  • Silence stops the action. The module shall stop a held action when the calls stop, within a configured deadline. This is not a convenience: a held request that is delivered over a network can stop arriving because the operator let go, because the client closed, or because the transport died with the control still pressed — and only the first is a deliberate stop. Treating all three identically is what makes the surface safe, and it is the same rule as §11/§14’s “a lost transport queues nothing.”
  • The module cannot distinguish them, and shall not pretend to. It reports that the request stopped arriving. A client that knows it is still sending can surface the difference; the PLC cannot, and inventing the distinction would be a diagnostic that lies.
  • Style is additive. ST_CommandInfo.Style defaults to ONESHOT, so every catalog entry that predates this clause keeps its existing meaning and no consumer breaks (§1.5).
  • A held action remains subject to everything in §7.6.1 — MANUAL mode, its §7.6 release, the MANUAL access level, and the module’s own interlocks. Style changes how it is operated, never what it is allowed.

Held is not a dead-man. A held action delivered from an HMI is a non-safety convenience, as §3.4.2/§9 already require of HOLD_TO_RUN. Where a held action moves an axis with the guards open, the permission comes from a safety-rated enabling device published through §9 (see ST_ManualEnableStatus), never from the fact that a button is being held.

Cross-references: §3.2 (command surface), §3.4 (mode), §3.13 (generic HMI), §7.6 (release), §7.7 (MANUAL level), §8.3 (audit), §8.11.4 (command labels), §9 (manual enable), §10.5.1 (contrast with channel force).

Access level is the who dimension of release, ANDed with the machine dimensions of §7.2–§7.6: an action executes only when its permissives/interlocks allow it and the active user level suffices.

The HMI login dialog with a user field containing op1 and a PIN field.

Logging in raises the access level for gated actions. The demo’s users and PINs are listed on fraktalautomation.com.Browser HMI simulation at revision a1163c7 · try it

(a) Levels & actions. Ordinal levels E_AccessLevel (NONE=0 < OPERATOR < TECHNICIAN < ENGINEER < ADMIN) and an enumerated set of gated actions E_GatedAction: DATA_READ, DATA_WRITE (ParCfg/StationCfg edits, §3.8a), MANUAL (manual movements), CHANGEOVER (SetModel, §3.1b), MODE_CHANGE (§3.4), START_STOP, ALARM_HISTORY (read, §8.3), ALARM_RESET (§8.3(b)), ACCESS_POLICY (editing this policy itself), append-only ALARM_SHELVE (shelve/unshelve annunciation, §8.10), POWER_CONTROL (Control On/Off and power-group requests, §9.8), and CONFIG_SET (saving, loading or importing a whole parameter set, §3.8b). Ordinals are transport contract; new actions shall be appended, never inserted.

(b) Per-station policy, PLC-authoritative and editable. Each root Unit carries an access policy — a required level per gated action — held as persistent station config (§3.8a: deployment data, editable, never in a recipe). Any threshold set to NONE means that action needs no login; a station may therefore be fully open (every threshold NONE) or locked down per action — the deployment’s deliberate choice. Shipped default is fully open (NONE everywhere): access control is never a silent lock-in (O1/O6), and the §14 commissioning checklist shall include provisioning an access provider and reviewing the policy. A generic HMI may edit the root’s published policy, but each edit is routed through the root request mailbox and rechecked against ACCESS_POLICY; the policy editor is not a second authority. To prevent retained self-lockout, raising the ACCESS_POLICY threshold above the active session level shall be rejected. The policy also holds the read and write level of every declared data class (§3.8d), edited through the same path; the built-in classes use the DATA_READ/DATA_WRITE thresholds. Per-function granularity for manual movements: MANUAL is the default threshold, and an individual manual function may declare its own higher required level in its OnManRelease definition (§7.6) — so “jog axis” and “open guard bypass” can differ.

(c) Sessions & enforcement. A per-root access manager holds the active level/user, authenticates through an injected I_AccessProvider — with a shipped local default (FB_LocalAccessProvider, persistent user table) mirroring §3.8’s provider pattern — and auto-logs-out after a configurable idle timeout (T#0S = never). Idle time is measured since successful login or the last accepted authenticated operator mutation; background reads, manifest fetches, and release-report polling shall not keep an abandoned session alive. Login/logout is data-driven (request members in the exposed namespace, §3.10(a′)); the secret member is cleared immediately after each attempt. A provider shall not retain a secret it can read back: the local default keeps a per-registration salt and an iterated SHA-256 of salt and PIN, never the PIN, and its table is excluded from every published or symbol surface (ADS, OPC UA). A composition root that takes PINs from retained commissioning data shall clear each one once it is registered. A transport/mailbox acknowledgement only proves that the attempt was consumed; clients shall determine authentication success from the resulting published CurrentUser, CurrentLevel, and LoginFailed state. A failed attempt shall receive explicit localized HMI feedback without revealing whether the user or secret was incorrect. Enforcement is in the PLC at every gated entry point (SetMode, SetModel, Start/Stop, OperatorReset, manual commands, decisions, power control, alarm shelving, force, and ParCfg/StationCfg writes): the HMI greys controls from the published level and the PLC re-checks — the client is never trusted (§14 defense in depth). Denied attempts, logins, logouts, and accepted privileged remote mutations shall be logged as MESSAGE events (§8.3), including the action identity and active user but never a secret. Thresholds are configured on the root the HMI addresses; framework-internal calls (the §3.7 cascade, step chains) are trusted — they only execute downstream of an already-authorized entry.

(d) Relation to transport security. Transport authentication/encryption remain the selected binding endpoint’s job (§11.2); §7.7 is the application authorization layer above it. Both are required for command-capable deployments: transport identity does not grant a PLC action, and application access does not replace a secured conduit (§14).

Cross-references: §7.6 (manual release ANDs access), §3.13 (HMI greys from published level), §3.8a (policy = station config), §8.3 (audit events), §8.9 (shelving roles now = these levels), §14 (defense in depth, commissioning checklist).

7.8 Release reporting (“why is this blocked?”)

Section titled “7.8 Release reporting (“why is this blocked?”)”

An operator who presses a control that does not act shall be able to see why — never left guessing. The framework therefore requires every gated action to publish a release report: the complete list of currently-unmet preconditions, each with a human description and its §8.8 ReasonCode, so the HMI shows a full rollup rather than a single first-out.

A red Start blocked banner listing four reasons: a manual-reset alarm on StationA, cylinder B not at position, the guard door control domain not ready, and control power off. An inset magnifies the start button.

Why will it not start? The release report, one reason per blocking condition.
  1. Each reason names the module and the condition.
  2. The start button is not released; tapping it shows the report.
Browser HMI simulation at revision a1163c7 · try it
  • Structure. ST_ReleaseReport — Released : BOOL plus Reasons : ARRAY OF ST_ReleaseReason (Description, ReasonCode, SourcePath, Kind, Bypassable). SourcePath is the canonical qualified identity of the module that owns the condition; it is never a transport alias path. The report is complete: it lists every failing precondition at once (mode wrong, access insufficient, a blocking alarm active, and each failed interlock condition), not just the top one — because a fault-list that hides the second cause makes an operator fix one thing and press again fruitlessly.
  • Layered rollup sources. A Unit Start report aggregates framework-common state (ready/run state, mode transition, access, blocking alarms, and control-domain readiness), one single-sourced common Start set, and any active mode-specific immediate entry/frontier conditions owned under §7.2.1. Modes may share the common set; they do not copy it. Conditions awaited only by a later step—part arrival, an operator confirmation, or downstream availability—belong in that step’s pending record (§6.5/§6.9) and shall not over-gate Start merely because the sequence will need them later. If Start immediately commands a child, that child’s applicable release records are part of the frontier and are included. A manual command report aggregates the Unit’s common manual conditions plus mode/access and only the selected target+direction’s function-specific conditions (§7.6.1).
  • One authoritative predicate; query has no side effects. ReleaseReport… is a pure query, and its Released result is the machine gate consumed by the corresponding action after any required audited access check. The action shall not separately re-code the condition expression. Therefore Released = TRUE iff the action is accepted in the same stable state, and every FALSE source record is the report entry the operator sees. Pressing a blocked control commands nothing; it only surfaces the report.
  • Safety boundary. A standard-PLC release report may include read-only safety/control-domain status to explain a block, but it never grants, bypasses, mutes, bridges, or forces a certified safety condition (§9.8).
  • HMI (§3.13). A persistent panel shows the live release report of the selected Unit/action while it is blocked, each reason with its description and (where bypassable, §7.4) its bypass state; it clears when the action releases. Pressing a greyed/blocked control opens/refreshes this panel. Interlock reasons use the same PermIntlk descriptions surfaced everywhere else (§7.2), so the operator sees consistent wording.

Cross-references: §3.4/§3.4.1 (mode preconditions), §7.2/§7.4 (interlocks & bypass), §7.6/§7.6.1 (manual release & commands), §7.7 (access), §8.3 (blocking alarms), §8.8 (reason codes), §3.13 (HMI panel).


Tier Source Alarm level
Station Fault top FB_Unit / Station Monitor High
Unit / EM FB_Unit, FB_EquipmentModule Med
CM / Sequence / Alarm Instance FB_ControlModule, sequencer Low
Safety safety zone faults Low (rolled to station)
System PLC-level faults Low (rolled to station)

Alarm trigger conditions are boolean networks like interlocks, so they may reuse the FB_PermIntlk condition pattern (§7.2) and be authored in Ladder, ST, or FBD/CFC per §5.5. Each trigger carries a Description + ReasonCode, so it feeds the queue (§8.3) and the message catalog (§8.8) the same way regardless of language.

Because every archetype implements I_Module.GetFaultSummary, fault rollup is a recursive tree walk: each module sums its own faults with its children’s first-out summary and passes it upward. A Unit filters two fault classes — sequencer faults and asynchronous alarms — to decide OEE-impacting downtime, exactly as in the parent-child alarm flow, but now generated automatically by the composite structure rather than wired per level.

8.3 Alarm & event history (queue, duration, reset classes)

Section titled “8.3 Alarm & event history (queue, duration, reset classes)”

Alarm/event come and gone transitions shall enter a per-Unit event log with a defined record and lifecycle, browsable in place and streamable to a historian.

(a) The event record (ST_AlarmEvent). ReasonCode + Description + SourcePath (§8.8 — the same vocabulary as every diagnostic), one authoritative Severity (LOW | MED | HIGH), orthogonal Category, ComeAt/GoneAt plus their ComeTimeSynchronized/GoneTimeSynchronized quality (and equivalent reset/shelf quality, §2.7), Duration (monotonic come→gone difference, per §8.11.4(e)), ResetClass, and State. There is deliberately no second message/warning/error axis: annunciation, sorting, and tree tinting all use Severity.

(b) Reset classes (E_ResetClass). Every event is declared either AUTO_RESET — it closes by itself when its condition re-establishes (typical for low/medium transient events) — or MANUAL_RESET — after the condition clears it remains blocking until a deliberate operator reset (typical for high-severity faults). Lifecycle: ACTIVE (come) → on condition-gone: AUTO_RESET closes immediately with Duration; MANUAL_RESET enters WAIT_RESET (still blocking) → operator reset closes it (ResetAt stamped). A MANUAL_RESET event shall never self-close (§9.3), and the Unit’s Start shall be refused while any such event is ACTIVE/WAIT_RESET.

An operator reset shall close a MANUAL_RESET event from either ACTIVE or WAIT_RESET — it is a deliberate external action, not a self-close, so the WAIT_RESET stage is where an event waits for the operator, never a precondition for being allowed to reset it. Requiring WAIT_RESET would make the reset a guaranteed no-op for the one class of event it exists to clear: whenever the blocking condition can only be re-established by running the machine — a permissive that must hold during motion, such as a two-hand control held through a press stroke — ACTIVE cannot be left, Start is refused because the event blocks it, and the operator has no action left. An event closed while its cause is still live is re-raised by its owner on the next scan through the automatic capture of (c), so this clears the latch and never the condition: the interlocks of §7.2 are untouched, no output is restored, and the release report of §7.8 still refuses Start and still names the live condition. A reset shall therefore also release the latched control state that the event was reporting — the Unit’s own run command and any child command its suspended sequence had issued (§6.1) — because closing the event while those remain asserted leaves the equipment unrecoverable for the same reason. Recovery modes (HOME and equivalents) shall be reachable after one such reset, under the §7.7 authority for ALARM_RESET.

(c) Automatic capture, manual raising. The Unit base shall capture module faults automatically — entering ERROR raises a MANUAL_RESET event carrying the rolled-up first-out severity and diagnostic (§8.2, §6.9); leaving ERROR marks it gone. Application code raises other events explicitly with a chosen severity/reset class (one call, §8.7 EVENT_ constants). Nothing is double-authored: the event is the diagnostic plus lifecycle.

(d) Discovery & retention. Each Unit publishes its active list and a fixed-size closed-event ring (newest-first, Truncated on overflow) through the Self-Description Service (§3.10) — the HMI discovers history with zero station code (§3.13), including each event’s duration. In-PLC retention is bounded by design; full history is the historian’s job: a logical I_EventSink capability is invoked at come and at close so a database/historian adapter (OPC UA A&C, SQL, MES) subscribes without touching the log. Sink realizations are deployment choices. The record path shall be the module’s canonical path (§4.8), so HMI, historian, and MES share one address.

(e) ISA-18.2 mapping. ACTIVE/WAIT_RESET/closed correspond to Unack-Alarm/RTN-states of ISA-18.2 §8.9; the reset here doubles as acknowledge for the blocking class, keeping one operator action instead of two (rationalization per §8.10 decides which reasons are alarms vs logged-only events).

To suppress nuisance alarms, independently controlled equipment shall fault only on a valid downtime event, and that event shall carry one descriptive High alarm raised at the station’s top level (reported by the Station Monitor). Lower tiers carry Med/Low alarms that roll up; only the top emits the single High that drives downtime reporting.

The Station Monitor shall capture faults from any module in its OEE reporting area on a first-out basis to attribute downtime to true root cause, and shall integrate Safety and System alarms. OEE/performance metrics derive from the same rollup.

OEE is a derivation from contracts the standard already has — no new instrumentation in the modules, only accounting in the Unit:

The OEE card: 60.9% overall, availability 71.0%, performance 88.0%, quality 97.5%, with a trend line.

OEE and its three factors, with the trend samples, on a station’s Statistics tab.Browser HMI simulation at revision a1163c7 · try it
  • Time classification. Each scan, the Unit attributes elapsed time to exactly one bucket: run (BUSY), down (ERROR, or a blocking alarm active §8.3), or idle (everything else). Buckets are monotonic accumulators since the last reset.
  • The three factors. Availability = run ⁄ (run + down) — idle time is tracked and published but excluded from A (no demand ≠ downtime; a deployment that schedules production differently re-derives A from the published buckets). Performance = (ideal cycle time × total count) ⁄ run time, computed only when an ideal cycle time is configured (§3.8 — per-model, since a different product may cycle differently). Quality = GoodCount ⁄ (GoodCount + NokCount) (§8.11). OEE = A × P × Q, and each factor carries a validity flag: an unconfigured or division-by-zero factor is invalid and omitted from the product — never assumed 100 % (O7: the UI must not flatter).
  • Trend samples. The Unit pushes an OEE sample (A, P, Q, OEE + validity) into a bounded ring at a fixed period, giving the HMI a recent-history series with zero historian dependency. Long-horizon trending is the historian’s job (§8.3 I_EventSink / external), not the PLC’s.
  • Reset. ResetOee clears the accumulators and ring — a gated action (§7.7 DATA_WRITE), audited (§8.3). Typical use: shift start; a deployment automates it from its scheduler.
  • HMI (§3.13). Units render an OEE facet: the three factors + OEE as percentages with exception-based colouring (muted when at/above target, colour only below — ISA-101 style), and a sparkline from the sample ring so the operator sees direction, not just a snapshot. Invalid factors render as “—”, never 100 %.

Cross-references: §3.8 (ideal cycle per model), §6.1 (BUSY), §8.3 (blocking, audit, historian), §8.11 (counters, timing), §7.7 (reset gating), §3.13 (rendering).

Part of the optional Line profile (§1.5, §3.8e).

§8.5.1 says counters and OEE are reset “typically at shift start” by a deployment’s scheduler, and §8.11.2 that counts reset on a deliberate, logged action. Left there, every deployment writes its own scheduler, the reset lands whenever that scheduler happens to run, and the figures for the shift that just ended are gone the moment it does. A shift is a fact about the line, and closing one is framework work.

(a) The calendar is line config. A line (§3.8e) carries a bounded shift calendar of at most MAX_SHIFTS entries, each an ordinary LINE_CFG write capability: its start as minutes after local midnight, or -1 when the shift is not used, plus one offset from UTC for the whole line (the synchronized clock of §2.7 is UTC; daylight saving is set, never guessed). A shift is named by its index, which the front end localizes. A shift runs from its start to the start of the next used shift, wrapping at midnight, so a calendar is complete by construction and has no gaps to reason about. Every station on the line reads the same calendar, from the owner or its mirror; no station holds its own.

Version 2 weekly calendar. A deployment that needs selected weekdays or unscheduled intervals shall use a versioned calendar (ST_ShiftCalendarV2, SchemaVersion := 2), without changing the released daily calendar’s layout or meaning. It retains the line UTC offset and at most MAX_SHIFTS rows. Each row has StartMin (-1 unused, otherwise 0..1439), DurationMin (1..1440) and ActiveDays (seven bits, Monday bit 0 through Sunday bit 6; 0 disables the row). Duration is elapsed minutes; an overnight shift belongs to its starting day. The complete calendar shall be validated before any write or whole-set load: offset -840..840, valid ranges and no intersecting half-open intervals over the weekly wrap. Adjacent boundaries are permitted. Selecting Saturday and Sunday, 08:00 and 720 minutes produces two 12-hour shifts, with off time between them.

Migration from the daily calendar shall derive each used row’s duration from its next used start, including midnight wrap and a sole 1440-minute row, and select all seven days. Unused rows stay unused. An invalid source shall be rejected; migration shall not guess durations or partially apply a calendar. Bindings may encode the bounded fields in their native scalar widths, with their physical schema/version declared separately.

In version 2, CurrentShift := 0 identifies an unscheduled interval. It uses the same counters, quality flags and closed-record accounting as scheduled shifts; production during off time shall not be discarded or attributed to the preceding shift. Its next boundary is the next enabled shift start. A completely empty calendar has no finite boundary. An edit in that case applies on the next scan; if it starts an active shift, first close the accrued unscheduled interval. Otherwise keep that interval’s start and accumulators, and only update its next boundary. Edits to a calendar with a finite boundary take effect at that boundary, never midway through its current interval.

Version 3 production targets. A deployment that needs per-shift production goals shall use a new calendar/record schema, without changing either released calendar’s layout. It retains the version 2 weekly interval rules and adds ProductionTarget to each row: a non-negative integer count of good parts per root Unit, with 0 meaning unconfigured. The binding declares its bounded row capacity; a five-row calendar can represent three weekday shifts and two weekend shifts with independently selected days and durations. Capacity growth shall preserve existing row identities; newly appended rows start unused and their targets unconfigured during migration.

Targets are LINE_CFG capabilities with the same effective access checks, whole-set validation, revision and boundary application as the calendar. Each root shall latch its current interval’s target when that interval starts, publish it as ShiftProductionTarget, and copy it into the closed shift record as ProductionTarget before resetting counters. Unscheduled intervals have target 0. Later edits shall not rewrite the target of an open or closed interval. The HMI may derive attainment from the root’s existing GoodCount and the latched target, allowing values above 100%; it shall not include NOK/rework in that numerator or treat an unconfigured target as a denominator. Targets are reporting goals and do not issue commands or stop production. A manual counter reset remains visible through the existing partial-record quality flag.

(b) Every root Unit closes its own shift. At each boundary, evaluated on the synchronized clock (§2.7), every root Unit that references the line closes the ending shift as one operation in one scan: it writes a shift record into a bounded ring ShiftHistory[1..MAX_SHIFT_HISTORY] (newest-first, Truncated on overflow) and then resets its per-shift accumulators. The record carries the shift’s index and name, its start and end timestamps with their time-quality flags, GoodCount, NokCount, ReworkCount, the §8.5.1 run/down/idle times, and the three OEE factors with their validity flags — the figures exactly as they stood at the boundary, so nothing between the last read and the reset is lost. The closing is audited (§8.3) and offered to I_EventSink, so a historian receives every shift without polling for it.

(c) Counters are split, not replaced. The per-shift counts and OEE accumulators are those that §8.5.1 and §8.11.2 already publish; a shift boundary is the deliberate, logged reset those sections require, taken on time instead of whenever a scheduler runs. ResetOee and a changeover reset remain available and behave as before; a manual reset mid-shift is recorded as such in the next shift record, so a shift total is never silently partial.

(d) Clock quality is carried, never hidden. A boundary crossed while the clock is not synchronized still closes the shift — stopping the accounting would lose more than a late boundary does — but the record says so (TimeSynchronized := FALSE), and the HMI marks it. A calendar change takes effect at the next boundary; it never rewrites a closed record. After a forward clock jump crossing several boundaries, close the one observed interval once with unverified quality; do not fabricate records or production for missed intervals. A backward jump marks the open interval’s quality unverified and shall not create a negative-duration record or rewrite history.

(e) HMI (§3.13). A Unit renders its current shift, the elapsed and remaining time, and the ShiftHistory ring as a table with the same exception-based colouring as the OEE facet. A generic HMI needs no station code: the calendar is edited as line config (§3.8e), and the history is a fixed framework type.

Cross-references: §2.7 (synchronized clock), §3.8e (line config), §8.3 (audit, I_EventSink), §8.5.1 (OEE), §8.11.2 (counts), §3.13 (rendering).

  • Safety alarms: faults of safety devices in the zone(s) affecting the station (see Safety section, tracked separately). Mapped through the standard Safety-to-Standard alias signals (AllEstopsOk, AllSafetyOk, …).
  • System alarms: PLC-level conditions impacting execution (fieldbus, IPC diagnostics, task health).

Messages shall be defined as EVENT_-prefixed constants and raised with an explicit class (e.g. WARNING, SOFTERROR, error). Class selection shall reflect operational impact, and each event shall carry a description suitable for the HMI and the alarm database.

Legacy handler frameworks return a bare numeric error code (e.g. -649231) that the HMI maps to a message. Numeric codes are retained as a localization/transport key, but a bare magic number on the return value is opaque in source, conflates what failed with where, and depends on an external catalog that drifts. This standard keeps the benefits and removes the weaknesses, using PLCopen vocabulary for familiarity:

  • _retVal is retired. Control flow uses the PLCopen Done / Error / Aborted status (§6.1, §6.5); these carry no message codes.
  • The number is the PLCopen ErrorID. On Error, a module raises ErrorID : DWORD — the value reaching the HMI — sourced from a namespaced enum E_Reason (e.g. E_Reason.PART_PRESENT_MISSING) that reads meaningfully in source. ErrorID := TO_DWORD(ReasonCode); never a hand-typed magic number. Codes are positive (PLCopen ErrorID is unsigned); a boundary mapping can negate for a legacy historian if ever required.
  • The full reason is a structured record. The Diagnostic/event (§6.9, §8.2) is ST_Diagnostic:
TYPE ST_Diagnostic :
STRUCT
ReasonCode : E_Reason; // named reason; ErrorID = TO_DWORD(ReasonCode)
SourcePath : STRING(255); // canonical path of the module/condition (§4.8)
Description : STRING(255); // localization key (from PermIntlk/module, §7)
IoTag : STRING(80); // exact, untranslated electrical/schematic tag; '' if N/A
IoAddress : STRING(80); // terminal/channel locator; '' if N/A
Severity : E_Severity; // LOW | MED | HIGH (§8.1)
Category : E_Category; // PROCESS | SAFETY | SYSTEM
Since : DT; // first-out timestamp
TimeSynchronized : BOOL; // quality of Since (§2.7); FALSE = display as untrusted
END_STRUCT
END_TYPE

A generic code plus SourcePath renders instance-specific — “Clamp3: part present missing” — so no unique global number per device is needed. When a fault implicates a particular physical channel, IoTag shall carry the exact tag from the project’s approved I/O/electrical list and IoAddress shall carry its physical locator. These are structured identity, not display prose: clients shall not translate or rewrite them. The localized Description explains the failure while the tag lets maintenance find the device on the schematic, terminal, and machine label. Diagnostics not attributable to one channel leave both fields empty; a multi-channel plausibility fault may carry a stable delimiter-separated tag/address list while the fieldbus projection highlights every implicated channel.

  • Code bands (partitioned so codes never collide):
Band Range Owner
System 1 – 999 PLC, task, fieldbus, IPC
Safety 1000 – 1999 safety devices / zones
Framework (common) 2000 – 9999 shared reasons: timeout, awaiting child, permissive not met, interlock dropped, recipe invalid…
Per module-type 10000 +, one contiguous block per type (100-wide for CM types within 10000–10999; EM types from 11000 in 1000-wide blocks) type-specific reasons

0 = NONE (no reason). Module-type codes are relative to the type; SourcePath disambiguates instances.

  • Band extensibility (implementation rule). IEC 61131-3 enums cannot be extended across libraries, so the framework’s E_Reason declares the framework bands only and shall not be compile-strict: a module type declares its band codes (10000+) as named constants in its own library and assigns them into ST_Diagnostic.ReasonCode/_M_Fault directly. The registry below — not the enum — is the collision authority, and the generated catalog is built from the union of the framework enum and the registered type bands. This keeps one number space with per-type bands (O3, O4) implementable on any platform’s enum semantics (O8) without a central enum every type edit would touch (O1).

  • Reserved sub-ranges & registry. The E_Reason enum is the single source of truth; to keep allocations visible across sections, the bands are sub-divided and the codes introduced by this standard are registered here. A new reason shall be added to the appropriate sub-range and recorded below so codes never collide:

Band / sub-range Reasons
System 10–21 controller & clock health (§8.12, §2.7): TASK_OVERRUN=10, TASK_JITTER_HIGH=11, CPU_LOAD_HIGH=12, MEMORY_LOW=13, IPC_TEMP_HIGH=14, FIELDBUS_MASTER_FAULT=15, DC_SYNC_LOST=16, TIME_SYNC_LOST=17, UTILITY_DEVIATION=18 (§8.14), IPC_FAN_FAULT=19, STORAGE_HEALTH_LOW=20, CONTROLLER_METRICS_UNAVAILABLE=21
Framework 2000–2009 common flow reasons: TIMEOUT=2001, PERMISSIVE_NOT_MET=2002, INTERLOCK_DROPPED=2003, RECIPE_INVALID=2004, STEP_STALLED=2005, RETRY_EXHAUSTED=2006, CYCLE_TIME_DEGRADED=2007 (maintenance event, §8.11.4/§8.12), UNSUPPORTED_COMMAND=2008 (input outside a type’s declared command set, §5.6)
Framework 2010–2019 external device / link supervision (§3.15): LINK_TIMEOUT=2010, DEVICE_NOT_READY=2011, DEVICE_PROTOCOL_ERROR=2012
Framework 2020–2029 traceability / part context (§3.16): CARRIER_READ_FAILED=2020, CARRIER_WRITE_FAILED=2021, PART_ID_MISMATCH=2022, RESULT_RECORD_REJECTED=2023
Framework 2030–2039 engineering/commissioning build gates (§7.5): COMMISSIONING_GATE_ACTIVE=2030 — one LOW/SYSTEM, non-clearable, non-shelvable event per active gate
Framework 2040–2049 configuration persistence & parameter sets (§3.8b): CONFIG_RESTORE_LOST=2040 (a retained image was rejected — an unrecognized schema version — so the owning module runs on declared defaults; version 0, never written, raises nothing), CONFIG_PERSIST_FAILED=2041 (an accepted write did not reach non-volatile storage inside the declared window), CONFIG_SET_REJECTED=2042 (a set load was refused; staged and all-or-nothing, so nothing changed, and the refusal names the offending (Scope, WriteKey)), EVENT_CONFIG_SET_APPLIED=2043 (§8.3 audit event, not an alarm)
Framework 2900–2909 framework self-test reasons, never raised in production (§5.7 base suite): TEST_FAULT=2901
Per module-type 10000+ type-specific, one contiguous block per type — 100-wide CM sub-blocks within 10000–10999, EM blocks from 11000 (registered: separator CM 10001–10005, cylinder CM 10101–10103, basic cylinder CM 10110–10116 (same 100-block; production variant of the cylinder type), axis CM 10201–10206, robot CM 10301–10315, TCP/ASCII device CM 10401–10406 (§3.15.1a base; device profiles extend within 10401–10499), power-group CM 10501–10502 (§9.8), air-pressure monitor CM 10601, clamp EM 11001, per Annexes A–B, G, I)

TIME_SYNC_LOST is a System-band code (17) because it is annunciated as a System-category alarm (§2.7, §8.6), even though the clock is configured in §2.

  • One catalog, generated from the numeric authorities. The code→message catalog — with {source} / {value} placeholders for localization — shall be generated from the Core E_Reason definition plus every registered type-band parameter list, so portable framework codes and additive library bands compose without duplicating their numbers. Rationalization joins by the named symbol (§8.9), not by restating the number. The HMI localizes by ErrorID/ReasonCode; absent an entry it falls back to Description.

In short: keep the number as the PLCopen ErrorID for transport and localization, source it from a named enum, carry the full reason in ST_Diagnostic, and always attach the source path.

§8.1–8.8 give the alarm mechanics; this section adds the governance that ANSI/ISA-18.2 (and its international form IEC 62682) require, so the cell’s alarms are actionable rather than a flood. Every alarm the standard can raise — each E_Reason / EVENT_ constant — shall be rationalized, not merely defined.

  • Alarm philosophy. A project shall adopt a short alarm-philosophy document that fixes the priority scheme, the operator-response expectation per priority, and the rules for suppression/shelving below. The E_Severity tiers (§8.1) map to that priority scheme.
  • Rationalization record. Each registered reason shall carry, in one machine-readable symbol-keyed registry joined to the numeric catalog (§8.8): a priority (derived from consequence × required response time, not assigned ad hoc), a one-line operator action (“what do I do about this?”), an alarm class (PROCESS / SAFETY / SYSTEM, from ST_Diagnostic.Category), and a flag for whether it is suppressible/shelvable. Generated PLC and HMI projections shall reject missing, unknown, duplicate, or conflicting entries. An entry without an operator action is an event, not an alarm, and shall be logged (§8.3) rather than annunciated — this is the primary lever against alarm overload. Project/application bands may extend the catalog through a complete validated record, but shall not override generated standard metadata.
  • Priority distribution. The rationalized set should approximate the ISA-18.2 distribution guidance (the large majority Low, few High) — a station whose alarms are mostly High has not been rationalized.
  • One reason, one priority, everywhere. Because priority lives in the generated catalog keyed by ReasonCode, the same reason carries the same priority on HMI, historian, and MES — no per-screen reclassification.

Cross-references: §8.1 (severity), §8.3 (queue/log), §8.8 (catalog from enum), §13 (changes to the alarm set follow MOC).

8.10 Alarm governance and optional performance profile

Section titled “8.10 Alarm governance and optional performance profile”

Rationalization is set once. Shelving and management of change below are part of the base contract. Long-window nuisance/flood analytics are an optional Alarm-performance profile because their correct scope is normally one cell, line, or site historian—not one duplicate rolling window beneath every root Unit (O1/O4). A deployment shall state whether this profile is claimed and name its single owning aggregator.

  • Flood & nuisance handling (profile). When the Alarm-performance profile is claimed, the owning Station Monitor or external historian shall debounce chattering annunciation according to a rationalized minimum-on/fleeting filter per reason and shall detect alarm floods (rate over a configured threshold in a rolling window). It shall retain every underlying event and shall never suppress control, blocking, first-out, or history semantics; it may replace repeated audible/banner annunciation with one conspicuous flood indication plus drill-through to the members.
  • Shelving / suppression. Only reasons flagged suppressible (§8.9) may be shelved, and only by an authorized role (§7.7 level, transported per §11.2). A shelf shall auto-expire (time-bounded, with auto-unshelve) and shall itself be logged. Shelving suppresses annunciation only — never control: a shelved blocking alarm (§8.3(b)) still blocks Start, interlocks (§7.2) are untouched, and release reports (§7.8) still list the condition; the HMI merely stops shouting about it (banner/list de-emphasis). Safety-category alarms (§8.6) are never shelvable regardless of flags. An alarm with no rationalization record (§8.9) is not shelvable — rationalize first, then shelve. Design-suppression (e.g. downstream alarms suppressed while a Unit is intentionally stopped) shall be defined in the philosophy, not improvised.
  • Performance KPIs (profile). When the profile is claimed, its owner shall expose alarm-rate (per 10 min), standing-alarm count, and stale-alarm count (active beyond a configured long threshold) as Self-Description Service values, so alarm health is measurable against ISA-18.2 targets. It consumes the complete §8.3 event stream through the bounded ring and/or I_EventSink; application modules shall not reimplement these aggregates.
  • Management of change. Adding, removing, or re-prioritizing an alarm shall follow the change process of §13; because alarms are generated from the E_Reason enum and catalog, a diff of those artifacts is the alarm MOC record.

Cross-references: §8.4 (single-High), §8.5 (Station Monitor/OEE), §11.2 (roles for shelving), §13 (MOC).

8.11 Performance capture (cycle time, counts, machine states)

Section titled “8.11 Performance capture (cycle time, counts, machine states)”

§8.5 derives OEE from the fault rollup, but OEE also needs a measured cycle time, a counted reject source, and a standardized machine state — none of which §8.5 specifies. This section defines that capture so OEE is computed from real signals, not inferred. The capture is written once into the Unit and Station Monitor; it is not re-implemented per station.

The Unit mode chain (§6.2) already has defined boundaries; performance capture hangs off them with no new sequencing:

  • A cycle-start marker fires on the first productive step of the AUTO chain (N100), a cycle-complete marker on the finish/loop step (N999). The Station Monitor derives CycleTime, LastCycleTime, and a rolling MinCycleTime from these markers.
  • The Unit shall expose blocked (downstream cannot accept) and starved (upstream has not delivered) as distinct signals, so lost time is attributed to the line, not charged to the station as a fault.
  • The Unit shall maintain GoodCount, NokCount, and ReworkCount, incremented once at the part outcome. With traceability enabled this occurs at EVENT_PART_PROCESSED (§3.16) from the part Verdict; when the optional carrier is absent, the owning sequence uses the framework outcome helper instead of fabricating a part record.
  • A NOK shall be attributed by its non-NONE first-out ReasonCode (§8.8) — the same reason vocabulary as a fault — so scrap is analysable by cause without a separate reject-code scheme. The owning NOK helper shall increment the counter and emit the fixed §11.6 NOK host event as one operation; PartUid is empty when traceability is not configured. Counters reset on a deliberate, logged action (shift/changeover), never silently.

The Station Monitor (§8.5) shall classify the station, every scan, into one fixed state set, from which Availability / Performance / Quality follow directly:

State Condition OEE bucket
PRODUCING AUTO chain cycling, not blocked/starved uptime
IDLE ready, no work present —
BLOCKED / STARVED §8.11.1 signals external loss
DOWN a fault holds the Unit (§8.2) downtime (first-out cause)
CHANGEOVER CHANGEOVER mode active (§3.4) planned
STOPPED operator/parent Stop planned

This state set maps one-to-one onto the PackML state/admin model (§11.7) and onto the host events (§11.6), so the same classification feeds local OEE, the line controller, and MES without re-derivation.

8.11.4 Step & command timing capture (the cycle-time profile)

Section titled “8.11.4 Step & command timing capture (the cycle-time profile)”

§8.11.1 measures the cycle total; diagnosing a slow or drifting cycle needs the breakdown — which step, which module, which command. The standard therefore captures timing at the two places every cycle already passes through, so the profile costs the application author nothing (O1) and explains time the way the stall walk explains stalls (O3):

A cycle-time trend of 20 cycles as stacked bars split into work, waiting for upstream (starved) and waiting for downstream (blocked), with the best cycle marked.

Captured cycle timing: each bar splits a cycle into work, starved and blocked time.Browser HMI simulation at revision a1163c7 · try it

(a) Command timing — in the module lifecycle (shall). The authoritative module lifecycle (§2.2) shall measure every command’s execution time (BUSY entry → DONE/ERROR/ABORTED) and maintain, per command id, a timing row {Id, Label, Count, Last, Minimum, Maximum, Avg} published in the module’s standard Timing structure. This is written once in the framework/generator; a type identifies its commands with one binding-native declaration and adds no other timing code.

(b) Step timing — from the step record (shall). The step-chain base shall feed a cycle profiler from the step record the chain already maintains for diagnostics (§6.5/§6.9): each _M_SetStep closes the previous step’s duration, and the finish step (the §8.11.1 cycle-complete marker) closes the cycle. The profiler publishes the last completed cycle and per-step aggregates (Count/Last/Minimum/Maximum/Avg keyed by StepNo). Application steps add no duplicate timing code.

(c) Generic HMI rendering (shall). Because both structures are fixed framework types exposed through the Self-Description Service (§3.10), the HMI shall render them generically for any Unit: a cycle waterfall, a Pareto of per-step Avg/Maximum, and drill-through to module command timing. ExpectedTime is drawn against each step so guard-versus-actual is visible.

(d) Degradation is data, not downtime (should). A step or command whose Avg drifts beyond a configured band above its baseline should raise a maintenance event via the condition-monitoring path (§8.12, Low severity, ReasonCode := E_Reason.CYCLE_TIME_DEGRADED) — creeping cycle time surfaces for planning before it becomes a stop, and the event names the exact step/command (O3).

(e) Bounds & clocks. Profile and stats arrays are fixed-size with a Truncated flag — capture shall never allocate or grow at runtime. Durations are taken from the platform’s monotonic millisecond clock, wall-clock stamps from the synchronized clock (§2.7), so profiles align across tiers and stations ([TC3] sources: TC3 §8.11). Aggregate resets are a deliberate, logged action per §8.11.2, never silent.

(f) Time classification — the real cycle time (shall). Every profiled step carries a time class (E_TimeClass): WORK — the default — or a wait class: WAIT_UPSTREAM (starved: awaiting the next pallet/part/material), WAIT_DOWNSTREAM (blocked: awaiting outfeed/downstream take-over), WAIT_OPERATOR (a §6.11 decision or manual intervention), WAIT_EXTERNAL (host/MES/tool response, §3.15/§11.6). A step declares its class in the step record it already has — one enum argument on the wait steps only (_M_SetStep(…, TimeClass := E_TimeClass.WAIT_UPSTREAM)); every undeclared step is WORK, so the common case costs nothing (O1). The profiler accumulates per-class totals (ByClass) and publishes WorkTime — the real cycle time — and WaitTime alongside Total, so comparing against the design cycle time and OEE performance accounting use work-only time by definition, not by after-the-fact estimation (O3). The wait classes are the per-step attribution of §8.11.3’s Starved/Blocked: WAIT_UPSTREAM/WAIT_DOWNSTREAM totals reconcile with the Unit’s Starved/Blocked accumulators, and the Unit base derives its live Starved/Blocked status from the current step’s wait class — one declaration, two views that cannot disagree (FB_UnitBase). A wait class shall not be used to hide process slowness: only genuine external waits qualify — that is what keeps WorkTime honest.

Cross-references: §6.2 (mode-chain boundaries), §3.16 (Verdict/part events), §8.5 (Station Monitor/OEE), §8.8 (reason vocabulary), §8.11.3 (Starved/Blocked ↔ wait classes), §8.11.4/§8.12 (timing capture & degradation events), §11.6/§11.7 (host & PackML mapping).

§10.5 already requires fieldbus/IPC diagnostics to surface as System alarms. This section generalizes that to a controller-health and condition-monitoring contract, so degradation is visible and trendable before it becomes downtime.

  • Controller health. The station shall monitor primary-task cycle time, jitter, and overruns; CPU and memory load; and, where the hardware exposes them, IPC temperature/fan and storage health. Threshold breaches raise System-category alarms (§8.6) with System-band reason codes — TASK_OVERRUN, TASK_JITTER_HIGH, CPU_LOAD_HIGH, MEMORY_LOW, IPC_TEMP_HIGH — and the live values shall also be exposed through the Self-Description Service for trending/predictive maintenance, not only as pass/fail alarms.
  • Fieldbus & device health. Fieldbus master state, lost frames, slave errors, and distributed-clock sync (FIELDBUS_MASTER_FAULT, DC_SYNC_LOST) surface per §10.5 ([TC3]: EtherCAT specifics, TC3 §10); smart-device links (§3.15) contribute their heartbeat/last-seen. These are System/Low events that shall not be silently swallowed.
  • Condition-based maintenance. A Control Module or device connector may publish condition signals — actuation/cycle counts toward a service interval, drive load/temperature, vacuum/pressure trend — as maintenance events (Low severity, §8.1), distinct from production faults: they inform planning, they do not stop the cycle. Service thresholds are ParCfg (§3.8).
  • Warning vs. alarm. Where a distinct approach threshold is configured, approaching a limit raises a Low/Med warning and exceeding it raises the alarm; otherwise the configured limit produces the single Low System event. The two use Severity (§8.1) on the same reason, so trending and annunciation share one source without inventing a mandatory second threshold for every metric.

The platform-neutral input is ST_SystemHealthInput: task, controller, IPC, fieldbus/DC, and ST_TimeQuality samples with an explicit availability flag for each optional group. Station thresholds and requirements live in schema-first ST_SystemHealthParCfg. A root Unit publishes the validated bounded copy as SystemHealth : ST_SystemHealthStatus; Present=FALSE means the profile was not configured, while Present=TRUE, Healthy=FALSE means one or more required probes are unavailable or outside limits. A reusable FB_SystemHealthPublisher (or equivalent binding implementation) shall own the threshold evaluation and the come/gone edges for the registered Low/System/AUTO_RESET events. Applications inject platform measurements; they shall not reproduce threshold/alarm logic per station. Several root Units on one PLC may mirror the same platform sample into their own bounded status/alarm scope so each independently assigned HMI sees the health affecting that Unit.

Cross-references: §2.3 (task/watchdog sizing), §2.7 (time sync for health timestamps), §10.5 (fieldbus diagnostics — the specific case this generalizes), §3.15 (link health), §8.1/§8.6 (severity, System alarms).

A station’s signal tower (and horn) shall be driven from the existing state and alarm model, in one place, so no station hand-wires lamp logic.

  • Single mapping. The lamp/beacon pattern is a fixed function of the §8.11 machine state and the highest active alarm severity (§8.1/§8.2): e.g. red = DOWN/active fault, amber = warning or BLOCKED/STARVED/CHANGEOVER, green = PRODUCING, blue/white = operator action required (a pending decision, §6.11, or manual step), off = STOPPED. Exact colours and the horn follow the site convention (IEC 60204-1 / ANSI), but the mapping is defined once and reused.
  • Driven by rollup, not by station code. Because state and severity already roll up the tree (§8.2, §8.5), the tower reads the station summary directly; adding or changing a module never touches tower logic.
  • Lamp test. The station shall provide a lamp-test function (operator-triggered) that drives every lamp/horn for a fixed interval to verify the device, then returns to the mapped state.

The reusable mapping publishes semantic outputs ST_SignalTowerOut := {Red, Amber, Green, Blue, White, Horn, TestActive}; only the project Hardware Driver maps those semantics to electrical channels. Site choices (OperatorUsesWhite, HornOnHigh, bounded LampTestDuration) are a schema-first ST_SignalTowerParCfg, never station-specific IF logic. A root Unit publishes SignalTower, derives its inputs from its authoritative MachineState, active alarm table, and decision state, and accepts remote lamp test only through the acknowledged mailbox under the MANUAL gate while the Unit is not BUSY. The test duration shall clamp to 30 seconds or less and self-clear even if the client disconnects.

Cross-references: §8.1/§8.2 (severity & rollup), §8.11 (machine state), §8.5 (station summary), §6.11 (operator-action signal).

8.14 Utility & energy monitoring (optional)

Section titled “8.14 Utility & energy monitoring (optional)”

A station that meters its utilities — electrical power, compressed air, coolant/water — may expose that consumption as a self-describing branch, so energy and utility use are visible for cost, sustainability (ISO 50001), and leak/anomaly detection. This is optional: a station without metering simply omits the branch, so the feature never burdens a simple station (§1.1 O1).

  • Model. Per-station (and optionally per-module) instantaneous and accumulated quantities are published through the Self-Description Service — electrical kWh, compressed-air Nm³, coolant L — each with the synchronized timestamp (§2.7). When the binding-qualified OPC 34100 projection is claimed, these same values shall map to the OPC UA for Energy Consumption Management information model; absence of that optional projection does not invalidate the native energy profile (§1.5).
  • Performance indicators. Combined with the good/NOK counts (§8.11), the Station Monitor (§8.5) may derive energy-per-part EnPIs (e.g. kWh per good part) and publish them north-bound (§11.9) for the plant energy/UNS layer.
  • Anomaly / leak detection. A consumption that drifts from its learned baseline (e.g. a rising idle-air draw) may raise a maintenance event via the condition-monitoring path (§8.12, Low severity, ReasonCode := E_Reason.UTILITY_DEVIATION) — informing planning, never stopping production.
  • Not a safety or interlock function. Utility availability that must gate operation (air-pressure-OK, coolant-flow-OK) remains a permissive/interlock (§7) or a safety alias (§9); §8.14 is measurement and monitoring only and shall not be used to gate motion.

Cross-references: §8.5/§8.11 (Station Monitor, counts for EnPI), §8.12 (condition-monitoring path), §2.7 (timestamps), §7/§9 (utility gating stays an interlock/safety function), §11.9 (north-bound exposure).


9.1 Separation of safety and standard logic

Section titled “9.1 Separation of safety and standard logic”
  • Safety functions shall be implemented in the certified safety system of the binding ([TC3]: Beckhoff TwinSAFE — TwinSAFE Logic plus safe I/O over FSoE / Safety-over-EtherCAT, TC3 §9), authored and validated by a qualified safety engineer, independently of the standard PLC application.
  • The standard application shall treat safety state as read-only: it consumes mapped safety status to gate motion and inform the operator, but shall not implement or substitute a safety function.
  • The safety system shall publish a fixed set of alias signals into the standard application — e.g. AllEstopsOk, AllSafetyOk, per-zone Zone<n>Safe, and per-actuator safe-state feedback. The names are standardized so every station reads safety identically.
  • The standard application gates energize/motion on the relevant alias and raises a Safety alarm (§8.6) with a ReasonCode (§8.8) when an alias drops.

For any actuator whose power can be safely removed:

  • Decouple — the safety system removes enabling power/torque on a safety event (safeDecouple).
  • Evaluate — the standard application detects the safe state via feedback and brings its sequences/commands to a defined safe stop (Hold/Abort, §6), surfacing the first-out reason (§6.9).
  • Energize — re-enable only after the safety condition is restored and a deliberate reset (§9.4). The standard application shall not self-re-energize from a latched safety event.
  • Safety reset shall be a deliberate operator action with the guarded area clear; the standard application shall not auto-restart motion after a safety event.
  • Restart interlocks, guard and light-curtain monitoring, and e-stop handling live in the safety system; the standard application reflects their status and blocks manual functions accordingly (§7.6).

Safety zones map to stations. A zone fault shall roll into the affected station’s Safety alarm and Station Monitor (§8.5–8.6) so downtime is attributed to the true cause.

Manual mode shall not bypass safety. Manual-function release (§7.6) is ANDed with the relevant safety alias, and commissioning gates (§7.5) never override safety.

9.7 Functional-safety lifecycle & PLCopen Safety

Section titled “9.7 Functional-safety lifecycle & PLCopen Safety”

§9.1–§9.6 fix the separation of safety from standard logic. This section adds the lifecycle and library expectations for the safety side itself.

  • Lifecycle. The safety system (§9.1; [TC3]: TwinSAFE, TC3 §9) shall be designed, implemented, and validated per the functional-safety lifecycle of ISO 13849-1 (and/or IEC 62061): the required Performance Level / SIL for each safety function is determined by risk assessment, and verification/validation are performed and documented independently of the standard application.
  • Standard safety functions via PLCopen Safety. Standard safety functions — emergency stop, guard/door monitoring, two-hand control, enabling switch, safe stop — should be built from the certified PLCopen Safety function-block set (the SF_* blocks) rather than bespoke safety logic, for traceability and certifiability.
  • Unchanged interface to the application. None of this changes §9.2: the standard application still consumes only the published safety alias signals (AllEstopsOk, Zone<n>Safe, …) read-only, and never implements a safety function.
  • Change control. Any change to a safety function shall trigger re-validation and follow the management-of-change process (§13); the safety project’s version/identity is tracked separately from the standard application’s (§13, §14.2).

Cross-references: §9.1–§9.2 (separation & alias interface), §9.4 (reset/restart), §13 (MOC & versioning), §14.2 (integrity/identity).

Stations using Control On/Off, independently switched power groups, guard access requests, safety valves, light curtains, keyed bridges, muting, or fieldbus-driven power reactions shall implement SAFETY_AND_CONTROL_POWER_PROFILE.md. The profile fixes an asymmetric interface: the standard PLC may issue untrusted stop/enable/unlock requests, while the certified safety system alone grants safe enable/unlock/reset and publishes verified state. ControlOn is control-domain orchestration; PowerOn is one named energy group. Neither may automatically resume after a safety or communication event.

The Unit forest and the control-domain graph are orthogonal. Every root Unit references zero or one ST_ControlDomainStatus; one domain may serve one or many peer root Units, while an unassigned Unit has no Control-On prerequisite from this profile. A control domain is cell infrastructure, not a fourth tier or a super-root Unit, and sharing it never merges Unit mode/cycle/recipe/OEE/access ownership. Status.ControlDomainId publishes the association; empty means none. Safety devices and power groups publish optional ST_SafetyStatus and ST_ControlPowerStatus facets; Present=FALSE hides an unused capability. Partial valve-island/drive isolation is expressed as an affected-power-group mapping whose execution remains in the validated safety project. Plug-and-produce means descriptor/identity/membership validation and deterministic composition, never live modification of validated safety logic.


  • The binding defines the primary fieldbus ([TC3]: EtherCAT — TC3 §10.1). The fieldbus master(s), topology, and distributed-clock settings shall be documented; device order in the configuration follows the physical/schematic order.
  • Drives, robots, scanners, and sub-buses are integrated as fieldbus devices or through documented gateways.
  • Application logic (CM/EM/Unit) shall access I/O only through the HAL data structure (§3.6); raw %I/%Q references in application logic are not permitted.
  • Symbols mapped to %I/%Q/%M carry the leading _ marker (§4.4) and live at the Hardware Driver layer; the driver presents typed, named signals to the HAL.

10.2.1 Mandatory I/O responsibility distribution

Section titled “10.2.1 Mandatory I/O responsibility distribution”

“Use a HAL” is insufficient unless the surrounding responsibilities are also separated. A conforming application shall distribute I/O integration into the following layers; these are code-ownership boundaries, not additional module tiers:

Layer Owns Shall not own
Framework topology mechanism bounded node/channel registry, bounds and duplicate validation, health propagation, exact-tag diagnostic correlation project tags, terminal order, station-specific HALs, sequence logic
Project I/O catalog the approved engineering-data join: electrical tag, physical address, localization key, unique path, owning module path, and semantic role cyclic value copying, raw %I/%Q access, mode/recipe/sequence behavior, generic registry algorithms
Hardware Driver the only reads/writes of mapped process-image symbols; conversion between physical polarity/scaling and semantic HAL fields; live fieldbus-value refresh mode sequencing, recipes, device state machines, collision logic, HMI presentation rules
Control Module reusable device behavior expressed in semantic roles (Extended, Retracted, Enable, etc.) through its HAL; optional injected I/O identity used in diagnostics terminal models, channel numbers, project electrical tags embedded in the type, direct process-image access
Composition root (MAIN/top-level program) instantiate, one-shot Setup, select real versus simulation drivers, and execute components in documented scan order channel-by-channel mapping, diagnostic matching algorithms, reusable device logic

The dependency direction is fixed: the project catalog configures the generic topology mechanism and injects physical identity into module roles; the Hardware Driver moves live values between process image and HAL/topology; modules consume only HAL semantics; the composition root only wires these participants. An I/O tag/address shall have one project source of truth. Repeating its literal independently in MAIN, a CM, and an HMI publisher is non-conforming even if the values happen to match.

The project catalog is deliberately project-specific and may contain a long generated/imported list; that list is engineering data expressed in code, not a reason to move it into a reusable device type. Conversely, bounds checking, duplicate detection, health propagation, and ST_Diagnostic.IoTag matching are reusable algorithms and shall not be reimplemented by each project catalog. A production toolchain should generate the catalog from the approved I/O list and fail CI on an unmatched or duplicate physical join.

The non-normative implementation guide IO_ARCHITECTURE.md illustrates the dependency direction, scan order, press-example placement, and recommended CI gates.

  • Each physical channel/device has a Hardware Driver (DI/DO/Motor/…); each driver supports a SIM toggle (§3.6, §2.6) selected by configuration.
  • Signal conditioning — debounce, invert, scaling — lives in the driver or CM, not in sequences. Per §5.5 this logic may be written in ST or Ladder.
  • Terminal, channel, and device names shall match the electrical schematic (§4.7); the PLC link uses the schematic name.
  • Drives, axes, robots, and scanners are wrapped as Control Modules exposing the standard handshake (§6.1) and the four-structure contract (§3.12); vendor-specific detail stays inside the CM/driver.

Fieldbus and controller diagnostics — lost frames, slave errors, distributed-clock sync loss, watchdog — shall surface as System alarms (§8.6) with a ReasonCode (§8.8) and shall not be silently swallowed ([TC3]: EtherCAT/IPC specifics, TC3 §10.5).

10.5.1 Fieldbus topology & I/O diagnostics view

Section titled “10.5.1 Fieldbus topology & I/O diagnostics view”

Beyond the logical module tree (§3.13), a maintenance user needs the physical bus picture — which node is down, which channel is stuck — because a field fault is diagnosed at the wiring, not the sequence. The framework therefore defines a platform-neutral fieldbus topology model, published for the HMI over the same self-description surface (§3.10):

  • Nodes. The bus is a tree of nodes (master → slaves/couplers → terminals); each node publishes Name, TypeId (vendor/product), Address (topological + logical), a node state (E_NodeState: OFFLINE < INIT < PREOP < SAFEOP < OPERATIONAL, plus FAULT), and a link-health flag. The state vocabulary is the CANopen/EtherCAT-style state machine expressed neutrally so other fieldbuses map onto it.

  • Channels. Each node publishes its I/O channels: Name, DescriptionKey, Address, Path, ModulePath, Direction (INPUT/OUTPUT), Kind (DIGITAL/ANALOG), live Value (BOOL for digital; scaled REAL + Unit for analog, raw available), per-channel quality/forced/fault flags, an explicit Forceable capability, and — where the binding implements forcing — the held force set-point kept separately from the live value, so a force survives a publish cycle and a cleared force restores the real value rather than freezing the last forced one. Name shall equal the exact tag in the approved I/O list and electrical schematic; it is untranslated structured identity. DescriptionKey is the localizable human description, Address is the terminal/channel locator, Path is the unique force/audit identity (§4.8), and ModulePath cross-links to the owning module. Forceable defaults FALSE; output direction alone never grants a force surface. The names and capabilities are therefore generated/imported from reviewed engineering data rather than independently retyped in the HMI.

  • Runtime validation and engineering-data join. Installed node presence/order and health shall be read from the fieldbus master’s own diagnostics at runtime so the view updates as nodes drop or return. Channel identity, scaling, electrical tags, and module ownership shall come from one reviewed project/toolchain I/O catalog (§10.2.1), because those engineering semantics are not reliably discoverable from a generic live bus. The binding shall validate the configured catalog against runtime node count/order/identity evidence and join channels by deterministic physical address; it shall never guess a missing relationship. Missing, duplicated, mismatched, or unmatched mappings set MappingValid=FALSE with a localizable MappingDiagnostic. Live values come from the same HAL/process-image authority used by the hardware driver. A node’s or channel’s contribution to a module fault uses the same first-out vocabulary (§8.8): matching ST_Diagnostic.IoTag marks the channel and makes module↔fieldbus navigation available. A binding may additionally offer richer runtime identity/channel discovery, but that optional adapter does not replace the reviewed catalog or become a base-conformance requirement.

  • HMI rendering (§3.13). The topology view is a second tree beside the module tree: nodes coloured by state (operational = neutral, degraded SAFEOP/link-warn = warning, FAULT/OFFLINE = error), channels listed with live values, digital as on/off, analog as value + unit. This is a read/diagnostic surface by default. A limited output force is a manual function gated by §7.6 and §7.7 (MANUAL), never a casual click, and constrained by four rules so it can never become a way to defeat the controller:

    1. It exists only in a commissioning build. Output forcing shall be a registered §7.5 engineering gate. In a production build the gate is inactive, Forceable is FALSE on every channel, and the HMI therefore renders no force affordance at all — the surface is absent, not greyed out (§3.9). Whenever the gate is active the station carries the standing §7.5.2 annunciation, so a machine that can be forced always says so.
    2. Explicit capability, outputs only. The HMI exposes a force control only when the PLC publishes Forceable=TRUE, and the PLC resolver rechecks that capability and mapping. A runtime force shall write only such a mapped output channel (energize a valve, drive a lamp) through gated PLC code. Missing capability data is FALSE (fail closed). Forcing an input — lying to the logic to bypass an interlock or sensor — is not provided by this surface; it is a commissioning act performed with the engineering tool under separate authority, never a normal operating practice.
    3. Withdrawn the moment the module can act. The runtime path writes the output variable through the application, so the owning module still runs and still owns its interlocks (§7.2). A force is effective only while its owning Unit is stopped and in MANUAL (§3.4); leaving either condition shall withdraw every force of that Unit rather than leave it contending with live logic. This is deliberate — the force cannot silently override active logic, and it cannot survive into automatic operation.
    4. Safety I/O is never forceable here. Safety-rated I/O lives on the safety system (§9, FSoE/TwinSAFE) and is out of reach of this path by construction; the standard-PLC force cannot touch it.

Every force and clear is a logged §8.3 event (audit trail).

  • Relation to the HAL (§3.6). The logical HAL struct a CM references (§3.6) is mapped onto physical channels in the fieldbus configuration; the topology view exposes that physical layer directly, so a “sensor not made” first-out (a module fault) and “terminal 3 channel 2 = FALSE, node in SAFEOP” (the bus view) are two lenses on the same event — the HMI lets maintenance cross from one to the other.

Cross-references: §3.6 (logical HAL), §3.10 (self-description), §3.13 (HMI trees), §4.8 (browse paths), §8.6/§8.8 (system alarms & reasons), §7.5 (the commissioning gate that enables forcing at all), §7.6/§7.7 (forcing is gated), TC3 §7.5/§10.6 (EtherCAT/ADS binding).

Axes and drives are wrapped as Control Modules (§10.4); this section fixes how their motion is expressed so it is vendor-neutral and reuses the handshake.

  • PLCopen Motion interface. A motion Control Module shall drive its axis through the PLCopen Motion function blocks (MC_Power, MC_MoveAbsolute, MC_MoveVelocity, MC_Home, MC_Stop, MC_Reset, with the standard AXIS_REF), not vendor-specific motion calls. The CM exposes named device commands (e.g. MOVE_TO, HOME) whose internal MC_* Busy/Done/Error/CommandAborted outputs map onto the CM’s PLCopen status (§6.1) — so a motion CM looks identical to any other CM to its parent.
  • Coordinated motion. Multi-axis/coordinated moves shall use the PLCopen coordinated-motion blocks inside the owning CM/EM; the parent still commands a single named action through the §6.1 handshake.
  • Limits & scaling. Axis scaling, soft limits, and velocity/accel limits live in the CM/driver (§10.3); motion targets are validated against them before issue (§5.6). Vendor-specific drive detail stays inside the CM (§10.4).
  • Safety. Safe-motion functions (STO/SS1/SLS) remain in the safety system (§9); the motion CM consumes their status read-only and brings motion to the §6 defined safe stop when an alias drops.
  • Full robots (multi-axis kinematic systems). A complete robot is wrapped as a Control Module fronted by an I_RobotConnector — a specialization of the §3.15 device connector that adds an ID-addressed command surface. A robot framework is more than HMI teaching: it is a motion-planning layer, and the standard’s rule is that all of its geometry and kinematics are taught/generated configuration (§3.8) addressed by stable ID — never a coordinate, waypoint, motion mode, or route in a PLC sequence. One bounded exception is permitted: where a target genuinely cannot be taught because it is located at runtime (vision-guided picking), a coordinate may enter PLC code only as a correction to a taught reference, never as an absolute pose, and shall be validated against a configured envelope before motion — a runtime pose is untrusted input (§14). A PLC-enumerated trajectory remains prohibited in every case. Specifically: points and paths (point-lists run by ID or sub-range, each point’s motion mode — Joints/PTP/Linear, absolute/blended — taught data); generated trajectories (the application template assembles the route between a named from and to position at runtime, so the PLC issues MOVE_TEMPLATE(from,to) and never enumerates waypoints); planning areas (3-D zones for collision-free recovery from an undefined pose after an E-stop/mode change via MOVE_FROM_AREA (area-resolved), with deterministic priority — distinct from the §9 functional-safety system, which stays read-only and gates a deliberate §9.4 reset); and parametric/symmetric pallets plus chained reference frames (a grid generated from a few taught corners, frames defined relative to frames, so a moved fixture is re-taught in one place). The parent commands named/ID-addressed actions through the §6.1 handshake; a point, a 26-point path, a generated route, or a pallet nest is one command that runs to completion, so the robot looks identical to any other CM. In practice a thin robot-handling Equipment Module exposes the station’s semantic operations (PICK_PART/PLACE_PART/SCAN_PART/PROCESS_PART…) above the robot CM’s primitives, adding no device logic (§3.5). Route generation is expressed as declarative routing data (a help/nest graph plus a per-nest help-affinity list) resolved by one generic planner in the connector — so a work position served by two or more help points is a native table entry, not hand-coded per-station branching — and area-resolved motion (MOVE_FROM_AREA) is the primary form, with pose recovery its extreme case. Link supervision (§3.15.2), validation before motion (§5.6) and read-only safety (§9) all apply, and robot commands are not auto-repeated on error (resumption is deliberate, mirroring §3.15/§9.3). Three device facts are mandatory for a conformant robot CM, because none is derivable from the rest of the contract and a cell cannot be operated safely without them. (i) Operating mode is a request/report pair: the PLC shall request a controller operating mode and publish separately what the controller reports it actually is, shall default to the most restrictive supported mode on start-up or loss of report, and shall reject a command the reported mode does not permit rather than issue one the controller will ignore. Mode is read-only status and is never treated as a safety grant (§9). (ii) Speed is a bounded scale held as configuration: a per-mode station ceiling and a per-recipe process scale compose as their minimum, so reduced speed outside automatic is a property of the module type rather than per-project habit; a scale outside its configured band is rejected before motion (§5.6). Both are scalars — no coordinate or motion mode enters PLC code. (iii) A protective stop is not a safety function: collision/crash protection is detected and acted on by the ordinary PLC, shall carry its own reason distinct from the §9 safety reason so the alarm record does not misreport a process event as a safety event, and shall not resume automatically. A handling application shall additionally prove possession — part-present verified after grip and before release — rather than infer it from the gripper command. Two further requirements follow from the same reasoning. A robot honours §6.1 HELD on its path: a suspended motion shall stop on the programmed path retaining its resume point and continue from that point when the named condition returns; the connector shall publish whether resumption is still valid, and a resume requested after the arm has left the retained path shall be refused rather than executed. The active load case should be maintained as the robot grips and releases, because a move computed for the wrong mass degrades accuracy and brake margin silently. The framework controls robots regardless of model or manufacturer by capturing per-model facts (signal counts, Euler conventions, available functions) as data the connector reads — so a portable, vendor-neutral teaching connector is the recommended default implementation; per-manufacturer connectors may implement the same I_RobotConnector as conformant alternatives, with the parent Unit unchanged in either case. Exposing a robot through the portable framework is an optional conformance profile (claimed like §11.7), not a mandate, but is the recommended path. See Annex I.

Cross-references: §10.3/§10.4 (driver, CM wrapping, limits), §6.1 (handshake/status mapping), §5.6 (target validation), §3.15 (device connector & link supervision — the robot connector specializes it), §3.8 (taught points/frames/tools are recipe-class configuration), §9/§9.7 (safe motion stays in the safety system), §10.7 (routing model), Annex I (robot CM worked example).

10.7 Declarative routing model (help/nest graph & help affinity)

Section titled “10.7 Declarative routing model (help/nest graph & help affinity)”

Promoted to Core from Annex I §I.9–§I.10; Annex I remains the worked realization. Where a motion system generates routes between taught positions at runtime (§10.6 robots being the primary case), the routing knowledge shall be declarative configuration resolved by one generic planner in the connector — never per-station imperative traversal code.

(a) Position classes. Positions are two classes: help points (auxiliary wait/transit positions) and nests (work positions).

(b) The route graph is data. The application supplies configuration, not code:

TYPE ST_RouteGraph : STRUCT
HelpAdj : ARRAY[1..MAX_HELPS, 1..MAX_HELPS] OF BOOL; // help↔help adjacency (allowed transits)
NestHelp : ARRAY[1..MAX_GRIPPERS, 1..MAX_NESTS] OF ST_NestHelpAffinity; // per-gripper; each nest → one OR MORE serving helps
DirectNest : ARRAY[1..MAX_NESTS,1..MAX_NESTS] OF DWORD; // optional direct nest→nest list id (else via help)
END_STRUCT

The planner builds from → departHelp → (help-graph search) → approachHelp → to generically for every station. If the graph yields no path, the planner shall return a no-route first-out (registered in the implementing type’s band, §8.8 — e.g. the robot CM’s ROBOT_NO_ROUTE) and the fronting CM raises a clean fault (§5.6) rather than an undefined move. Per-edge overrides are optional data, not code.

(c) Multi-help work positions are native. A nest carries a help-affinity list — one or more help points, each tagged with a role (APPROACH / DEPART / EITHER, default EITHER) and, optionally, the transit region it serves:

{attribute 'qualified_only'} TYPE E_HelpRole : (EITHER := 0, APPROACH := 1, DEPART := 2) DINT; END_TYPE
TYPE ST_HelpAffinity : STRUCT
HelpId : DWORD; // a help point serving this nest
Role : E_HelpRole; // APPROACH into the nest / DEPART from it / EITHER (default)
RegionId : DWORD; // OPTIONAL transit region this help connects to (0 = any)
END_STRUCT
TYPE ST_NestHelpAffinity : STRUCT
Helps : ARRAY[1..MAX_HELPS_PER_NEST] OF ST_HelpAffinity; Count : INT;
END_STRUCT

The planner resolves the serving help role-first — direction is the higher-consequence constraint (a wrong-direction corridor can drive the tool into the fixture; a wrong region is only a longer, still-safe route) — and uses region/proximity only to break ties among same-direction corridors. Region is therefore required only on a nest with two corridors for the same direction. An unresolvable nest shall yield a no-help-for-nest first-out (e.g. ROBOT_NO_HELP_FOR_NEST), never a silent mis-route. Multi-help is the general case; single-help is the trivial one (Count := 1).

(d) Reversal & disposition by construction. A reversal (e.g. NOK disposition) is an ordinary move with a different destination — no special mode. Two rules keep it safe and loud: entry corridors default to EITHER (a nest is exit-able the way it was entered unless its geometry is physically one-way, in which case a reversal fails with the no-help first-out); and retract is a separate path definition, not the approach played backwards, so extraction geometry may differ from insertion.

(e) Paid once, tested once. The planner and help resolver are part of the connector type and are verified by the type’s test suite (§5.7; worked cases: Annex I §I.14) — a station that adds a multi-approach nest adds a table row, not logic (§1.1 O1, O3, O4).

Cross-references: §10.6 (robot CM — the primary consumer), §3.15 (connector owns the planner), §8.8 (registered first-out reasons), §5.6 (validate-then-move), Annex I §I.9–§I.11 (worked realization incl. area-resolved motion).


  • Every binding shall expose the Fraktal Self-Description Service of §3.10 and document its default transport, endpoint/gateway components, protocol/schema version, and any alternative projections. The service publishes only explicitly deployed roots and explicitly registered standalone data; implementation-only references/handles are excluded.
  • Fraktal/TC3 uses TF6100 OPC UA by default (TC3 §3.10/§11.1). Fraktal/AB uses EtherNet/IP explicit messaging through the Fraktal gateway by default and may expose OPC UA as an alternative projection (AB §3.10/§11). Neither choice changes the Core service model.
  • Canonical identity follows §4.8: each local hierarchy segment equals the local PLC/schematic instance name, while Status.Name carries the complete dotted module path. Every projection shall retain that identity.
  • The selected endpoint(s), logical application namespace, protocol/schema version, and station identity shall be documented per station. A native hierarchical server may expose the namespace directly; a gateway may reconstruct it from the binding manifest and bounded value services.
  • Command-capable transports shall provide authenticated principals, integrity and confidentiality appropriate to the declared IEC 62443 conduit, and least-privilege roles (operator / maintenance / engineering). Anonymous or unauthenticated write access is not permitted. A projection that is read-only shall state that restriction explicitly.
  • A binding-specific security mechanism belongs in that binding: [TC3] certificate trust and sign-and-encrypt policy are defined in TC3 §11.1; [AB] gateway/controller trust boundaries and EtherNet/IP/OPC UA alternatives are defined in AB §11.

The Flutter operator app and any MES/SCADA connect through a binding adapter and render or consume the model generically (§3.10, §3.13). No client-specific symbol wiring is added to the PLC and no transport-specific address becomes the module’s canonical identity.

A command-capable client shall distinguish and report transport reachability, transport authentication/session readiness where applicable, Fraktal namespace/schema compatibility, root discovery, request staging/commit, controller acknowledgement, and controller acceptance as separate states. It shall not infer command success from a connected session or a successful transport write alone: arguments are committed through the root mailbox and command success requires the matching acknowledgement plus Accepted=TRUE. LOGIN is the deliberate exception: Accepted confirms that the attempt was consumed, while authentication success is the resulting access state defined by §7.7(c). Repeated value refresh shall not starve or reorder a command, and reconnect shall not replay an unacknowledged write (§3.10, §3.13, §14).

  • Recipe/type sources (LOCAL / OPCUA / SOCKET_JSON|XML / REST, §3.8) are configured behind the logical I_RecipeProvider capability; transport endpoints and credentials are documented per station and never embedded in module logic.
  • External payloads are validated before load (§3.8); a failed or partial fetch faults the consuming module with a ReasonCode (§8.8) rather than loading a half-recipe.

The alarm queue and AlarmQueueHandler (§8.3) publish to the alarm database/historian using the module’s canonical path as the record path and the ReasonCode/catalog of §8.8, so PLC, HMI, historian, and MES share one address and one reason vocabulary.

11.6 MES / ISA-95 host-event & transaction mapping

Section titled “11.6 MES / ISA-95 host-event & transaction mapping”

§3.16 defines part events inside the PLC; this section fixes how the cell talks to L3 (MES), so integration is a mapping rather than a per-project build. The cell exposes a fixed host-event set and maps it to ISA-95 (IEC 62264) concepts — aligning with the PackML Administration-tag idea that higher-level systems consume performance and part data through a standard structure.

The cell shall emit only these host events; sites do not invent new ones without extending this table:

Host event Source ISA-95 / L3 meaning
PART_RECEIVED / PROCESSING_STARTED / PROCESSED / PROCESSING_ABORTED §3.16 material/product tracking + production response (verdict, genealogy)
CHANGEOVER_STARTED / CHANGEOVER_DONE accepted Start / successful completion of the Unit CHANGEOVER sequence (§3.4) work-order / product-definition change
TOOL_CHANGED / MATERIAL_CHANGED EM/Unit resource/material lot change
MODE_CHANGED OnModeChanged (§3.14) equipment operational-mode change
NOK / scrap performance capture (§8.11) quality / scrap transaction

Each event shall carry: the producing station canonical path (§4.8), the part Uid where applicable (§3.16), a synchronized timestamp (§2.7), the Verdict/result, and the ReasonCode (§8.8) for an abort/NOK — so an MES receives a self-describing, reason-coded record.

  • A root Unit shall publish one bounded, read-only HostEvents object through the Self-Description Service, containing a ring of ST_HostEvent records plus RingHead, valid Count, published Capacity, and an explicit Wrapped data-loss indicator. ST_HostEvent carries a monotonic sequence, fixed event kind, station path, optional part Uid/subject/value, timestamp and synchronization quality, verdict, and reason. It is on-demand data and never a command surface. Clients derive modulo/ring traversal from Capacity; they shall not duplicate the binding’s array limit.
  • The same record may additionally be delivered over OPC UA A&C, socket/REST, or MQTT-Sparkplug (§11.9) behind the logical I_HostEventSink capability, mirroring provider injection (§3.8/§11.4), so delivery transport is composition rather than Unit logic. The bounded PLC ring remains available when an optional sink is absent or unavailable.
  • The event shape should map cleanly to ISA-95 / B2MML transactions (production performance, material lot/genealogy), so an MES that speaks B2MML consumes the cell without a bespoke driver.

Host events are produced by the cell; commands into the cell (work order, recipe selection) arrive through the recipe/type path (§3.8) or a release-gated method, are treated as untrusted third-party input (validate per §3.8 and §14), and shall not bypass mode/release rules (§3.4, §7.6).

Cross-references: §3.16 (part events), §2.7 (timestamps), §8.8 (reason vocabulary), §3.8/§11.4 (provider injection), §14 (untrusted input).

11.7 PackML / OPC UA line-coordination profile

Section titled “11.7 PackML / OPC UA line-coordination profile”

Interoperability note (Annex J). The same projection philosophy extends to MTP (VDI/VDE/NAMUR 2658 / IEC 63280): a root Unit exports as a PEA — services from its runnable modes, DataAssemblies from the Status mirror (§3.10), parameters from §3.8, alarms from §8.3 — so any MTP-conformant orchestration layer (POL) can integrate a Fraktal station with no bespoke driver. The mapping, its honest mismatches, and the exporter checklist are Annex J.

§6.6 introduces PackML as an optional overlay. This section defines the binding-qualified PackML/OPC UA conformance option: only a deployment claiming that option shall expose the complete OPC 30050 projection below. The native ExecState/mode model (§6.1, §3.4) remains the internal source of truth, and a binding or deployment that does not claim this optional projection remains conformant to base Core (§1.5).

The native execution state and Stop/Hold/Abort transitions shall map to the PackML state machine:

Native (§6.1/§8.2) PackML state
READY, idle Idle (via Resetting → Idle)
Start requested Starting → Execute
BUSY, cycling Execute
Stop after cycle (§3.14 OnModeExit) Completing → Complete, or Stopping → Stopped
Hold (§6) Holding → Held → Unholding
Blocked/Starved (§8.11) Suspending → Suspended
ERROR / fault hold (§8.2) Aborting → Aborted → Clearing

E_Mode (§3.4) maps to PackML Unit Modes; unsupported-mode rejection (§3.7) maps to a refused SetUnitMode:

E_Mode PackML Unit Mode
AUTO Producing
MANUAL Manual
CHANGEOVER / CALIBRATION / HOME Maintenance (or site-defined custom modes)

11.7.3 PackTags (Command / Status / Administration)

Section titled “11.7.3 PackTags (Command / Status / Administration)”

The profile shall expose the three PackTag groups, sourced from contracts the standard already defines — so PackML is a projection, not new logic:

  • Command — UnitMode, CntrlCmd (Start/Stop/Hold/Reset/Abort), MachSpeed, material/equipment interlocks. Consumed through SetUnitMode / SetMachSpeed methods and mapped onto the native SetMode/Start/Stop (§3.3/§3.4) and release rules (§7.6).
  • Status — UnitModeCurrent, StateCurrent (from §11.7.1), MachSpeedActual, equipment-interlock status.
  • Administration — alarms (from §8, with the §8.8 reason as the PackML alarm id and the first-out StopReason from §6.9), and the production/performance counters and cycle times from §8.11. The Admin group is where higher-level systems read performance and stop-reason data.

When the PackML/OPC UA profile is claimed, the mapping above shall be complete and validated, and exposed through a PackMLObjects folder in that OPC UA projection. The conformance claim shall name the binding (for example Fraktal/TC3 + PackML/OPC UA). The native model is unaffected; this profile is an additional north-bound interface, coexisting with the ISA-95 host events (§11.6).

Cross-references: §6.6 (overlay intro — now specified here), §3.4/§3.7 (modes & rejection), §8/§8.8/§8.11 (alarms, reasons, counters), §11.1 (Self-Description endpoint), §11.6 (ISA-95 events — complementary).

11.8 Module self-description portability (AAS & MTP mapping)

Section titled “11.8 Module self-description portability (AAS & MTP mapping)”

The self-describing module tree and generic HMI of §3.10/§3.13 are conceptually the same artifact as the Industrie 4.0 Asset Administration Shell (AAS, IEC 63278) and the modular-automation Module Type Package (MTP, VDI/VDE/NAMUR 2658, advancing as IEC 63280): a vendor-neutral, importable description of a module’s identity, services, communication, and HMI. To make the cell portable into AAS-/MTP-aware tooling, the standard defines an export mapping generated from the same self-description — the native model stays the runtime source of truth; the AAS/MTP artifacts are a generated projection, like §11.7.

Each module (Unit/EM/CM) maps to an AAS asset with submodels drawn from contracts already present:

AAS submodel Source in this standard
Nameplate / Identification module Name, ModuleType, canonical path (§3.2, §4.8)
TechnicalData ParCfg schema (§3.8), feature flags (§3.9)
OperationalData State, ModeActive, ST_Diagnostic (§3.2, §8.8)
ModuleContract (custom) the four-structure contract (§3.12) + handshake surface (§6.1)
Documentation linked drawings/manuals per project

The MTP manifest is assembled from the same model: module commands/modes (§3.4/§3.5) → MTP Services; the Self-Description Service records (§3.10) → MTP Communication; the tile/detail rendering (§3.13) → the MTP HMI template. The result is a manifest a Process Orchestration Layer can import for plug-and-produce, consistent with RAMI 4.0.

The AAS/MTP export is an optional, binding-qualified conformance profile. When claimed, it shall be generated from the live self-description (never hand-maintained in parallel) so it cannot drift from the running cell, and it shall carry the same canonical paths (§4.8) as every other interface, so AAS, MTP, OPC UA, HMI, and MES all address the module identically.

Cross-references: §3.10/§3.13 (self-description & generic HMI — the source), §3.12 (data contract), §4.8 (one address everywhere), §11.7 (sibling north-bound profile).

11.9 North-bound telemetry (OPC UA Pub/Sub, MQTT Sparkplug, UNS)

Section titled “11.9 North-bound telemetry (OPC UA Pub/Sub, MQTT Sparkplug, UNS)”

§11.1’s Self-Description Service supplies secured control and on-demand reads through the selected binding transport. For telemetry fan-out to many consumers and for IIoT/cloud and a plant Unified Namespace (UNS), the cell may additionally publish its data.

  • Optional publish path. The cell may expose a north-bound profile over OPC UA Pub/Sub (IEC 62541-14) or MQTT with Sparkplug B, publishing a projection of the same self-describing model (§3.10): state, modes, diagnostics (§8.8), performance (§8.11), and health (§8.12). This supplements, never replaces, the secured command/on-demand service.
  • UNS-aligned addressing. Published topics/datasets shall be keyed by the module’s canonical path (§4.8) so the UNS topic hierarchy mirrors the module tree — one address across the native service, OPC UA, HMI, MES, AAS/MTP (§11.8), and the UNS.
  • Liveness by design. Sparkplug birth/death certificates (or Pub/Sub keep-alive) give consumers connection liveness without polling — the publish-side analogue of the link-supervision philosophy (§3.15).
  • Security. The publish path is subject to §14: broker/endpoint authentication and TLS, least-privilege topics, no anonymous publish, and it lives on a documented conduit (§14.1).

Cross-references: §11.1 (client/server control interface — primary), §3.10/§4.8 (self-description & one address), §8.8/§8.11/§8.12 (published content), §11.8 (AAS/MTP siblings), §3.15 (liveness philosophy), §14 (security/conduits).

11.10 Field-level peer & device exchange (OPC UA FX) — optional/emerging

Section titled “11.10 Field-level peer & device exchange (OPC UA FX) — optional/emerging”

§11.7 projects the cell upward to a line controller (machine-to-line) and §3.15 reaches outward to a single smart device. OPC UA FX (Field eXchange) covers the third direction: deterministic controller-to-controller (C2C) and device-to-device (D2D) peer exchange across the field level, typically over TSN for motion-grade timing. It is the standards-based path for stations to coordinate directly with each other and with OPC-UA-capable devices.

  • Optional / watch profile. Cross-vendor FX tooling is still maturing (multi-vendor demonstrations ongoing through 2026), so FX is a may, not a shall. It is recommended where multi-station or multi-vendor-robot coordination is in scope (e.g. an automotive line where adjacent stations or differently-branded robots hand off in lockstep, or gateway-free device integration); pilot it before committing it to a shall.
  • Projection, not new logic. What a station publishes or consumes over FX shall be a defined slice of the same self-describing model (§3.10) — typically handshake-level command/status (§6.1) between peer stations, or to a device — keyed by the module’s canonical path (§4.8). FX adds a peer interface; it does not introduce a second control path or duplicate logic.
  • Relationship to §3.15. The smart-device connector (§3.15) fronts proprietary links (vendor sockets, S7, REST); FX is the standards-based alternative for OPC-UA-capable peers and devices. The same link-supervision philosophy applies — connection establishment, liveness, and a defined loss reaction (HOLD/ABORT/MODE_STOP, §3.15) — expressed over FX connection monitoring rather than a bespoke heartbeat.
  • Time & security. FX over TSN shares the synchronized time domain of §2.7; the FX conduit is subject to §14 (authentication, TLS, documented conduit, least privilege).

Cross-references: §11.7 (machine-to-line — complementary direction), §3.15 (proprietary-link sibling & loss-reaction philosophy), §3.10/§4.8 (projected model, one address), §2.7 (TSN time domain), §14 (conduit security), §11.1 (client/server control interface — unaffected).

11.11 Discovery & identification base model (OPC UA for Machinery) — optional

Section titled “11.11 Discovery & identification base model (OPC UA for Machinery) — optional”

OPC UA for Machinery (the umati base companion specification, OPC 40001) defines reusable building blocks — identification/nameplate, finding all machines, components, item state/monitoring, preventive maintenance, job management, and energy — so that any MES or dashboard discovers any machine uniformly, regardless of vendor. Because the cell already carries a self-describing tree (§3.10), conforming its identity, state, and component nodes to this base model lets third-party/umati tooling discover the cell with zero custom mapping. Like §11.8, this is an optional, generated projection — the native model stays the source of truth.

The recursive model maps onto the Machinery building blocks unusually directly — in particular, the spec’s Components concept (a machine may contain other machines, each with its own Identification) is the standard’s Unit→EM→CM tree (§3.2, O4):

Machinery building block Source in this standard
MachineIdentification (Identification AddIn) Name/ModuleType (§3.2), version/identity (§13), browse path (§4.8) → ProductInstanceUri, Manufacturer, Model, SerialNumber, SoftwareRevision
Machines object (find all machines) the station(s) exposed on the cell’s server (§11.1)
Components (recursive, each with Identification) the child modules of the tree — each Unit/EM/CM is a Component (§3.2, §3.11)
MachineryItemState / Monitoring the machine-state set (§8.11) and State (§3.2)
Preventive Maintenance condition-monitoring signals (§8.12)
Job Management (ISA-95 / ISO 22400 based) the MES host events (§11.6)
Energy the utility/energy nodes (§8.14, OPC 34100)

When claimed, the Machinery mapping shall be generated from the live self-description (never hand-maintained), and shall carry the same canonical paths (§4.8) as every other interface. It is a sibling projection to AAS/MTP (§11.8) and the PackML profile (§11.7): the same cell, addressed identically, speaking one more discovery dialect.

Cross-references: §3.2/§3.11/§4.8 (identity, recursive components, one address), §8.11/§8.12/§8.14 (state, maintenance, energy blocks), §11.6 (job management ↔ ISA-95 events), §11.7/§11.8 (sibling projections), §13 (version/identity for the nameplate).


This section fixes the annexes’ scope so they exercise every contract end-to-end. The annexes are worked examples of the TC3 binding (repository fraktal-tc3): each demonstrates Core contracts through TC3 mechanics and carries a one-line “Core concepts demonstrated / TC3 mechanics used” header identifying the seam.

  • Annex A — Control Module: separator/stopper (a workpiece-carrier separation device): recipe via I_RecipeProvider, the PLCopen handshake (Execute/Busy/Done/Error/ErrorID), a first-out ST_Diagnostic with a real E_Reason, interlocks drawn in Ladder with device logic in ST, and the tile/detail HMI views. (Drafted — see companion Annex_A_Separator_ControlModule.md.)
  • Annex B — Equipment Module: clamp (cylinder + two sensors) packaged as a reusable sub-tree type (§3.11), commanding its CMs through the handshake. (Drafted — see companion Annex_B_Clamp_EquipmentModule.md.)
  • Annex C — Unit: station with an AUTO mode SFC step chain orchestrating the EMs, mode cascade to a child Unit, and the stall-diagnostic walk surfacing on the Unit’s HMI view. (Drafted — see companion Annex_C_Station_Unit.md.)

Annexes A–C predate the §3.14–§3.17, §8.9–§8.13, §9.7, §10.6, §11.6–§11.9 and §14 contracts. The following annexes extend the set so every contract is exercised end-to-end; they reuse the Annex A–C station so each new feature is shown in context rather than in isolation:

  • Annex D — External device & link supervision (§3.15): a smart device (programmable power supply or robot) wrapped as a Control Module through I_DeviceConnector — heartbeat, the configured loss reaction, bounded reconnect with no self-resume, and the link fault rolling up the §6.9 stall walk to the Unit view. (Drafted — see companion Annex_D_ExternalDevice_LinkSupervision.md.)
  • Annex E — Traceability & MES (§3.16, §11.6): a station reading a part carrier (RFID), accumulating an ST_PartResult, emitting the four part-lifecycle events, and mapping them to ISA-95 host transactions; shows a NOK attributed by ReasonCode and written back before EVENT_PART_PROCESSED. (Drafted — see companion Annex_E_Traceability_MES.md.)
  • Annex F — PackML / OPC UA profile (§11.7): the Annex C InfeedUnit projected onto the PackML state machine and PackTags (Command/Status/Admin), with SetUnitMode/SetMachSpeed, demonstrating line coordination with no change to the native model. (Drafted — see companion Annex_F_PackML_OPCUA_Profile.md.)
  • Annex G — Motion Control Module (§10.6, §5.6): an axis CM driving PLCopen MC_* blocks behind the standard handshake, with target validation against axis limits and a safe stop on a dropped safety alias. (Drafted — see companion Annex_G_Motion_PLCopen.md.)
  • Annex H — Module test suite (§5.7): a Control Module type with a TcUnit suite run against the simulated HAL — asserting the handshake, the first-out diagnostic (ReasonCode/SourcePath), and an interlock reaction, plus an integration test asserting the Annex B rollup — and the CI wiring that gates the merge. (Drafted — see companion Annex_H_Testing_TcUnit.md.)
  • Annex I — Robot Control Module (§10.6, §3.15): a complete robot — including its motion-planning framework — as a Control Module (I_RobotConnector) with a thin handling EM for semantic PICK/PLACE/SCAN/PROCESS above it. ID-addressed points/paths/pallets with no coordinates, motion modes, routes, or help choices in code; declarative routing (a help/nest graph resolved by one generic planner) replacing per-station imperative methods; native multi-help work positions (a per-nest help-affinity list resolved from the move’s endpoints — turning the reference framework’s hand-coded two-help workaround into a table row); area-resolved motion and pose recovery kept distinct from the §9 safety system; parametric/symmetric pallets, per-gripper nests, and chained frames. Faults (unreachable point, no route, no help for nest, unresolved area, dropped link) roll up the §6.9 stall walk with no per-robot code. Validated against a real portable-robot manual and TwinCAT application export. An optional conformance profile composing with Annexes E, F and H. (Drafted — see companion Annex_I_Robot_ControlModule.md.)

The remaining new contracts do not need a standalone annex: operator dialogs (§6.11) and the signal-tower mapping (§8.13) are shown inline in Annex C’s HMI; system health (§8.12), the lifecycle hooks (§3.14), defensive coding (§5.6), the AAS/MTP export (§11.8), north-bound telemetry (§11.9), utility/energy monitoring (§8.14, optional), and cybersecurity (§14) are cross-cutting and are demonstrated by the cell as a whole rather than a single object. Where a future annex touches them, it shall reference the relevant section rather than re-specify it.

Each annex shall show the same object in simulation and on hardware to demonstrate the unchanged contract (§2.6).


  • This standard is versioned; each project records the standard version and the framework-library version it targets.
  • The framework library follows semantic versioning. A breaking change requires controls-engineering sign-off and a migration note; projects adopt new major versions on a planned basis, not silently.
  • Deviations approved under §1.5 are recorded in a project deviation register with rationale, scope, approver, and date.
  • Changes to this standard are proposed through controls engineering; superseded requirements are retained as history so existing projects can be assessed against the version they targeted.

14. Cybersecurity (IEC 62443 & secure coding)

Section titled “14. Cybersecurity (IEC 62443 & secure coding)”

Functional safety (§9) protects people from the machine; cybersecurity protects the machine and its data from the network. They are separate disciplines and this standard treats them separately. Binding endpoint security (§11.2) is necessary but is only one control; this section frames the cell within IEC 62443 and mandates secure-coding practice.

  • Target SL. Each project shall declare a target Security Level (IEC 62443-3-3, SL 1–4) for the cell, sized to its risk; the controls below scale to that target.
  • Zones & conduits. The cell shall be placed in a defined zone, with documented conduits to each external party — line/MES, engineering, and any smart-device sub-network (§3.15). Each conduit declares its protocol, direction, and security policy. The conduit to engineering (project download/debug) shall be access-controlled and shall not be permanently open on the production network.

The standard shall apply the recognized secure-PLC-coding practices; most are already required elsewhere and are gathered here:

  • Validate all external input. Recipe/host payloads (§3.8/§11.4), carrier/part data (§3.16), and command arguments and array indices (the defensive-coding rule, §5.6) shall be range/format-checked before use, faulting with a ReasonCode rather than acting on bad data. This is both a reliability and a security control.
  • Fail safe by default. Outputs are non-stored and step-bound (§6.10); a lost link (§3.15), lost recipe (§3.8), lost time sync (§2.7), or lost safety alias (§9.2) drives a defined safe reaction, never an undefined state.
  • Least privilege. Authenticated binding roles (operator / maintenance / engineering, §11.2) shall gate writes, mode changes, shelving (§8.10), and reconnect/manual functions (§7.6); anonymous or unauthenticated write is prohibited.
  • No secrets in source. Endpoints, credentials, and keys shall be configuration/secret-store values (§11.4, §3.15), never literals in module code or version control.
  • Integrity & monitoring. The running project/firmware shall carry a version/identity stamp (§13) checkable at runtime; fieldbus, IPC, and link anomalies surface as System alarms (§8.6, §10.5, §3.15) so tampering or unexpected disconnects are visible, not silent.
  • Minimize attack surface. Unused services/ports on the IPC shall be disabled; only the documented conduits (§14.1) are reachable.

Security-relevant changes — conduit/endpoint changes, role changes, credential rotation — shall follow the change process of §13 (MOC), and the audit log shall record privileged actions (writes, mode changes, shelving, downloads).

Cross-references: §9 (functional safety — separate discipline), §11.2 (binding endpoint security), §3.8/§11.4 (validated providers), §3.15 (device conduits/links), §3.16 (part-data input), §5.6 (defensive coding), §13 (MOC & versioning).


End of Fraktal Core — Part I (draft, §1–§14). Platform binding: Fraktal_TC3_Part_II.md (Fraktal/TC3).