Annex D — Worked Example: External Device & Link Supervision

Companion to Fraktal Core (Part I) exercised through the Fraktal/TC3 binding (Part II); slots under Core §12. Core concepts demonstrated: device connector & link supervision (§3.15), loss reactions, bounded reconnect with no self-resume, link fault in the stall walk (§6.9/§8.2). / TC3 mechanics used: TCP socket/transport FBs, TON/SysTime, OPC.UA.DA pragmas (TC3 §3.10). Reference implementation — illustrative, not compile-tested; validate against the pinned TwinCAT version and your transport library.

This annex builds the external device connector tier (§3.15) and shows the one thing the I/O-bound annexes (A–C) can’t: a networked smart device whose dominant failure mode is the link itself going away. It demonstrates the I_DeviceConnector contract — heartbeat, a configured loss reaction, bounded reconnect with no self-resume — and shows a dead link rolling up through the same stall walk (§6.9) as any sensor fault, with no per-device diagnostic code.

The station from Annexes A–C gains a programmable DC power supply over TCP (a typical end-of-line-test device). The supply is fronted by a Control Module so the Unit commands it like any other CM and never sees the protocol:

InfeedUnit (FB_InfeedUnit : FB_Unit) ← Annex C
├─ Separator1 (FB_SeparatorCM) ← Annex A
├─ ClampStation (FB_ClampEM → CylA, CylB) ← Annex B
├─ FixtureUnit (FB_FixtureUnit : FB_Unit) ← Annex C
└─ Supply1 (FB_SupplyCM, Control Module) ← here
└─ _conn (FB_PsConnector : I_DeviceConnector) ← TCP session + heartbeat

D.1 Reasons (Framework band — already registered, §8.8)

Section titled “D.1 Reasons (Framework band — already registered, §8.8)”
// E_Reason — external device / link supervision (Framework 2010–2019)
// LINK_TIMEOUT := 2010 // heartbeat lapsed beyond LinkTimeout
// DEVICE_NOT_READY := 2011 // session up, device reports not operable
// DEVICE_PROTOCOL_ERROR := 2012 // malformed / refused exchange
{attribute 'qualified_only'}
TYPE E_LinkReaction : (HOLD := 0, ABORT := 1, MODE_STOP := 2) DINT;
END_TYPE

The connector owns the socket and the heartbeat; nothing above it sees the protocol. Heartbeat here is a cyclic identity/measure query whose reply must arrive within LinkTimeout; consecutive misses drop Linked.

// Publication is inherited from the explicitly marked deployed root instance.
FUNCTION_BLOCK FB_PsConnector IMPLEMENTS I_DeviceConnector
VAR
ParCfg : PsLinkParCfg; // Endpoint, LinkTimeout, Reaction, BackoffMin/Max
_name : STRING(80);
_sock : FB_EthSocket; // transport (vendor/stack detail stays in here)
_hbReq : FB_PsQueryIdentity; // the cyclic liveness exchange
_tHb : TON; // heartbeat-due timer
_tLoss : TON; // loss-confirm timer (PT := LinkTimeout)
_tBkoff: TON; // reconnect backoff
_linked: BOOL;
_diag : ST_Diagnostic;
_lastSeen : DT;
END_VAR
METHOD Setup : BOOL
VAR_INPUT Name : STRING(80); Endpoint : STRING(255); Recipe : I_RecipeProvider; END_VAR
THIS^._name := Name; ParCfg.Endpoint := Endpoint;
// recipe wiring (LinkTimeout, Reaction, backoff) as Annex A …
METHOD Connect : BOOL _sock.Open(ParCfg.Endpoint); Connect := TRUE;
METHOD Disconnect : BOOL _sock.Close(); _linked := FALSE; Disconnect := TRUE;
PROPERTY Linked : BOOL Linked := _linked;
PROPERTY LastSeen : DT LastSeen := _lastSeen;
PROPERTY LinkReason : ST_Diagnostic LinkReason := _diag;
// ---- cyclic ----
METHOD Cyclic
IF NOT _sock.Connected THEN
_M_EnterLost(E_Reason.DEVICE_NOT_READY, 'Session down');
_M_Reconnect(); RETURN;
END_IF
// heartbeat: issue query when due, watch for reply within LinkTimeout
_tHb(IN := NOT _tHb.Q, PT := ParCfg.HbPeriod);
IF _tHb.Q THEN _hbReq.Execute := TRUE; END_IF
_hbReq(Socket := _sock);
IF _hbReq.Done THEN
_hbReq.Execute := FALSE; _tHb(IN := FALSE);
_lastSeen := SysTime(); // synchronized clock (§2.7)
_tLoss(IN := FALSE); _linked := TRUE; _M_ClearDiag();
ELSIF _hbReq.Error THEN
_M_EnterLost(E_Reason.DEVICE_PROTOCOL_ERROR, 'Bad/again refused reply');
END_IF
// confirm loss only after LinkTimeout of no healthy beat
_tLoss(IN := NOT _linked, PT := ParCfg.LinkTimeout);
IF _tLoss.Q THEN _M_EnterLost(E_Reason.LINK_TIMEOUT, 'Heartbeat lapsed'); END_IF

_M_EnterLost sets _linked := FALSE and stamps _diag with the reason and the connector’s SourcePath; _M_Reconnect re-opens on a bounded backoff (_tBkoff, BackoffMin→BackoffMax) and never resumes a dependent command on its own.


D.3 The Control Module that fronts the device

Section titled “D.3 The Control Module that fronts the device”

FB_SupplyCM exposes ordinary device commands (OUTPUT_ON, SET_VOLTAGE) through the standard handshake. Its only addition over a plain CM is that every command first requires Linked — a lost link is adopted as the module’s fault:

// The type is ONLY its device logic: Execute/Abort arrive through ExecuteCommand/
// AbortCommand, and Busy/Done/Error/Aborted/ErrorID are base-owned (§2.2).
FUNCTION_BLOCK FB_SupplyCM EXTENDS FB_ControlModuleBase
VAR_INPUT
Command : E_PsCommand;
ParCfg : ST_PsParCfg;
ParCmd : ST_PsParCmd; // e.g. Voltage for SET_VOLTAGE — latched on the Execute rising edge
END_VAR
VAR_OUTPUT
OutCmd : ST_PsOutCmd;
OutImm : ST_PsOutImm;
END_VAR
VAR
{attribute 'OPC.UA.DA' := '0'}
_conn : FB_PsConnector;
END_VAR
METHOD Setup : BOOL
VAR_INPUT Name : STRING(80); Endpoint : STRING(255); Recipe : I_RecipeProvider; END_VAR
_conn.Setup(Name := CONCAT(Name, '.Link'), Endpoint := Endpoint, Recipe := Recipe);
// ---- cyclic body ----
METHOD PROTECTED OnCyclic
OnCyclic := SUPER^.OnCyclic();
_conn.Cyclic(); // heartbeat/session managed here
IF NOT _conn.Linked AND Busy THEN
_M_AdoptLink(); // link loss → CM fault (D.4)
END_IF
// … normal command step chain (SET_VOLTAGE → OUTPUT_ON) when Linked, in _M_Dispatch …

The loss reaction is honoured here: HOLD freezes the chain awaiting reconnect; ABORT safe-stops the command and reports Error; MODE_STOP additionally asks the owning Unit to stop after cycle (the Unit handles it in OnModeExit, §3.14).


_M_AdoptLink copies the connector’s first-out link reason up — exactly the rollup of §8.2, so the device names itself:

METHOD PRIVATE _M_AdoptLink
// Adopt the connector's first-out link reason VERBATIM — reason, SourcePath and Since (§8.2);
// the base moves the module to Error and stamps it.
_M_AdoptFault(_conn.LinkReason); // reason + "InfeedUnit.Supply1.Link" path

Concrete trace — the supply is unplugged mid-cycle:

InfeedUnit step Nxxx "Energize" ──awaits──▶ Supply1.OUTPUT_ON
Supply1 (FB_SupplyCM) ──Error────▶ adopts link reason
Supply1._conn (FB_PsConnector) ──Lost─────▶ LINK_TIMEOUT @ "InfeedUnit.Supply1.Link"

The operator sees, on the Unit’s view, through the unchanged §6.9 walk:

Step … Energize stalled → awaiting Supply1.OUTPUT_ON → InfeedUnit.Supply1.Link: heartbeat lapsed

…with no per-device diagnostic code — only the heartbeat, the standard handshake, and the recursive GetFaultSummary.


Station ▸ Supply1 (CM tile: state LED ← ExecState; link LED ← Linked)
└─ Link last seen 12:04:51 · "heartbeat lapsed" [Reconnect]
View Binding
Tile name; state LED ← ExecState; link LED ← _conn.Linked.
Detail manual OUTPUT_ON/SET_VOLTAGE (release-gated, §7.6); last-seen ← LastSeen; live LinkReason.Description; Reconnect (release-gated). No auto-resume of the interrupted command — resumption is a deliberate operator/sequence step.

  • A networked smart device as a first-class Control Module via I_DeviceConnector, with the protocol confined to the connector (§3.15).
  • Link supervision: heartbeat, LinkTimeout, and a configured HOLD/ABORT/MODE_STOP reaction — the networked analogue of an interlock.
  • Bounded reconnect with no self-resume (§3.15, mirroring the safety re-energize rule §9.3).
  • A dead link rolling up the same stall walk as any sensor fault, naming the exact device with no per-device code (§6.9, §8.2).

End of Annex D (draft).