Skip to content

Annex J — Interoperability Mapping: Module Type Package (MTP, VDI/VDE/NAMUR 2658 / IEC 63280)

Companion to Fraktal Core (Part I); exercised through the Fraktal/TC3 binding (Part II). Core concepts projected: self-description (§3.10), command surface & handshake (§3.2, §6.1), modes (§3.4), recipe/config (§3.8), alarms (§8.3), PackML profile (§11.7 / Annex F). Status: conceptual mapping, not an implemented exporter. Fraktal has no dependency on MTP: this annex is an optional, strictly outbound projection — nothing in Core or the TC3 binding requires it, and no MTP concept (flat topology, HMI-description model) is adopted inward. The 2658 sheets and the MTP 2.0 specification are licensed standards; every element name below (state names, DataAssembly classes, operation-mode fields) must be verified against the purchased sheets before an exporter is written. This annex fixes the mapping shape and flags the mismatches honestly.

MTP (originated as VDI/VDE/NAMUR 2658 by NAMUR/ZVEI, now stewarded internationally by PROFIBUS & PROFINET International, with MTP 2.0 released 2026 and standardization on the IEC 63280 track) is the industry’s answer to the same question Fraktal answers: a manufacturer-neutral, self-describing module integrated into an orchestration layer with no bespoke driver. Its vocabulary:

  • PEA (Process Equipment Assembly) — the self-contained module with its own controller.
  • POL (Process Orchestration Layer) — the higher-level system that imports module descriptions and orchestrates.
  • MTP file — an AutomationML (IEC 62714) interface description shipped by the module vendor: communication (OPC UA nodes), HMI description, services, alarms. The logic stays in the module’s controller; the MTP describes, never contains, behaviour — exactly Fraktal’s §3.10(a′) stance that the HMI/orchestrator binds data, not code.
  • Transport is OPC UA (2658 Part 5) — Fraktal’s existing spine.

Mapping Fraktal onto MTP serves O1 (one self-description, many consumers), O4/O8 (a Fraktal station becomes consumable by any MTP-conformant DCS/POL, not only the Fraktal HMI), and protects the standard from ecosystem isolation.

Fraktal MTP (2658) Fit
Root Unit (a station) PEA Strong. A Fraktal root Unit with its OPC UA server is precisely a PEA: autonomous logic, published interface.
External line controller / DCS POL Strong. Today Annex F serves this role via PackML; MTP is the richer, discovery-capable equivalent.
Parent Unit orchestrating child EMs/CMs (internal) POL-like role Mismatch, by design: MTP’s world is a flat set of PEAs under one POL; Fraktal is a recursive forest (§3.1). The mapping exports root Units as PEAs and keeps the internal hierarchy invisible to the POL — children are implementation detail, exactly as a PEA’s internals are.
Command surface + E_ExecState handshake (§3.2, §6.1) Service with procedures + the 2658-4 service state machine Good via Annex F: the 2658-4 state machine is PackML-shaped (idle/starting/execute/completing/… plus held/paused branches). Fraktal already projects ExecState onto PackML (§11.7); the same projection drives the MTP service states. States Fraktal doesn’t natively distinguish (e.g. paused vs held) follow the Annex F mapping rules.
Mode-selected sequences (§3.4): one _M_<Mode>Chain per mode Service procedures (one service, selectable procedures) Good. A Unit’s runnable modes export as procedures of its main service; _M_Supports (§3.7) decides which procedures exist.
Recipe/config parameters (§3.8) OperationElements / ServParams (service parameters) Good. Typed, per-module, write-gated — both sides agree. Fraktal’s §7.7 write gating remains PLC-enforced (MTP does not weaken it).
Status mirror (§3.10): states, counters, diagnostics IndicatorElements (AnaView/BinView/DIntView/StringView DataAssemblies) Strong. The Status mirror fields enumerate 1:1 onto indicator DataAssemblies.
CM actuators/HAL (§3.6) ActiveElements (valve/drive/PID DataAssemblies) Partial. Fraktal deliberately hides the HAL behind the module; exporting ActiveElements is optional and read-only by default (§10.5.1’s output-force gating is a Fraktal extension MTP does not model).
Alarm log & states (§8.3, ISA-18.2 map) MTP alarm management aspect Good. Come/gone/reset-class semantics carry over; verify field names against the sheet.
HMI tree + facets (§3.13) 2658-2 HMI description (P&ID-style visual instructions) Partial, different philosophies: MTP describes a picture (P&ID topology with linked faceplates); Fraktal describes data and lets the client render. An exporter can emit a minimal 2658-2 description (one faceplate per module), but Fraktal’s tree/facet HMI is richer for discrete machinery and is not replaced.
§7.8 release reporting, §7.6.1 manual catalog, §7.7 access levels (no MTP equivalent) Fraktal extensions. Exported, if at all, as vendor-specific OPC UA nodes; they keep working for Fraktal-aware clients alongside MTP consumers.
Safety (§9, TwinSAFE/FSoE) Out of MTP’s transfer scope Agreement: both standards keep safety on the safety system; an MTP never conveys safety functions.

J.3 The export path (engineering-time, not runtime)

Section titled “J.3 The export path (engineering-time, not runtime)”

Because every Fraktal module already self-describes (§3.10: Status mirror, command catalog §7.6.1, config schema §3.8, alarm metadata §8.3), an MTP exporter is a projection, not new instrumentation:

  1. Walk a root Unit’s published structure (the same walk the HMI does).
  2. Emit the AML manifest: OPC UA server endpoint + NodeIds for each mapped DataAssembly; one service per Unit with a procedure per supported runnable mode; ServParams from the config schema; the alarm aspect from §8.3 metadata.
  3. Ship the .mtp/.aml file with the machine; the customer’s POL imports it and orchestrates the station with zero bespoke integration.

[TC3] path: Beckhoff ships MTP engineering/runtime support in TwinCAT (TE8400 / TF8400), which generates the module structure and OPC UA exposure from an MTP model. A TC3 deployment can either (a) hand-write the exporter against this annex, or (b) model the exported subset in TwinCAT MTP and bind it to the Fraktal Status mirror — evaluate both against the pinned TwinCAT version; this annex does not prescribe which.

J.4 Honest mismatches (read before implementing)

Section titled “J.4 Honest mismatches (read before implementing)”
  • Process vs discrete orientation. MTP grew in process industries (skids, batch); Fraktal is discrete-manufacturing-flavoured (stations, cycles, parts). The service/procedure model fits, but MTP has no native notion of Fraktal’s per-cycle traceability (§8.11, Annex E) — that remains on Fraktal’s own OPC UA surface.
  • Granularity of orchestration. MTP orchestrates services of whole PEAs; it does not reach inside to command a child CM. That is correct: the Fraktal boundary (§3.2 — parents command children, externals command the root) is preserved, not violated, by MTP.
  • State-machine richness. 2658-4’s service states exceed E_ExecState; the PackML projection (Annex F) is the normative bridge, and its mapping decisions (e.g. what reports as HELD) apply unchanged here.
  • No nesting — a projection choice, not a design constraint. Fraktal keeps its recursive hierarchy unchanged; MTP simply never sees it. Any subtree root could serve as the export boundary (the contract is identical at every tier), but one physical asset shall export as exactly one PEA: never expose a module and one of its ancestors as sibling PEAs, or the POL and the parent become two masters of the same child — violating §3.2. A multi-root forest exports as multiple PEAs; the forest itself is not an MTP concept.
  • Licensed source of truth. Element names in this annex come from public secondary literature; the purchased 2658 sheets / MTP 2.0 spec override this annex wherever they differ.
  • Each root Unit exports as one PEA with a valid AML manifest importable by a conformant POL.
  • Every Status-mirror field appears as the correct IndicatorElement class with a resolvable NodeId.
  • Each supported runnable mode appears as a procedure; commanding it from the POL drives the real Unit through §6.1 (verify against a POL, not just schema validation).
  • Service states track the PackML projection rules of Annex F.
  • §8.3 alarms surface in the MTP alarm aspect with come/gone consistency.
  • §7.7 gating still holds for every write reachable via MTP (POL writes are clients like any other; the PLC re-checks).
  • Fraktal-specific surfaces (§7.8 release reports, §7.6.1 manual catalog, fieldbus topology §10.5.1) remain available to Fraktal-aware clients and do not leak as unguarded MTP writes.

Built from Specification/Annexes/Annex_J_MTP_Mapping.md at revision a1163c7 of the Fraktal repository.