This document instructs an AI coding agent how to guide a programmer from an empty TwinCAT solution to a deployed, HMI-commandable Fraktal station. It is a workflow and evidence checklist, not a replacement for the normative standard. Part I and the selected platform binding remain authoritative.

When the request concerns a first project, initial deployment, commissioning, or OPC UA bring-up, the agent shall:

  1. Read AGENTS.md, Fraktal_Core_Part_I.md, the applicable binding (Fraktal_TC3_Part_II.md for TwinCAT), HMI_CONTRACT.md, this guide, and FraktalCore/PLC/TwinCAT/IMPLEMENTATION_NOTES.md before changing code.
  2. State the current phase and the evidence required to leave it. Do not mix a PLC compile failure, runtime deployment failure, OPC UA authorization issue, and HMI contract failure into one diagnosis.
  3. Reuse the Core lifecycle, module libraries, providers, topology publisher, HMI mailbox, and generic HMI. Never create station-specific HMI screens or a parallel command protocol.
  4. Build basic reusable mechanisms first, then compose project-specific behavior. Hardware addresses, electrical tags, recipes, safety mappings, and station composition belong to the application, not reusable module types.
  5. Never infer functional-safety behavior from ordinary I/O or simulate a certified result in a physical deployment. Record missing safe devices, evaluated aliases, reset rules, and output authority as blockers.
  6. Preserve user changes and record every spec/implementation reconciliation in IMPLEMENTATION_NOTES.md.
  7. Report concrete evidence: compiler version, build output, target identity, ADS port, namespace URI, browse paths, mailbox write result, acknowledgement, and PLC diagnostic key. “Ping works” is never connection acceptance.

2. Inputs to collect before implementation

Section titled “2. Inputs to collect before implementation”

The agent shall identify or explicitly mark unknown:

  • pinned TwinCAT XAE and XAR builds, controller model, operating system, PLC runtime name and ADS port;
  • approved I/O list, terminal order, process-image addresses, electrical tags, safe versus ordinary signals, and fieldbus failure policy;
  • the Unit forest, Unit/EM/CM decomposition, shared control domains, recipes, modes, commands, manual functions, and release conditions;
  • safety concept: E-stops, guards, light curtains, two-hand control, safe valve or drive outputs, reset/bridging/muting behavior, and validated safe aliases;
  • network addresses and conduits, TF6100 version, endpoint/security policy, HMI platforms, station languages, and which root Units each HMI owns;
  • project target security level, user roles, credential/certificate owner, and whether the current activity is commissioning or production;
  • where retained data lives - a project decision: a folder on the controller (FB_FilePersistMedium; on a CX/IPC with a write filter that folder needs an exclusion), the controller’s retentive memory (FB_RetainPersistMedium), or an external store a later adapter provides - and the restore policy the station declares for a lost configuration (DEFAULTS_AND_ANNUNCIATE or BLOCK_UNTIL_ACKNOWLEDGED).

Unknown mechanical or naming details may be isolated behind configuration. Unknown safety authority or ambiguous output polarity shall remain fail-closed.

  1. Draw the forest. Each station is one root FB_Unit; peer stations remain peer roots. An EM never contains a Unit. A shared cage or power arrangement is a control domain associated with multiple roots, not a super-root. A production line is the same kind of arrangement (Core §3.8e): one FB_LineData declared beside the roots and referenced by each root with SetLine, never registered as any Unit’s child.
  2. Put each hardware-bound leaf in a CM with one semantic HAL channel. Put a bounded function assembled from CMs in an EM. Put continuous modes and cycle ownership in a Unit. A networked device’s connector (robot controller, smart device) is not a CM: it is composed inside the CM that fronts it (§3.15.1), which services it every scan, so exchanging a simulated and a real connector never changes the module tree.
  3. Search Fraktal_Modules before creating a type. Prefer configuration or a small extension over a project-specific duplicate.
  4. For a new reusable CM, copy PLC/TwinCAT/scaffold/FB_TemplateCM, reserve and record its reason band, define its enum/HAL/config contract, and implement only the device CASE in _M_Dispatch plus required hooks.
  5. Keep SchemaVersion : UINT first in every configuration/recipe record. Adding or reordering fields changes the schema and requires migration or a deliberate RECIPE_INVALID fault.
  6. Use localization keys for every operator-facing string. Preserve electrical tags, addresses, identifiers, model codes, and browse paths verbatim. A reusable library type raises only std.* keys and publishes a std.moduleType.* type key; project text uses project.* keys in the project catalogue, never in the standard one.
  7. Decide what each module publishes. A module’s diagnostic is Status.Diagnostic, published once by the base; never declare or copy it in an OutImm (lint rule D2). A Unit’s OutImm holds only facts the Unit derives from its children (for example “at load position”); a child’s own state is read on the child, never copied under a second name.
  8. Classify every stop condition before writing it. A defect faults and needs a reset. A condition the operator or the process is expected to restore - a released two-hand control, lost supply air - is an interlock or process condition of the device that needs it (SetAreaSafe, SetDirectionalPermits): the device HOLDS with its outputs withdrawn and resumes by itself, and the Unit reports the hold by name. Never hand-code a Unit-level fault for a condition a child already owns.

Exit evidence: reviewed tree, reason-band allocation, explicit HAL boundary, recipe schema, command list, the defect/restorable classification of every stop condition, and no duplicate lifecycle, copied state, or station HMI code.

4. Phase B — application composition and I/O

Section titled “4. Phase B — application composition and I/O”

Create an executable application project; do not place MAIN or a task inside Fraktal_Core or Fraktal_Modules.

Recommended application ownership:

  • GVL_<Project>IO: raw %I/%Q/%M mapped symbols only;
  • <Project>IoCatalog: static tag/address/description/module-role engineering data;
  • <Project>IoDriver: the only POU that reads/writes the raw I/O GVL and maps it to semantic HALs;
  • FB_IoTopologyPublisher: reusable bounds, duplicate, health, and diagnostic join behavior;
  • simulation driver/plant: virtual commissioning only;
  • control-domain coordinator and final output authority: project infrastructure, separate from the three module tiers;
  • MAIN: setup, root declarations, the line and control-domain instances, real/simulation selection, and explicit scan order—not individual channel assignments and not application logic. A condition that drives an output, such as a pushbutton lamp, is derived in the owning Unit’s OutImm and only mapped by the driver.

Organize the application by the instance tree: a 00_System folder (MAIN, raw I/O GVLs, driver, domain coordinator, simulation) and one 0N_<Unit> folder per root Unit holding its Unit type, Sequences, Release, Recipes and Io. Never put a concrete station Unit or its mode chains in a library.

Mode chains. Each continuous mode is a separate POU extending FB_SequenceBase, owned by the application; the Unit’s _M_Dispatch only runs it. The Unit base restarts every attached chain on first scan, mode change and abort, so a project writes no reset glue; a chain keeps its own state in OnChainReset. Whether a fresh Start or an operator reset restarts or resumes a chain is the project’s policy, taken with one _M_RestartSequences() call in OnCommandStart / OnOperatorReset.

Start. A Unit’s Start() consumes its release report and nothing else: add every entry condition to the project’s release component so a refusal names itself. Conditions awaited later in the cycle (a part present, a two-hand press) are M_Await records in the chain’s wait step, which the HMI shows.

Editable data. Register every value an operator or engineer may change as a typed capability (M_RegisterConfigNumber/Duration/Flag/Choice) with its ConfigKind and an E_EngUnit: STATION_CFG for this station, PAR_CFG for the active model’s recipe (with the same range constants PrepareRecipe enforces, written back to the model’s record so a changeover keeps the edit), and LINE_CFG on the line only, with keys beginning line.. Give each a project.config.* label; the HMI groups them as station, model and line data.

Retained data. Without wiring, a station keeps its values in TwinCAT PERSISTENT data, its parameter sets in FB_LocalConfigStore and its users in the Boot directory. To keep them where the project decided (Part II TC3 §3.8b, IMPLEMENTATION_NOTES §163), declare one medium in MAIN and hand that instance to every consumer before the first cyclic call; switching medium later is the one declaration:

VAR
Storage : FB_FilePersistMedium; // or FB_RetainPersistMedium
ConfigStore : FB_MediumConfigStore; // named parameter sets on the medium
AccessUsers : FB_LocalAccessProvider;
END_VAR
VAR CONSTANT
DATA_FOLDER : STRING(160) := 'C:\ProgramData\Fraktal\<Station>\';
END_VAR
// once, at setup:
Storage.Setup(Folder := DATA_FOLDER, Where := Tc2_System.PATH_GENERIC);
ConfigStore.Setup(Medium := Storage, KeyPrefix := '<Root>.sets');
Station1.SetConfigStore(Store := ConfigStore);
Station1.SetPersistMedium(Medium := Storage); // station, owned line, every model
AccessUsers.M_UseMedium(Medium := Storage); // refused for a non-confidential medium
AccessUsers.M_UseKey(Key := '<Root>.users');
Station1.Access.Setup(Provider := AccessUsers, pAlarmLog := ADR(Station1.AlarmLog));

Then expect: the documents are read back at start and replayed through the staged set path before any configuration write is accepted, and Start names the restore until it is done; the first start on a new medium loses nothing and writes the current values as the first documents; a document confirmed and later missing, damaged or no longer fitting is a §3.8b restore loss under its key; a write the medium cannot complete holds PersistPending and raises CONFIG_PERSIST_FAILED until a retry succeeds. The retentive pool is readable over ADS, so the user table stays in the Boot directory on it. A value the composition root states every boot should not also be an editable capability, because the restore replays the document over it. The files belong to the runtime’s account; an ordinary Windows user can read them but not change them.

Every deployed root declaration shall carry the binding’s explicit publication marker. For TwinCAT TMC-Filtered publication:

PROGRAM MAIN
VAR
{attribute 'OPC.UA.DA' := '1'}
Station1 : FB_StationUnit;
END_VAR

The instance name, Setup/FB_init name, schematic name, and OPC UA browse name shall agree.

Do not add the enable marker to an FB type definition. A separately published GVL value uses the same immediate-variable form:

{attribute 'qualified_only'}
VAR_GLOBAL
{attribute 'OPC.UA.DA' := '1'}
Topology : ST_FieldbusTopology;
END_VAR

Before building, run powershell -File "FraktalCore/PLC/TwinCAT/Tests/tools/Test-OpcUaPublication.ps1". It rejects definition-level enable markers, misplaced GVL markers, and persistent pointer/interface/reference fields without an immediate DA=0.

Exit evidence: application/library separation, instance-tree folders, one source for each I/O tag, validated topology mapping, explicit root markers, chains on FB_SequenceBase, every Start condition in the release report, every editable value registered with kind, unit and label, the retained-data medium and restore policy chosen and wired, and documented scan order.

5. Phase C — simulation and automated acceptance

Section titled “5. Phase C — simulation and automated acceptance”
  1. Supply a simulation HAL/plant for each reusable type.
  2. Run the inherited base suite and each type’s T2/T3/T5 rows. Composites and Units also prove their tier rows, rollup, mode support, recipe transaction, stop, and no-self-resume behavior.
  3. Exercise HOME, AUTO, CHANGEOVER, MANUAL releases, each recipe, every first-out timeout, fieldbus loss, control-domain loss, and recovery without automatic restart. Prove each restorable condition HOLDS and resumes, and each defect faults and recovers with ONE operator reset.
  4. Confirm the final output authority withdraws outputs after logic evaluation; ordinary application code never grants a certified safe output.

Exit evidence: clean test report, virtual-commissioning scenario record, and all safety-dependent physical tests still marked separately for SAT.

6. Phase D — TwinCAT build and target deployment

Section titled “6. Phase D — TwinCAT build and target deployment”

Before operating XAE, read TWINCAT_XAE_WORKFLOW.md. It is the authoritative record and repeatable procedure for solution isolation, nested IEC compilation, CheckAllObjects, Core→Modules library save/install, test download/run, cleanup, and evidence capture. In particular, its hidden-XAE script is compiler-only and never authorizes target activation or a download.

  1. Pin and record XAE/XAR. A .plcproj is added to a TwinCAT XAE solution with PLC → Add Existing Item; it is not opened as a solution.
  2. Build and install Fraktal_Core as a library, then build and install Fraktal_Modules (tools/Invoke-TwinCatLibraryInstall.ps1 does both in order; the current versions are listed in AGENTS.md §5). tools/Invoke-TwinCatBuild.ps1 then compiles both libraries, the Press bench, the CoreDemo example and both test gates, warning-clean. Build the application and both applicable test gates afterwards: Tests/Fraktal_Tests.plcproj for Core/Modules and Examples/PressDemo/PressTests.plcproj for the internal Press feature-testing bench. This bench is framework integration evidence, not a real project or machine-acceptance target. Use a separate application solution, or unload/remove the Core and Modules source-library projects before adding applications that consume the installed libraries; otherwise XAE can see identical object GUIDs in source and installed copies. Native SFC POUs need no SFC/IecSfc library reference (the compiler provides SFC support). After changing a .plcproj library reference, close and reopen XAE before evaluating the next build. Run either test gate only on an isolated test runtime/ADS port with Autostart Boot Project disabled; neither is ever the machine boot application. Never load PressTests beside the deployed Press project because it links the same source objects. Before accepting the result, verify both the runner and count against the gate table in TWINCAT_XAE_WORKFLOW.md §6.3, which tools/check_consistency.py keeps equal to the source - never against a number copied elsewhere. A Core identity after attempting Press means the wrong solution was downloaded or stale Core boot data restarted on the target. Disabling source autostart does not delete previously created target boot data.
  3. Resolve the project to the intended target, add/scan the EtherCAT hardware, compare it to the approved I/O list, link process-image symbols, and verify terminal identity/order before enabling physical output authority.
  4. Enable creation and download of the PLC symbol file/TMC. Activate the configuration, download the application, create boot data when required, start the correct PLC runtime, and verify the task is cycling.
  5. Confirm the deployed runtime name and ADS port. TF6100 will import the matching Port_<ADS port>.tmc only after its server reload/restart.

Exit evidence: warning-clean application build, target/runtime identity, EtherCAT OP/mapping validation, running task, boot-project decision, and the deployed TMC corresponding to the active application.

6.9 Commissioning gates — check these BEFORE debugging “nothing moves”

Section titled “6.9 Commissioning gates — check these BEFORE debugging “nothing moves””

On first power-up of real hardware, two VAR CONSTANT gates in the application’s MAIN deliberately hold physical outputs off. They are not bugs, and chasing control logic past them wastes days:

Gate (VAR CONSTANT in MAIN) When wrong Symptom
CONTROL_CIRCUIT_MAPPING_CONFIRMED FALSE The I/O driver forces the control-circuit coils (SwitchControlOn / EnableControlOn) FALSE every cycle. The relay chain never closes, the valve-enable relays never energize, and no output moves at all — even though the actuator coils are written unconditionally.
USE_SIMULATION TRUE MAIN calls M_ClearOutputs() every cycle: outputs stay dark while the simulation driver animates the plant, so the HMI shows motion the machine never performs.

The decisive test: force the output in TwinCAT XAE. If forcing works but the PLC never drives it, it is one of these gates — the terminal, wiring and process image are already proven good.

They are constant so they cannot be flipped online; changing one is a source edit plus a download. MAIN publishes inert read-only mirrors (UseSimulation, ControlCircuitMappingConfirmed) purely so the state stays visible over ADS. Read them live with:

Terminal window
cd FraktalCore/HMI/gateway && dart run tool/probe_sim_flag.dart <amsNetId> [port]

CONTROL_CIRCUIT_MAPPING_CONFIRMED is a safety interlock: it holds the control coils off until the control-circuit electrical semantics are verified on the real cabinet. An agent must never set it — report it and stop; that verification belongs to the commissioning engineer.

Once the gate is open, the remaining “outputs still dead” causes are ordinary permits, in this order: control-power SafetyPermit / FieldbusHealthy (a withheld-power fault latches RearmRequired, so an operator reset is needed after fixing the cause), then sensor polarity — an E-stop or pressure input read with the wrong sense makes a healthy machine report unsafe and silently withholds control power.

7. Phase E — TF6100 and OPC UA commissioning

Section titled “7. Phase E — TF6100 and OPC UA commissioning”

TF6100 is installed and configured on the computer that owns the PLC runtime (the CX/IPC in a remote-runtime deployment). The Flutter HMI is an OPC UA client; it does not need another TF6100 server.

7.0 One-time server initialization (Trust-On-First-Use) — TF6100 ≥ 5.x

Section titled “7.0 One-time server initialization (Trust-On-First-Use) — TF6100 ≥ 5.x”

TF6100 setup ≥ 4.4.0 (the 5.x server shipped with TwinCAT 4026) requires a one-time TOFU initialization before it publishes any Data Access namespace. This is the single most-missed step and it mimics every other failure:

  • Symptom: the HMI connects, activates a session, but reports “no Fraktal root Unit discovered / 0 value nodes”; an Objects browse shows only Server and Initialization; NamespaceArray lists …/TF6100/Server/Initialization and not the PLC URI. This is not a symbol/TMC/ADS-port/license fault — the server is simply uninitialized and the Initialization namespace is literally its pre-init state.
  • Initialize via the OPC UA Configurator over a secured endpoint. Configure the server connection with SecurityPolicyUri = Basic256Sha256, SecurityMode = SignAndEncrypt, IdentityTokenType = UserName, and an admin identity, then Connect and complete the TrustOnFirstUse. A username/password token can only be carried on an encrypted channel — a None/SignAndEncrypt mismatch or a None endpoint yields BadIdentityTokenRejected / No matching UserTokenPolicy, so the admin login must use the secured endpoint even when a later commissioning exception uses None.
  • On a TwinCAT usermode/standalone runtime (UM-RT): the server runs with restricted rights and cannot create the OS user during TOFU — Tofu_AddStatus: Access has been denied while trying to add the user to the operating system (NetUserAdd). Pre-create the account in Windows first (elevated: net user <user> <password> /add), then initialize; the server registers the existing user as administrator in TcUaSecurityConfig.xml. On the full XAR runtime the server has the rights and this workaround is unnecessary.
  • Initialization disables the Anonymous identity token. Re-add/enable it in Security → Users/Groups only when an explicit secure-anonymous, commissioning-anonymous, or physically isolated Anonymous exception is required; activate the revised configuration afterward.

Exit evidence for 7.0: TcUaSecurityConfig.xml exists with the admin user and a secured Configurator session connects. If an Anonymous exception was selected, an anonymous browse of Objects also returns the Data Access device (not just Server/Initialization).

  1. Install/license TF6100 on the PLC target and configure a Data Access device for the intended runtime/ADS port. TF6100 5.x needs a valid license (a 7-day trial generated in XAE is enough); an unlicensed server logs No license, running in DEMO mode and will not publish. If the server cannot resolve the [BootDir] placeholder in AutoCfgSymFile (seen on UM-RT: TcReg_GetBootDir failed), set that field to the absolute boot symbol path, e.g. …\Runtimes\<runtime>\3.1\Boot\Plc\Port_<ADS port>.tmc.
  2. Use TMC-Filtered publication and reload TF6100 after downloading a changed PLC/TMC. Mark implementation-only pointer/interface/reference storage with {attribute 'OPC.UA.DA' := '0'}; it is never part of the HMI contract. The generated TMC shall carry DA=1 on every deployed root and standalone topology variable, and shall not expose _unit, _hal, _children, provider, carrier, or recipe aliases.
  3. Configure the endpoint and certificate trust. Record the gateway profile: production (default, trusted certificate + SignAndEncrypt + dedicated user), secure-anonymous (encrypted transitional commissioning), commissioning-anonymous (None/Anonymous with bounded auto-expiry), or isolated-anonymous (documented physically isolated exception). A failed secure profile shall never downgrade automatically.
  4. Only for an explicit Anonymous profile, edit the existing Anonymous user and assign it to the built-in Users group. In the Users group, grant the exact PLC namespace Browse, ReadAttribute, and ReadValue. Grant node Write only to each root Unit’s HmiRequest subtree. Write the configuration to the remote target and restart TF6100. Remove these temporary rights after commissioning on a network-connected target.
  5. Do not grant only the Unit leaf while hiding its ancestors. Objects, the Data Access device, PLC1, and MAIN must remain browsable for discovery.

The namespace URI is read from Server/NamespaceArray; do not hard-code an assumed namespace index. A typical TwinCAT runtime reports urn:BeckhoffAutomation:Ua:PLC1.

Exit evidence: secure endpoint decision, active user/group mapping, namespace/node rights, server restart, and an authorized browse showing PLC1/MAIN/<Root>/Status plus the root HmiRequest/HmiResponse mailboxes.

8. Phase F — HMI first-run configuration

Section titled “8. Phase F — HMI first-run configuration”
  1. Install the gateway and its matched Web HMI build by following WEB_HMI_GATEWAY_DEPLOYMENT.md: use FraktalSetup.exe (select Gateway + Web HMI in the wizard) for a Windows tray/kiosk deployment or the supplied systemd unit for Linux. The gateway serves the compiled Web HMI and /fraktal from one loopback listener, so a separate static web server is not required. Record the installed package hash, gateway profile, Web origin, OPC UA application identity, and assigned --write-root paths.
  2. Prove the layers independently: /livez reports a running process, /readyz reports a recent good PLC operation, / loads the compiled Web HMI, and /fraktal completes the WebSocket handshake and Fraktal discovery. For a local browser, open http://127.0.0.1:8080/. A release Web HMI derives the same-origin ws://.../fraktal or wss://.../fraktal endpoint automatically. For remote Windows-hosted browsers, select the installer’s secure remote Web HMI option, set the exact HTTPS origin, and trust the exported FraktalGatewayRootCA.crt on every authorized client. This deploys the bundled authenticated same-host HTTPS/WSS proxy while the gateway remains loopback-only. Linux/site-SSO deployments provide the equivalent proxy; never expose the gateway directly on a LAN interface.
  3. For production native Windows/Linux/Android clients, use the configured wss://<gateway>/fraktal endpoint. The same gateway protocol is implemented by native and browser clients. A direct Windows opc.tcp://<PLC host>:4840 endpoint is an explicitly logged Anonymous/None path for commissioning, troubleshooting, or a physically isolated PLC only.
  4. Select available languages. The detected locale is enabled by default; standard and project catalogs remain separate and are importable/exportable by an authorized administrator.
  5. After discovery, select the root Units this HMI may display and command. Persist this scope only after the repository reaches LIVE; an authenticated administrator may edit it later.
  6. Validate a read and an acknowledged write: inspect live mode, request a supported mode, observe HmiResponse.AckSequence, Accepted, and Diagnostic, and confirm ModeActivePublished changes. Then, logged in at the required level, edit one value in each configuration group the station has (model, station, line): a flag shows as a checkbox, a choice as a translated dropdown, a number with its unit after the field. Confirm the edit survives a model change and a restart.
  7. Test link loss. The operator shell shall disappear immediately, no command is queued across reconnect, and connection editing appears only after 30 s.

Exit evidence: installed gateway + Web HMI package/hash, liveness, PLC readiness, static page and WebSocket results, selected-language and Unit-scope record, LIVE connection, successful mailbox round trip, mode/status update, and fail-closed link-loss behavior.

Diagnose in this order and stop at the first failed layer:

Layer Evidence Failure meaning / action
IP Correct route and target identity; ping if allowed Ping proves only IP reachability. Correct cabling, route, VLAN, firewall, or wrong target.
TCP Port 4840 accepts a socket Install/start TF6100 or correct endpoint/firewall.
Channel SecureChannel opens Resolve policy/certificate/ApplicationURI mismatch.
Session Session reaches Activated Resolve IdentityToken, username/password, or trust rejection.
Namespace NamespaceArray contains the PLC Data Access URI If absent, the Data Access device/TMC was not loaded for that runtime.
Browse Objects exposes the Data Access device/PLC tree PLC URI present but only Server visible means the identity lacks active group/namespace browse rights. Write configuration to the remote target and restart TF6100.
Fraktal root <Root>/Status is browsable Check explicit root DA marker, TMC download/reload, structured publication, and correct deployed application.
Mailbox paths HmiRequest leaves are writable and HmiResponse readable Correct TF6100 node rights and verify the breadth-limited client did not report a truncated contract.
Commit Writing arguments then Sequence changes AckSequence Verify the root Unit is called cyclically, request enum ordinals match, and the active PLC application contains the mailbox handler.
Acceptance Accepted=TRUE; otherwise read Diagnostic This is a PLC release/mode/access rejection, not a transport failure. Diagnose the published key/report.
Live state Published mode/status changes Verify requested mode is supported and the HMI is watching the owning root Unit.

Before those runtime layers, a TwinCAT compile that reports every reusable type (FB_CylinderCM, FB_TwoHandStartCM, ST_CylinderHal, and similar) as unknown has not resolved Fraktal_Modules. Do not repair the resulting hundreds of member/call/type-conversion messages individually. Build and install the exact pinned Core library first, resolve that version in Modules, build and install the exact pinned Modules library, reload the application placeholders, and rebuild. Messages claiming that a named type cannot convert to the identically named type are also typical stale/duplicate library-resolution fallout.

If a native chart reports unknown SFCStepType, the fault is that POU’s SFC ObjectProperties/XmlArchive implementation block, not a missing library — native SFC needs no IecSfc reference. The compiler synthesises one implicit SFCStepType record per graphical step, so the resulting .x, ._x, .t, ._t, transition-BOOL, and assignment errors are one cascade from the malformed chart; regenerate the chart (do not repair each action or add a placeholder).

A project Unit such as FB_PressDemoUnit is different: it shall resolve from the owning application branch, not from Fraktal_Modules. If only the project Unit, its SFCs, or its Release component is unknown, verify the application’s local <Compile Include> entries before changing library references.

Additional interpretations:

  • A server hostname returned by FindServers is not itself a failure when the redirected connection reaches SessionState: Activated.
  • “Security policy not available” lines for rejected alternatives are not the failure when a permitted endpoint is subsequently selected and activated.
  • Unsupported datatype ... UXINT means TF6100 skipped a pointer-like TMC leaf. If the path belongs to the application (for example a local recipe provider), exclude that internal field from DA publication and reload the TMC. The Beckhoff-owned TwinCAT_SystemInfoVarList._AppInfo.TComSrvPtr leaf is not a Fraktal node and may be skipped; it does not explain a PLC compile failure or an otherwise missing Unit tree.
  • A first authorized browse may be larger than the unauthorized browse. The native repository caches breadth-first discovery once per session and batch reads values afterwards. It prunes unused fieldbus Nodes[] and Channels[] from their published counts. A truncated=true snapshot is a publication-scope or client-limit defect: the HMI rejects it, the gateway keeps /readyz degraded, and the operator shell stays unavailable. Do not hide it by increasing limits indefinitely.
  • If the module tree is live but a control appears unresponsive, inspect opcua-request-start, write/commit failure, acknowledgement, timeout, and HmiResponse.Diagnostic logs. Do not return to ping/TMC troubleshooting after the tree is already live.
  • TF6100 configuration and security files belong to the remote server host. Their absence on the HMI/development PC is expected.
  • If one station appears more than once, compare each candidate’s local browse name to the final segment of its qualified Status.Name. The canonical deployed root is the shallow direct PLC1/MAIN/<Root> instance. Paths through UnitRef, recipe catalogs, I/O drivers, or coordinators are reference aliases, not additional stations. Fix publication ownership where practical and confirm the HMI reports the aliases as discarded rather than passing duplicate identities to its selectors.

Before FAT/SAT completion, the agent shall require evidence that:

  • Anonymous write and SecurityPolicy=None are disabled on every network-connected production path; any permanent isolated-anonymous exception identifies its owner and proves the PLC/HMI cell is physically isolated and unrouted;
  • the HMI uses the secured wss gateway path on supported production platforms, with a provisioned OPC UA gateway identity and authenticated TLS reverse-proxy boundary;
  • the gateway and Web HMI are a matched, signed release; the installed hash, /livez, /readyz, static /, WebSocket/discovery, and fail-closed reconnect evidence are recorded separately;
  • namespace browse/read and mailbox write permissions follow least privilege;
  • PLC access policy, safety aliases, control-domain membership, fieldbus loss response, recipes, localization, documentation access, backups, boot project, and recovery procedure have been reviewed;
  • retention is proven on the target across real runtime restarts - at least two, so the newest copy of each document has been in both slots - plus one deliberately lost document and one blocked write; the data folder is excluded from the write filter and its ACL reviewed. A second FB instance standing in for a restart is not this evidence (IMPLEMENTATION_NOTES §163);
  • the final running versions of PLC, libraries, HMI, TF6100, safety project, I/O list, TMC, and configuration exports are recorded under change control.

An AI agent shall not call an anonymously writable commissioning setup production-ready. The isolated legacy exception is a documented deployment constraint, not an equivalent security posture.

11. Appendix — initial bring-up quick paths

Section titled “11. Appendix — initial bring-up quick paths”

Condensed, ordered checklists for the two most common starting points. Follow the normative phases above for anything not covered here.

11.1 Local development PC (PLC runtime + TF6100 + HMI on one Windows PC)

Section titled “11.1 Local development PC (PLC runtime + TF6100 + HMI on one Windows PC)”

Fastest loop for HMI/PLC development against the shipped press demo.

  1. Windows Developer Mode ON — required so flutter run -d windows can create plugin symlinks (start ms-settings:developers). Without it the build fails with “Building with plugins requires symlink support.”
  2. PLC: add the application .plcproj to a TwinCAT XAE solution (§6), build, enable TMC File in the PLC project Settings tab, Activate Configuration with Autostart Boot Project, and confirm the runtime is in Run. Note the ADS port — the first PLC runtime is 851, the Nth is 850 + N (the shipped press demo lands on 854 when it is the 4th project in the solution). The TMC-File step is what generates …\Boot\Plc\Port_<ADS port>.tmc; without it TF6100 has no symbol file to publish.
  3. License: in XAE SYSTEM → License, generate the TF6100 7-Day Trial (plus base TC1200/TC1100/TC1000 trials if the system is fresh) and restart. Unlicensed → No license, running in DEMO mode and no published data.
  4. Install TF6100 (close VS/XAE first; elevated): & 'C:\ProgramData\Beckhoff\TcPkg\TcPkg.exe' install TF6100.OpcUaServer.XAR -y. The package refuses while VS/XAE is running (exit 1051).
  5. Point Data Access at the running PLC (Configurator → Data Access → Add Device Type → the PLC’s ADS port). On the usermode runtime, if the server logs TcReg_GetBootDir failed/unresolved [BootDir], set the device’s symbol-file path to the absolute …\Runtimes\<runtime>\3.1\Boot\Plc\Port_<ADS port>.tmc.
  6. Initialize + optionally re-enable Anonymous (§7.0): pre-create the OS admin user (net user <user> <pw> /add), connect the Configurator over the secured endpoint (Basic256Sha256 / SignAndEncrypt / UserName) and complete TrustOnFirstUse. For the local development exception, add an Anonymous user (assign to Users), grant PLC namespace Browse/Read (+ HmiRequest Write), and Activate.
  7. Install the gateway + Web HMI: build FraktalSetup.exe as shown in WEB_HMI_GATEWAY_DEPLOYMENT.md, install it for the kiosk/development user (select Gateway + Web HMI in the wizard), and set commissioning-anonymous, --commissioning-ttl-minutes 120, and --write-root PLC1/MAIN/PneumaticPress in that instance’s gateway.args (%LOCALAPPDATA%\Fraktal\Gateway\instances\<name>\gateway.args — one instance per PLC, reachable from its own tray submenu). Restart from the tray, require Ready, then open http://127.0.0.1:8080/; the packaged Web HMI derives ws://127.0.0.1:8080/fraktal automatically. A source run_gateway.ps1 + flutter run -d chrome pair remains a development-only alternative. Direct opc.tcp://127.0.0.1:4840 remains available for transport troubleshooting but logs its Anonymous/None posture.

Usermode/standalone-runtime specifics:

  • The standalone server’s config files under C:\ProgramData\Beckhoff\TF6100-OPC-UA\… are restored to install defaults on reboot. Make persistent changes through the Configurator, not by editing those XML files.
  • A plain TcSysSrv service restart can bring TwinCAT back up in Config mode; switch it to Run (XAE, the systray, or an ADS WriteControl(AdsState.Reset) to port 10000) so the PLC runtimes and Data Access are actually live.

11.2 Brand-new Beckhoff PLC (CX / IPC, remote runtime)

Section titled “11.2 Brand-new Beckhoff PLC (CX / IPC, remote runtime)”

Same phases, with the runtime and TF6100 on the controller, engineered from a development PC.

  1. Establish an ADS route from the engineering PC to the controller (broadcast search or manual AMS NetId) and confirm the target identity — never commission by IP/ping alone (§9).
  2. Run Phases D–E for the controller target: build + install the libraries, resolve to the controller, scan and validate the EtherCAT I/O against the approved list, link the process image, enable TMC File, activate + create the boot project, and confirm the task cycles and the ADS port. If the image runs a write filter (UWF/EWF/FBWF), exclude the station’s data folder (and the TwinCAT Boot directory) before relying on any retained value.
  3. Install/license TF6100 on the controller (the CX runs the server; the HMI PC does not need its own TF6100). Apply the real or trial license on the controller.
  4. Initialize (§7.0) on the controller. On the full XAR runtime, TOFU creates the OS user directly; on a usermode/standalone image, pre-create the OS user on the controller first. Configure Data Access for the controller’s ADS port.
  5. Configure endpoint/security. Commissioning Anonymous → Users with least-privilege namespace rights only while an explicit exception profile is active (§7 step 4). Production: trusted gateway certificate, SignAndEncrypt, dedicated user; disable Anonymous/None on network-connected targets (§10).
  6. Build the matched gateway + Web HMI package and deploy it with the Windows tray installer or Linux systemd unit in WEB_HMI_GATEWAY_DEPLOYMENT.md. Prove /livez, /readyz, static /, the /fraktal WebSocket, non-empty discovery, and an acknowledged mailbox request separately. Open http://127.0.0.1:8080/ for a same-host browser; release Web builds select the same-origin gateway automatically. Native and Web remote HMIs use an authenticated TLS reverse proxy and wss://. On Windows the installer can deploy/supervise that proxy, write the exact --allow-origin, and add a local-subnet firewall rule; the exported proxy CA root still has to be trusted on each client. The gateway itself remains loopback-only (browsers cannot open raw OPC UA TCP).

Built from Specification/Guides/FIRST_PROJECT_AGENT_GUIDE.md at revision a1163c7 of the Fraktal repository.